Product information for Elsner 70802:
Applications
The room controller is used in residential and office buildings where intelligent, central control of room temperature, lighting, shading, and scene functions is required. It serves as a central control and display unit for heating and climate control, with the integrated temperature sensor measuring the current room temperature. The measured values can be combined with external values to determine a mixed value (e.g. room average), which is used for control. The functions include control of heating and cooling via integrated PI controllers, which can operate in single- or two-stage mode. Control is performed according to separate setpoints or a base setpoint. Additionally, fan-coil control for blower convectors is possible.
Functions and equipment in detail
The device offers a variety of control pages accessible via the touch display. These include a page for displaying current measured values, a bus data display with four universal display positions, temperature control with mode switching (heating/cooling), as well as control options for shading, windows (manual movement), light switches (manual switching or dimming, RGB, colour temperature, Human Centric Lighting), scenes (four scenes with call-up, storage, and status display), and a weekly time switch with eight time periods. The integrated weekly time switch enables time-controlled operation of the functions. Additionally, two info pages are available, each displaying two text objects. Device settings can be made via the display, as well as the configuration of the screen saver (clock, clock/indoor temperature/outdoor temperature alternating, off) and the key tone (switchable on and off).
Technology explained simply
The controller is designed for the KNX bus system and operates in TP1-256 mode. Communication takes place via a KNX plug-in terminal, designed for conductors with a diameter of 0.8 mm s and a stripping length of 5 mm. The nominal voltage is 30 V DC SELV, and the maximum current consumption is 18 mA. The maximum number of group addresses and assignments is 2000 each. The communication objects are available in three variants: 471, 433, and 379. After a bus voltage recovery, it takes approximately 5 seconds until data can be received. The integrated logic functions include eight AND and eight OR logic gates, each with four inputs. As inputs, switching events as well as 16 logic inputs in the form of communication objects can be used. The output of each gate can be configured as either 1 bit or 2 × 8 bits. Additionally, eight multifunction modules (calculators) are integrated, which can modify input data through calculations, condition checks, or data point type conversions. Four control value comparators enable the output of minimum, maximum, or average values, with five inputs each available for values received via communication objects. The summer compensation for cooling adjusts the setpoint temperature according to the outdoor temperature, with the characteristic curve defining the minimum and maximum setpoint temperatures.
Compatibility and accessories
The room controller is designed for integration into existing KNX systems and can communicate with other KNX devices. The four inputs support binary contacts or the temperature sensor T-NTC (article number 30516), with the measurement range for the T-NTC sensor between 40 °C and +80 °C. The maximum cable length is 3 m for the T-NTC sensor and 10 m for digital inputs. The integrated temperature sensor measures in the range of 5 °C to +60 °C. Additionally, the device measures CO2 in the range of 400 to 5000 ppm and air humidity in the range of 5 to 95 %. The devices are designed for use in rooms with an overvoltage category III and a pollution degree 2.
Mounting and installation
The device is installed into a suitable switch series, with the frame adapted to the switch series used in the building. Installation is carried out on a standard installation surface, taking into account the mounting depth of 35 mm and the mounting ring size of 55 mm × 55 mm. Installation is performed via the KNX plug-in terminal, designed for connection to the KNX bus. Configuration is done in S-Mode, with settings made via the display.
Advantages in operation
The room controller offers a central, user-friendly interface for various functions such as heating, cooling, lighting, shading, and scenes. The integrated weekly time switch enables automated control, while the logic functions (AND and OR gates, multifunction modules, control value comparators) allow flexible adaptation to specific requirements. The mixed value calculation from internal and external temperature values ensures precise control. The summer compensation optimizes cooling based on outdoor temperature. The display of CO2 and humidity values supports indoor air quality. The devices are designed for indoor use with an ambient temperature of 0 °C to +45 °C and provide stable, reliable performance in everyday operation.
Compatibility and accessories
The room controller is designed for integration into existing KNX systems and can communicate with other KNX devices. The four inputs support binary contacts or the temperature sensor T-NTC (article number 30516), with the measurement range for the T-NTC sensor between 40 °C and +80 °C. The maximum cable length is 3 m for the T-NTC sensor and 10 m for digital inputs. The integrated temperature sensor measures in the range of 5 °C to +60 °C. Additionally, the device measures CO2 in the range of 400 to 5000 ppm and air humidity in the range of 5 to 95 %. The devices are designed for use in rooms with an overvoltage category III and a pollution degree 2.
Mounting and installation
The device is installed into a suitable switch series, with the frame adapted to the switch series used in the building. Installation is carried out on a standard installation surface, taking into account the mounting depth of 35 mm and the mounting ring size of 55 mm × 55 mm. Installation is performed via the KNX plug-in terminal, designed for connection to the KNX bus. Configuration is done in S-Mode, with settings made via the display.
Advantages in operation
The room controller offers a central, user-friendly interface for various functions such as heating, cooling, lighting, shading, and scenes. The integrated weekly time switch enables automated control, while the logic functions (AND and OR gates, multifunction modules, control value comparators) allow flexible adaptation to specific requirements. The mixed value calculation from internal and external temperature values ensures precise control. The summer compensation optimizes cooling based on outdoor temperature. The display of CO2 and humidity values supports indoor air quality. The devices are designed for indoor use with an ambient temperature of 0 °C to +45 °C and provide stable, reliable performance in everyday operation.
| General | |
| Housing | Real glass, plastic |
| Display visible diagonal | 2.3" (59 mm) |
| Display resolution [pixels] | 320 × 240 |
| Colours (similar) | RAL 9010 (white), RAL 9005 (black) |
| Degree of protection | IP20 |
| Dimensions (W × H × D) mounting ring (W × H) depth | 55 mm × 55 mm × 35 mm, 71 mm × 71 mm, 7 mm |
| Weight total | ≈ 90 g |
| Ambient temperature | 0…+45°C / -5…+45°C / -5…+45°C |
| Ambient air humidity (rH) (non-condensing) | 5...95 % |
| Storage temperature | 25...+70°C |
| Over voltage category | III |
| Pollution degree | 2 |
| Inputs | |
| Number | 4 |
| Contact voltage | 3.3 V |
| Contact current | 0.33 mA |
| Temperature sensor T-NTC (No. 30516) measurement range at input | 40...+80°C |
| Maximum cable length T-NTC / digital inputs | 3 m / 10 m |
| KNX bus | |
| Medium | TP1-256 |
| Configuration mode | S-Mode |
| Maximum group addresses | 2000 |
| Maximum assignments | 2000 |
| Communication objects | 471 / 433 / 379 |
| Nominal voltage | 30V DC SELV |
| Electricity consumption | ≤ 18mA |
| Connection KNX plug-in terminal conductor diameter | 0.8 mm s |
| Connection KNX plug-in terminal stripping length | 5 mm |
| Time until data reception after bus voltage recovery | ≈ 5 s |
| Sensors | |
| CO2 measurement range | 400...5000 ppm |
| Humidity measurement range | 5...95 % |
| Temperature measurement range | 5…+60°C |
Questions & answers
What is the delivery time of Elsner 70802 Cala Touch KNX T, black?
The article Elsner 70802 Cala Touch KNX T, black is currently in stock
According to our experience the article is ready for dispatch within 5 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Elsner 70802 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Elsner 70802 Cala Touch KNX T, black always at the best possible price. We can give you a discount of 2% on Elsner 70802 Cala Touch KNX T, black if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Elsner 70802 Cala Touch KNX T, black we can offer you a price of 277,58 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.