Elsner 70822 Cala Touch KNX AQS/TH, black, KNX sensor for CO2, temperature, humidity
|
439,00 EUR 457,48 EUR |
|||||||||||
|
( 522,41 EUR incl. VAT ) ≈ £365.69 | ≈ $481.58 plus delivery charges: 55,00 € |
|||||||||||
| Delivery time from supplier's stock (ca.) 5 workdaysinfo_outline | |||||||||||
| In Stock: >5 pieces | |||||||||||
| Lieske Part No.: | 701111 | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Mfg Part No: | 70822 | ||||||||||
| UPC/EAN: | 4051996708223 | ||||||||||
| Weight: | 0.123 kg | ||||||||||
| Type: | 70822 | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Elsner 70822:
Applications
The room controller is designed for integration into building automation systems, particularly in residential and office buildings, where intelligent control of room climate and lighting functions is required. It serves as a central interface for capturing environmental data such as CO2 concentration, temperature, and humidity, enabling automated control of ventilation and heating systems. The integrated weekly time switch with eight time periods supports time-based control of functions. The device can also be used as a secondary station for operating another controller, allowing flexible adaptation to existing systems.
Functions and Equipment in Detail
The device features a touch display showing various control pages, including a page for displaying current measurement values, a menu page for device settings, and pages for temperature control, lighting control (switching, dimming, RGB, colour temperature, Human Centric Lighting), shading, window functions, scene control, and bus information. The integrated weekly time switch enables time-based control of functions. There are eight AND and eight OR logic gates, each with four inputs, which can be used to link switching and communication objects. The outputs of the logic gates can be configured as either 1 bit or 2 x 8 bits. Additionally, eight multifunction modules are integrated, enabling calculations, condition checks, or data point type conversions. An integrated setpoint comparator can compare received values and output them. The measurement values for CO2, temperature, and humidity can be used to control threshold-dependent switching outputs. The thresholds can be set via parameters or through communication objects.
Technology Explained Simply
The room controller operates within the KNX network via the TP1-256 medium and supports the S-Mode as a configuration mode. The nominal voltage is 30 V DC SELV, and the current consumption is up to 18 mA. The maximum number of group addresses and assignments is 2000 each. Communication objects are available in three variants: 471, 433, or 379, depending on configuration. The KNX plug terminal supports wire diameters from 0.6 to 0.8 mm and requires a stripping length of 5 mm. After bus voltage is restored, it takes approximately 5 seconds before data can be received. The integrated sensors measure CO2 in the range of 400 to 5000 ppm, relative humidity from 5 to 95 %, and temperature from 5 to +60 °C. An external temperature sensor T-NTC (item 30516) can be connected to one of the four inputs, with a measurement range of 40 to +80 °C for this sensor. The maximum cable length for the T-NTC sensor is 3 m, and for digital inputs, it is 10 m. The contact voltage of the inputs is 3.3 V, and the contact current is 0.33 mA. The sensors enable the calculation of mixed values, with the proportion of internal and external measurement values being adjustable in percentage. Additionally, the bus message checks whether the values for temperature and humidity lie within the comfort zone (DIN 1946), and the dew point is calculated.
Compatibility and Accessories
The device is designed for use in a KNX network and can communicate with other KNX components. It supports integration of external sensors, particularly the temperature sensor T-NTC (item 30516), which can be connected to one of the four inputs. Control of ventilation, heating, and cooling is performed via integrated PI controllers operating based on temperature, humidity, or CO2 concentration. Ventilation control can be single- or two-stage, as can heating and cooling control. Fan-coil control for fan convectors is also supported. Device functions can be linked via communication objects and logic gates, enabling complex control logics.
Mounting and Installation
Mounting is done in a standard installation mounting ring with dimensions 71 mm × 71 mm. The device is installed into the wall plate, with a mounting depth of 7 mm. Installation requires connection to the KNX bus via the integrated plug terminal. The connection cables must be prepared according to the specified stripping length of 5 mm. Device configuration is performed via the S-Mode, with settings made through the touch display. Device settings include configuration of display and control pages, logic gates, multifunction modules, and thresholds for sensor data.
Advantages in Operation
The room controller offers comprehensive control capabilities for room climate and lighting functions within a KNX network. The integrated sensors enable precise capture of environmental conditions, allowing efficient and comfortable control of ventilation, heating, and lighting. The weekly time switch and logic gates enable flexible and automated control. The touch interface is intuitive to use and provides a clear display of current values and functions. Integration into existing KNX systems is simple and does not require additional components. Settings can be made directly on the device via the display, enabling quick adaptation to changing requirements. The device functions are designed for indoor use and meet safety and reliability requirements in building automation.
| General | |
| Housing | Real glass, plastic |
| Display visible diagonal | 2.3" (59 mm) |
| Display resolution [pixels] | 320 × 240 |
| Colours (similar) | RAL 9010 (white), RAL 9005 (black) |
| Degree of protection | IP20 |
| Dimensions (W × H × D) mounting ring (W × H) depth | 55 mm × 55 mm × 35 mm, 71 mm × 71 mm, 7 mm |
| Weight total | ≈ 90 g |
| Ambient temperature | 0…+45°C / -5…+45°C / -5…+45°C |
| Ambient air humidity (rH) (non-condensing) | 5...95 % |
| Storage temperature | 25...+70°C |
| Over voltage category | III |
| Pollution degree | 2 |
| Inputs | |
| Number | 4 |
| Contact voltage | 3.3 V |
| Contact current | 0.33 mA |
| Temperature sensor T-NTC (No. 30516) measurement range at input | 40...+80°C |
| Maximum cable length T-NTC / digital inputs | 3 m / 10 m |
| KNX bus | |
| Medium | TP1-256 |
| Configuration mode | S-Mode |
| Maximum group addresses | 2000 |
| Maximum assignments | 2000 |
| Communication objects | 471 / 433 / 379 |
| Nominal voltage | 30V DC SELV |
| Electricity consumption | ≤ 18mA |
| Connection KNX plug-in terminal conductor diameter | 0.6…0.8 mm s |
| Connection KNX plug-in terminal stripping length | 5 mm |
| Time until data reception after bus voltage recovery | ≈ 5 s |
| Sensors | |
| CO2 measurement range | 400...5000 ppm |
| Humidity measurement range | 5...95 % |
| Temperature measurement range | 5…+60°C |
Questions & answers
What is the delivery time of Elsner 70822 Cala Touch KNX AQS/TH, black, KNX sensor for CO2, temperature, humidity?
The article Elsner 70822 Cala Touch KNX AQS/TH, black, KNX sensor for CO2, temperature, humidity is currently in stock
According to our experience the article is ready for dispatch within 5 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Elsner 70822 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Elsner 70822 Cala Touch KNX AQS/TH, black, KNX sensor for CO2, temperature, humidity always at the best possible price. We can give you a discount of 2% on Elsner 70822 Cala Touch KNX AQS/TH, black, KNX sensor for CO2, temperature, humidity if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Elsner 70822 Cala Touch KNX AQS/TH, black, KNX sensor for CO2, temperature, humidity we can offer you a price of 432,42 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.