Rittal 7859410 PSM measurement module with CAN bus, 8x C13 switchable
|
625,49 EUR |
|
|
( 744,33 EUR incl. VAT ) ≈ £523.54 | ≈ $687.41 plus delivery charges: 55,00 € |
|
| Delivery time from supplier's stock (ca.) 12 workdaysinfo_outline | |
| In Stock: >50 pieces | |
| Datasheet: | file_download Download |
|---|---|
| Lieske Part No.: | 147694 |
| Mfg Part No: | 7859410 |
| UPC/EAN: | 4028177801844 |
| Weight: | 1 kg |
| Type: | DK 7859410 |
Product information for Rittal 7859410:
Applications
The module is ideal for applications requiring detailed energy consumption analysis and remote control of consumers. It is particularly suitable for retrofitting existing PSM installations to improve energy efficiency and optimise operating costs. Compatibility with the European PSM programme enables flexible integration into existing systems. Use in redundant systems is supported by the ability to switch power circuits by rotating the module. The operating temperature ranges from 5 °C to 60 °C, allowing application in standardised server rooms and industrial environments.
Functions and Equipment in Detail
The module features integrated energy measurement with an accuracy of ±1 %. Measured parameters include voltage (V), current (A), frequency (Hz), active power (kW), active energy (kWh), reactive power (kVar), reactive energy (kVarh), apparent power (kVA), apparent energy (kVAh), power factor (cosPhi), and crest factor. Additionally, an operating hour counter (in days, hours, minutes) is maintained. The measured values can be displayed locally on a backlit LC display, which turns red when current or power thresholds are exceeded. The thresholds for voltage, current, and active power are freely configurable. The switching function is performed by bistable double-coil relays with a switching capacity of 4,000 VA per relay. The outputs can be controlled individually or in groups via the CMC III system.
Technology Explained Simply
The module is powered via the CMC III system with a nominal operating voltage of 18 V to 24 V DC. Communication with the CMC III is via CAN-Bus, with two CAN-Bus interfaces and two RJ45 connectors available. Network functionality includes IPv4, IPv6, SNMPv3, Modbus/TCP, and OPC-UA, but only in conjunction with the CMC III system. Data transmission enables central visualisation of switching states on the CMC III website and in the RiZone platform. Alarms can be managed via email or SMS, and rights management allows restriction of switching functionality. A position sensor ensures that the display and web view are correctly shown in 90° increments.
Compatibility and Accessories
The module is compatible with the European PSM programme and can be integrated into existing PSM installations. It supports up to 16 PSM modules on a CMC III-PU (per IP address) and up to 4 on a PU Compact. Suitable accessories include the PDU Metered 16A/1P IEC-C20 6xC13 (48,3 cm ( 19 inch )), which provides additional power distribution with metering function. The use of universal socket locks enables securing of unused sockets.
Mounting and Installation
Mounting is simple and touch-protected via Plug & Play, even during operation. The module is easy to install and remove, enabling flexible use at different locations. Installation requires two module slots in the PSM power rail. The delivery includes the PSM metering module with CAN-Bus and a CAN-Bus connection cable with a length of 1 m.
Operational Advantages
The module facilitates compliance with requirements from ISO 50001 and EN 50600-2-2, which relate to energy efficiency and energy management. Local display and remote control enable efficient operational monitoring. High measurement accuracy and configurable thresholds support proactive fault detection and prevention. Integrated alarm management and rights management increase security and control over power distribution. The maximum operating altitude is 2,000 m above sea level, and the relative humidity (non-condensing) ranges from 10 % to 90 %. The protection rating IP 20 according to IEC 60 529 protects against finger contact and solid foreign objects, but not against water or dust. The operating temperature ranges from 5 °C to 60 °C, and the storage temperature from -20 °C to 70 °C.
Materials and Design
The socket inserts are made of plastic (PA6 GF 30 V1), and the profile is made of anodised aluminium. Dimensions are 500 mm length, 53 mm width, and 45 mm depth. The module is designed for indoor use and complies with the Low Voltage Directive 2014/35/EU and the EMC Directive 2014/30/EU. Standards EN 50 600-2-2 and EN 60950 are met. The pollution degree class is 2, indicating an environment with low pollution.
