Dold 0070147 RN5897.12/300/61 DC12-24V insulation monitor 10k-250k 20k-1M
|
459,13 EUR |
|||||||||||
|
( 546,36 EUR incl. VAT ) ≈ £384.75 | ≈ $504.12 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1001684 | ||||||||||
| Mfg Part No: | 0070147 | ||||||||||
| UPC/EAN: | 4030641701475 | ||||||||||
| Weight: | 0.335 kg | ||||||||||
| Type: | RN5897.12/300/61 DC12-24V | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0070147:
Applications
This device is suitable for monitoring IT systems in various application areas, particularly in mobile and industrial environments where high safety and reliability of the electrical installation are required. It is suitable for networks with frequency converters, battery networks, and DC drives, where insulation faults are often difficult to detect. Its application in hybrid and battery vehicles, as well as in mobile power generators, is explicitly supported, with device parameterization adaptable to the specific requirements of these systems.
Functions and Equipment in Detail
The insulation monitor features two independently adjustable threshold settings, which can be used for pre-alarm and alarm functions. The adjustment range for the pre-alarm value is between 20 kOhm and 1 MOhm, and for the alarm value between 10 kOhm and 250 kOhm. Adjustment is performed via three rotary switches on the device front, enabling user-friendly parameterization. Operating states are visualized via a multicolored device status LED, informing the user of the current device status. An automatic and manual self-test ensures functional verification of the device, with the test sequence indicated via the LED.
Technology Explained Simply
The device measures insulation resistance between the test terminals L(+) and L(-) as well as the protective earth terminals PE1 and PE2. An active test voltage pulse with alternating polarity is used to detect both symmetrical and asymmetrical insulation faults. Monitoring also occurs in de-energized networks, ensuring continuous safety functionality. A switchable connection monitoring for the test circuit L(+) / L(-) generates a fault message if one of the terminals is not connected with low resistance. Monitoring of protective earth terminals PE1/PE2 for wire breakage is not switchable and provides an additional safety function.
Compatibility and Accessories
The device is designed for network leakage capacitances up to 30 μF and can be used in AC, DC, and mixed AC/DC networks. The auxiliary voltage is supplied via terminals A1(+) and A2 with DC 12–24 V. The contact configuration includes two changeover contacts, with one designated for pre-alarm and another for alarm. The operating or resting current principle for the alarm relays is adjustable, enabling flexible integration into existing alarm systems. An external control input (X1, X2) allows connection of a combined test/reset button.
Mounting and Installation
The device is designed as an installation distributor and has a width of 52.5 mm, enabling mounting in standard control panels. The connection terminals are clearly labeled: A1(+) and A2 for auxiliary voltage, L(+) and L(-) for the test circuit, PE1 and PE2 for protective earth, and X1 and X2 for the external control input. Terminals PE1 and PE2 must be connected to the protective earth system via separate conductors. The device front is equipped with a tamper-proof transparent cover, protecting against unauthorized manipulation.
Advantages in Operation
The insulation monitor provides preventive fire and system protection through early detection of insulation faults. The adjustability of threshold values allows application-specific adaptation, enabling alarm functions to be optimally matched to the respective installation. Alarm memory is selectable, enabling error tracking. Simple operation via rotary switches and visual indication via LED reduce maintenance and operational effort. The device requires no additional pre-stage device, simplifying installation and reducing system costs.
| Technical data | |
| Approvals | UL |
| Classification | For mobile power generators |
| Enclosure design | Distribution board |
| IMD type | AC, AC/DC, DC |
| Nominal voltage IT system | AC 0 - 230 V, DC 0 - 230 V |
| Response value | 10 - 250 kΩ |
| Response value type | Adjustable |
| Width | 52,5 mm |
| Type | RN 5897/300 |
| Earth fault indicator | |
| Variant | |
| Alarm value | 10 - 250 kOhm |
| Auxiliary voltage | DC 12 - 24 V |
| Contact equipping | 2 x 1 changeover contact |
| Prewarning value | 20 kOhm - 1 MOhm |
| Approvals and Markings | UL-listed C/US, CCC |
Questions & answers
What is the delivery time of Dold 0070147 RN5897.12/300/61 DC12-24V insulation monitor 10k-250k 20k-1M?
The article Dold 0070147 RN5897.12/300/61 DC12-24V insulation monitor 10k-250k 20k-1M is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0070147 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0070147 RN5897.12/300/61 DC12-24V insulation monitor 10k-250k 20k-1M always at the best possible price. We can give you a discount of 2% on Dold 0070147 RN5897.12/300/61 DC12-24V insulation monitor 10k-250k 20k-1M if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0070147 RN5897.12/300/61 DC12-24V insulation monitor 10k-250k 20k-1M we can offer you a price of 438,47 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.