Product information for Xaver Bechtold 10130406:
Applications
The cable is designed for use in industrial control systems, where reliable signal transmission between control devices and drives is required. It is commonly used in production plants, assembly lines, and material handling systems, where mechanical stresses of moderate intensity occur. Use in wet or damp environments is possible due to the PVC insulation and sheath, although the cable is not intended for permanent underwater application.
Functions and equipment in detail
The cable features seven conductors with a cross-section of 1.0 mm², one of which is a green-yellow protective earth conductor. The conductors are marked with a continuous numerical designation, enabling easy identification and wiring. The conductors consist of bare, fine-stranded copper wires according to VDE 0295 class 5, ensuring high flexibility and durability during mobile installation. The conductor insulation and the outer sheath are made of PVC, making the cable largely resistant to mechanical stresses and chemical influences such as acids, alkalis, and certain hydrocarbon compounds.
Technology explained simply
The designation YSLY-JZ describes the cable according to standard VDE 0888-100. Here, Y stands for the PVC sheath, S for the protective earth conductor configuration, L for the stranded structure of the conductors, Y for the PVC insulation of the conductors, and JZ for the marking with continuous numbers and a green-yellow protective earth conductor. The rated voltage is 300/500 V, which is sufficient for most industrial control applications. The test voltage of 4000 V ensures electrical strength. The temperature resistance is -5 °C to +70 °C for mobile installation and -40 °C to +80 °C for fixed installation. The bending radius is 4 times the cable diameter for fixed installation and 15 times for flexible applications, defining the mechanical load capacity. Flame retardancy corresponds to VDE 0472 part 804, test type B (equivalent to IEC 332-1), ensuring limited flame spread in the event of a short circuit or fire.
Compatibility and accessories
The control cable is suitable for use with standard connectors, terminals, and switching devices in industrial environments. The numbered marking of the conductors simplifies wiring and maintenance. The cable can be combined with other YSLY control cables, especially in plants requiring uniform cable design. The use of protective earth conductors (JZ) is required if the plant is to be earthed.
Installation and mounting
Installation is carried out by fixed routing in cable ducts, trays, or on cable trees. For flexible applications, the cable must be moved without tensile stress, and the specified bending radius must be observed. The cable is not intended for routing in moving parts such as cable loops or in cable carriers, as the mechanical stresses are higher there. Mounting is done using standard tools such as cable cutters and cable crimpers.
Advantages in operation
The cable offers high mechanical and chemical resistance, extending its service life in industrial environments. The clear marking of the conductors reduces errors during installation and maintenance. The PVC insulation and sheath provide good insulation and protection against external influences. Flame retardancy increases operational safety, especially in plants with increased fire risk.
The item price shown refers to 100 meters Xaver Bechtold 10130406
| General | |
| Nominal voltage | 300/500 V |
| Test voltage | 4000 V |
| Temperature range in motion | -5 to +70 °C |
| Temperature range, non-operating | -40 to +80 °C |
| Bend radius for fixed installation | 4 x cable diameter |
| Bend radius flexible | 15 x cable diameter |
| Flame retardancy | VDE 0472 T. 804 test type B (IEC = 332-1) |
| Conductor | Copper stranded wire, bare, fine-stranded in accordance with VDE 0295 Class 5 |
| Wire insulation | PVC |
| Sheath | PVC |
| Conductor marking | Continuous digit printing with green-yellow protective conductor in accordance with VDE 0293-308 |
| Number of cores | 7 piece |
| Core cross section | 1,0 mm² |
| Jacket colour | Grey |
| Chemical resistance | Resistant to acids, alkalis, certain hydrocarbon compounds |
Questions & answers
What is the delivery time of Xaver Bechtold 10130406 YSLY-JZ 7G1.0 mm² 100 m ring Eca PVC control cable with numbered conductors?
The article Xaver Bechtold 10130406 YSLY-JZ 7G1.0 mm² 100 m ring Eca PVC control cable with numbered conductors is currently in stock
According to our experience the article is ready for dispatch within 3 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Xaver Bechtold 10130406 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Xaver Bechtold 10130406 YSLY-JZ 7G1.0 mm² 100 m ring Eca PVC control cable with numbered conductors always at the best possible price. We can give you a discount of 2% on Xaver Bechtold 10130406 YSLY-JZ 7G1.0 mm² 100 m ring Eca PVC control cable with numbered conductors if you choose payment in advance on ordering.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.
How many units does the article contain?
Xaver Bechtold 10130406 YSLY-JZ 7G1.0 mm² 100 m ring Eca PVC control cable with numbered conductors is offered by us in a sales unit of 100 meters If you need a larger quantity, you can contact us at any time. We will make a special offer for you