Dold 0070147, EAN: 4030641701475

Dold 0070147 RN5897.12/300/61 DC12-24V insulation monitor 10k-250k

Dold 0070147 RN5897.12/300/61 DC12-24V insulation monitor 10k-250k

Lieske Part No. 1001684
Mfg Part No 0070147
EAN-Code 4030641701475
Manufacturer Dold
Here only 459,13 EUR
546,36 EUR incl. VAT

Further information for Dold 0070147 RN5897.12/300/61 DC12-24V insulation monitor 10k-250k

Technical data
ApprovalsUL
ClassificationFor mobile power generators
Enclosure designDistribution board
IMD typeAC, AC/DC, DC
Nominal voltage IT systemAC 0 - 230 V, DC 0 - 230 V
Response value10 - 250 kΩ
Response value typeAdjustable
Width52,5 mm
TypeRN 5897/300
Earth fault indicatorYes
Variant
Alarm value10 - 250 kOhm
Auxiliary voltageDC 12 - 24 V
Contact equipping2 x 1 changeover contact
Prewarning value20 kOhm - 1 MOhm
Approvals and MarkingsUL-listed C/US, CCC
The insulation monitor RN5897.12/300/61 DC12-24V from Dold is a device of the VARIMETER IMD family for monitoring insulation quality in IT systems. It is specifically designed for mobile power generators and meets the requirements of DIN VDE 0100-551. The device monitors ungrounded networks with alternating, direct, or mixed voltage up to a maximum of 300 V and is therefore universally applicable in installations such as UPS systems, networks with frequency converters, battery networks, DC drives, hybrid and battery vehicles, as well as mobile power generators. Insulation monitoring is performed in accordance with IEC/EN 61557-8, ensuring standardized and reliable fault detection.

Applications
This device is suitable for monitoring IT systems in various application areas, particularly in mobile and industrial environments where high safety and reliability of the electrical installation are required. It is suitable for networks with frequency converters, battery networks, and DC drives, where insulation faults are often difficult to detect. Its application in hybrid and battery vehicles, as well as in mobile power generators, is explicitly supported, with device parameterization adaptable to the specific requirements of these systems.

Functions and Equipment in Detail
The insulation monitor features two independently adjustable threshold settings, which can be used for pre-alarm and alarm functions. The adjustment range for the pre-alarm value is between 20 kOhm and 1 MOhm, and for the alarm value between 10 kOhm and 250 kOhm. Adjustment is performed via three rotary switches on the device front, enabling user-friendly parameterization. Operating states are visualized via a multicolored device status LED, informing the user of the current device status. An automatic and manual self-test ensures functional verification of the device, with the test sequence indicated via the LED.

Technology Explained Simply
The device measures insulation resistance between the test terminals L(+) and L(-) as well as the protective earth terminals PE1 and PE2. An active test voltage pulse with alternating polarity is used to detect both symmetrical and asymmetrical insulation faults. Monitoring also occurs in de-energized networks, ensuring continuous safety functionality. A switchable connection monitoring for the test circuit L(+) / L(-) generates a fault message if one of the terminals is not connected with low resistance. Monitoring of protective earth terminals PE1/PE2 for wire breakage is not switchable and provides an additional safety function.

Compatibility and Accessories
The device is designed for network leakage capacitances up to 30 μF and can be used in AC, DC, and mixed AC/DC networks. The auxiliary voltage is supplied via terminals A1(+) and A2 with DC 12–24 V. The contact configuration includes two changeover contacts, with one designated for pre-alarm and another for alarm. The operating or resting current principle for the alarm relays is adjustable, enabling flexible integration into existing alarm systems. An external control input (X1, X2) allows connection of a combined test/reset button.

Mounting and Installation
The device is designed as an installation distributor and has a width of 52.5 mm, enabling mounting in standard control panels. The connection terminals are clearly labeled: A1(+) and A2 for auxiliary voltage, L(+) and L(-) for the test circuit, PE1 and PE2 for protective earth, and X1 and X2 for the external control input. Terminals PE1 and PE2 must be connected to the protective earth system via separate conductors. The device front is equipped with a tamper-proof transparent cover, protecting against unauthorized manipulation.

Advantages in Operation
The insulation monitor provides preventive fire and system protection through early detection of insulation faults. The adjustability of threshold values allows application-specific adaptation, enabling alarm functions to be optimally matched to the respective installation. Alarm memory is selectable, enabling error tracking. