Dold 0067526 UG5124.82PS UH=DC20-265V 1.5mA trip circuit monitor DC40-265V
|
330,88 EUR |
|||||||||||
|
( 393,75 EUR incl. VAT ) ≈ £277.28 | ≈ $363.31 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1000801 | ||||||||||
| Mfg Part No: | 0067526 | ||||||||||
| UPC/EAN: | 4030641675264 | ||||||||||
| Weight: | 0.17 kg | ||||||||||
| Type: | UG5124.82PS UH=DC20-265V 1,5mA | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0067526:
Applications
The UG 5124 is specifically designed for monitoring trip circuits in power circuit breakers. It is used in industrial and power engineering installations where the reliability of switching operations is critical. Continuous monitoring ensures that immediate action can be taken in the event of a fault, for example by triggering an alarm or deactivating a switch. The galvanic isolation between the measuring circuit and the evaluation unit allows the use of different voltage sources, increasing flexibility in application.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, used for signaling states. Monitoring is performed via a constant current source that injects a measuring current of 1.5 mA into the circuit to be monitored. This current flows between the poles of the control voltage of the switch being monitored. If the current cannot flow due to a fault, the relay activates. The repeat accuracy is ±2 % of the set value.
Technology Explained Simply
The technology is based on a rest current principle, where a constant measuring current (1.5 mA) flows through the circuit to be monitored. The galvanic isolation of the measuring circuit from the evaluation unit is achieved via an optical isolator, ensuring safe separation between the measuring voltage and the internal electronics. The measuring voltage range is DC 40–265 V, while the auxiliary voltage for the device itself is DC 20–265 V. The constant current source limits power dissipation in the measuring circuit, as the current is largely independent of voltage. This prevents unwanted heating in the monitored circuit.
Compatibility and Accessories
The trip circuit monitor is compliant with IEC/EN 60255-1 and designed for use in industrial installations. The connection terminals are coded plug-in terminals, enabling quick device replacement. Terminal designations are A1+/A2 for auxiliary voltage, M1+/M2 for the measuring circuit, and contacts 15–18 and 25–28 for the two changeover contacts. Switching capacities are defined according to AC 15 (make: 3 A / AC 230 V, break: 1 A / AC 230 V) and DC 13 (1 A / DC 24 V). The electrical service life is 150,000 switching operations at 1 A and AC 230 V.
Mounting and Installation
The device is mounted in enclosures and is designed for installation on a 35 mm DIN rail. The connection terminals are designed for easy and secure connection. Time delay settings are adjusted directly on the front panel via rotary switches, enabling user-friendly commissioning. The connection blocks are plug-in, allowing device replacement without soldering.
Advantages in Operation
The UG 5124 offers a wide auxiliary voltage range of DC 20–265 V, simplifying adaptation to various installation conditions. Galvanic isolation and the constant current source ensure high reliability and minimize load on the monitored circuit. Separate settings for pickup and drop-out time delay allow precise adaptation to the specific requirements of the installation. Integrated LEDs (green: ON, yellow: OK, red: Error) provide visual status indication, with the yellow LED flashing during drop-out delay and the red LED flashing during pickup delay. The thermal current rating is up to 4 A per contact, with the total current limit curve defining the maximum load.
| Technical data | |
| Enclosure design | Switch cabinet |
| Output contacts | 2 C/O contacts |
| Width | 22,5 mm |
| Type | UG 5124 |
| Variant | |
| Auxiliary voltage | DC 20 - 265 V |
| Contact equipping | 2 changeover contacts |
| Measuring current | 1,5 mA |
| Measuring voltage | DC 40 - 265 V |
Questions & answers
What is the delivery time of Dold 0067526 UG5124.82PS UH=DC20-265V 1.5mA trip circuit monitor DC40-265V?
The article Dold 0067526 UG5124.82PS UH=DC20-265V 1.5mA trip circuit monitor DC40-265V is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0067526 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0067526 UG5124.82PS UH=DC20-265V 1.5mA trip circuit monitor DC40-265V always at the best possible price. We can give you a discount of 2% on Dold 0067526 UG5124.82PS UH=DC20-265V 1.5mA trip circuit monitor DC40-265V if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0067526 UG5124.82PS UH=DC20-265V 1.5mA trip circuit monitor DC40-265V we can offer you a price of 315,99 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.