Monitoring and Control
Monitoring is performed via the CMC III system, which can manage alarms via email or SMS. Switching states are visualisable on the CMC III website and in the RiZone platform. Rights management enables fine-grained control of switching functions. The measurement functions are resettable and can be reset via software or at intervals (e.g. active energy kWh, operating hour counter h).
| General | |
| Material | Socket inserts: Plastic (PA6 GF 30 V1), Profile: Aluminium, anodised |
| Scope of delivery | PSM measurement modules with CAN-Bus, CAN-Bus connection cable, 1 m |
| Distribution power per module | 3.680 W |
| Switching power per relay | 4.000 VA |
| Length | 500 mm |
| Pollution degree | 2 |
| Interface bus system | 2 x CAN-Bus interface to CMC III (max. 16 at PU/4 at PU Compact), 2 x RJ45 (connection to CMC) |
| Number | 1 |
| Relay version | Double coil, bistable |
| Rated operating voltage | 18 V (DC) - 24 V (DC), power supply via CMC III system |
| Input voltage | 230 V AC |
| Input voltage tolerance | ± 10 % |
| Nominal current | 16 A |
| Required module slots (number) | 2 |
| Number of participants PU compact (max.) | 4 |
| Number of participants PU (max.) | 16 |
| Policies | Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU |
| Degree of protection IP according to IEC 60 529 | IP 20 |
| Monitoring | Alarm management via CMC III (e.g. email or SMS), visualisation of switching status on CMC III website and RiZone, up to 16 PSM modules on one CMC III PU (per IP address), rights management via CMC III (e.g. restriction of switching functionality) |
| Standards | EN 50 600-2-2, EN 60950 |
| Description of measurement functions | Voltage V, current A, frequency Hz, active power kW, active energy kWh, reactive power kVar, reactive energy kVarh, apparent power kVA, apparent energy kVAh, power factor cosPhi, crest factor (peak factor), operating hour counter d, h, min, measurement accuracy of ± 1 %, measurement functions resettable/reset via software/interval measurement: active energy kWh, operating hour counter h, thresholds (voltage, current, power) freely configurable |
| Protocols | Network functionality (only in combination with CMC III system): IPv4, IPv6, SNMPv3, Modbus/TCP, OPC-UA |
| Width | 53 mm |
| Depth | 45 mm |
| Maximum operating altitude above sea level | 2.000 m |
| Operating temperature range | 5 °C...60 °C |
| Humidity (non-condensing) | 90 % |
| Socket outlets | 8 x C13 |
| Relative humidity (non-condensing) | 10 % |
| Storage temperature range | -20 °C...70 °C |
| PCF/VE (Cradle-to-Gate) | 3.8 kg CO2 eq (Cat B) |
| Note on PCF class | Category B: PCF value (Cradle-to-Gate) approximately calculated based on product weight and self-declared |
Questions & answers
What is the delivery time of Rittal 7859410 PSM measurement module with CAN bus, 8x C13 switchable?
The article Rittal 7859410 PSM measurement module with CAN bus, 8x C13 switchable is currently in stock
According to our experience the article is ready for dispatch within 12 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Rittal 7859410 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Rittal 7859410 PSM measurement module with CAN bus, 8x C13 switchable always at the best possible price. We can give you a discount of 2% on Rittal 7859410 PSM measurement module with CAN bus, 8x C13 switchable if you choose payment in advance on ordering.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.
This product is recommended as accessory for
|
Rittal 7030100 Interface CMC III Can-Bus Sensor
With the CMC III CAN bus sensor, sensors of the previous system CMC-TC can be connected to the CMC III system. One CMC-TC sensor can be connected to each CMC III CAN bus sensor.Benefits: Fast ... Lieske Part No.: 360252 Mfg Part No: 7030100 Type: DK 7030100 |
-11% 87,29 EUR 98,60 EUR
![]() ≈ £73.06 | ≈ $95.93
Made to order · Delivery time approx. 5 workdaysinfo_outline
|
Fitting accessory for Rittal 7859410 PSM measurement module with CAN bus, 8x C13 switchable
|
Rittal 7979202 PDU Metered 16A/1P IEC-C20 6xC13 (48,3 cm ( 19 inch ))
The Rittal DK 7979202 is a 48,3 cm ( 19 inch ) power distribution unit (PDU) with integrated energy measurement, specifically designed for use in IT network and server racks. It enables precise ...Lieske Part No.: 1980388 Mfg Part No: 7979202 Type: DK 7979202 |
657,92 EUR
![]() ≈ £550.68 | ≈ $723.05
Delivery time from supplier's stock (ca.) 12 workdaysinfo_outline
|