Applications
This relay is suitable for industrial applications requiring continuous monitoring of DC power supplies, for example in systems with battery storage, photovoltaic systems, or industrial control systems. The ability to set minimum, maximum, or window monitoring allows for flexible adaptation to different operating conditions. Early detection of voltage deviations supports preventive maintenance and increases the operational safety of the entire installation.
Functions and Equipment in Detail
The device features a configurable relay function, where the output state (operating or resting position) can be set according to requirements. The pickup delay, drop-out delay, and start-up bypass time can be individually configured to avoid false alarms and optimize the response to actual disturbances. The hysteresis is adjustable in the range of 0.2 to 50 % of the pickup value, ensuring precise threshold control. A fault memory documents occurring faults, simplifying the diagnosis of malfunctions.
Technology Explained Simply
Monitoring is performed via a voltage measurement input (e+, f), which receives the DC voltage to be monitored. The auxiliary voltage (A1, A2) supplies the device with DC 24 V. The Modbus RTU interface enables communication with higher-level control systems, allowing status information, configuration, and diagnostics to be queried via a serial interface. LED indicators signal the operating status: green LED for operational readiness, red LED for faults, and yellow LEDs for Modbus communication and status indication of the two relay outputs.
Compatibility and Accessories
The relay is designed for use in enclosures and complies with the standard IEC/EN 60255-1. The Modbus RTU interface enables integration into existing automation systems. Assigning monitoring functions to the two relay outputs allows for differentiated alarm signaling, for example, pre-alarm via relay 1 and alarm via relay 2. The rated impulse withstand voltage is 6 kV/2, indicating high insulation strength.
Mounting and Installation
The device is mounted in an enclosure and connected via the designated terminals (A1/A2 for auxiliary voltage, e+/f for voltage measurement input, 11/12/14 and 21/22/24 for relay outputs). The Modbus interface is connected via terminals A and B. The start-up bypass time ensures that no reaction occurs to voltage fluctuations immediately after power-up, preventing false alarms.
Advantages in Operation
Thanks to simple configuration, reduced wiring, and the possibility of remote monitoring via Modbus RTU, maintenance effort is reduced. Differentiated fault messages and the fault memory support rapid fault localization. The combination of compact design, wide measurement range, and high functionality makes the relay a cost-efficient solution for voltage monitoring in industrial installations. Operational safety is increased by early detection of voltage deviations, which improves the availability of the installation.
The item price shown refers to 100 pieces Dold 0069324
| Technical data | |
| 1- / 3-phase | 1 |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | DC 1000 V |
| Output contacts | 2 C/O contacts |
| Width | 22,5 mm |
| Type | UG 9431 |
| Operate delay | |
| Variant | |
| Auxiliary voltage | DC 24 V |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | DC 1000 V |
Questions & answers
What is the delivery time of Dold 0069324 UG9431.12PM DC20-1000V UH=DC24V DC voltage relay, for Modbus?
The article Dold 0069324 UG9431.12PM DC20-1000V UH=DC24V DC voltage relay, for Modbus is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0069324 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0069324 UG9431.12PM DC20-1000V UH=DC24V DC voltage relay, for Modbus always at the best possible price. We can give you a discount of 2% on Dold 0069324 UG9431.12PM DC20-1000V UH=DC24V DC voltage relay, for Modbus if you choose payment in advance on ordering.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.
How many units does the article contain?
Dold 0069324 UG9431.12PM DC20-1000V UH=DC24V DC voltage relay, for Modbus is offered by us in a sales unit of 100 pieces If you need a larger quantity, you can contact us at any time. We will make a special offer for you