Product information for Dold 0060929:
Applications
This semiconductor relay is frequently used for controlling and monitoring heating elements, motors, valves, and lighting systems. The zero-voltage switching ensures that the load circuit is activated at the next zero crossing of the sinusoidal supply voltage, reducing stress on the load and the device. For motors, a start-up bypass time must be considered in the control system if overcurrent monitoring is activated. The integrated load circuit monitoring enables rapid fault detection, for example, in cases of partial load faults, fuse failure, or thyristor defects.
Functions and Features in Detail
The device is designed as a zero-voltage switch and features two antiparallel-connected thyristors. Control is achieved via terminals A1/A2 with an auxiliary voltage of DC 24 V. The load circuit operates with a load voltage of AC 200–480 V and a load current of up to 40 A. Monitoring is performed via a PNP semiconductor alarm output operating on the idle current principle, which activates when a fault is detected. Fault conditions are indicated by a two-color LED display: green indicates no fault, red indicates a fault, and off indicates that no auxiliary voltage is present.
Technology Explained Simply
The DCB technology (Direct-Copper-Bonding process) ensures optimal heat dissipation and increases the device’s service life. The width is 45 mm, enabling compact mounting on a DIN rail. The device is equipped with a heatsink that improves heat dissipation and enhances operational reliability. The integrated load circuit monitoring continuously monitors load current and load voltage and detects deviations from the set load current value. In the event of a fault, the alarm output is activated to inform the control system.
Compatibility and Accessories
The semiconductor relay is compliant with IEC/EN 60947-4-3 and suitable for use in industrial control systems. The alarm output is PLC-compatible and can be integrated into existing control systems. Optionally, a temperature limit switch (normally open) can be inserted into the designated slot on the underside of the device to activate an over-temperature protection function. A suitable switch is, for example, the UCHIYA type UP62–100, which opens at a heatsink temperature above 100 °C.
Mounting and Installation
Mounting is done on a DIN rail, with the device equipped with a snap-on heatsink. Installation must only be carried out by a qualified electrician. Terminal designations are clearly defined: A1/A2 for control input, A3+/A2 for operating voltage and load circuit monitoring, and Alarm for the semiconductor alarm output. Connections L1 and T1 are for supply and load connection.
Operational Advantages
The device offers wear-free operation without mechanical contacts, increasing service life and reducing maintenance requirements. The zero-voltage switching minimizes electrical stress and extends the life of the load. The integrated load circuit monitoring enables reliable fault detection and indication, minimizing downtime. The combination of high I2t value and DCB technology ensures robust and reliable performance under high loads.
| Technical data | |
| Load current up to | 40 A |
| Load voltage up to | AC 480 V |
| Number of poles | 1-pole |
| On/Off Input Control | DC |
| Width | 45 mm |
| Type | PH 9270 |
| Signalling output | |
| Variant | |
| Auxiliary voltage | DC 24 V |
| Load current | AC 40 A |
| Load voltage | AC 200 - 480 V |
| Semiconductor output | 1-pole |
| Variant | Switching at zero crossing. With heigh I2t-value. Control via A1/A2 with under current monitoring and PNP transistor output with de-energized on trip. With heat sink |
Questions & answers
What is the delivery time of Dold 0060929 PH9270.91/101/02 AC200-480V AC40A semiconductor contactor UH24VDC?
The article Dold 0060929 PH9270.91/101/02 AC200-480V AC40A semiconductor contactor UH24VDC is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0060929 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0060929 PH9270.91/101/02 AC200-480V AC40A semiconductor contactor UH24VDC always at the best possible price. We can give you a discount of 2% on Dold 0060929 PH9270.91/101/02 AC200-480V AC40A semiconductor contactor UH24VDC if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 5 pieces of Dold 0060929 PH9270.91/101/02 AC200-480V AC40A semiconductor contactor UH24VDC we can offer you a price of 204,11 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.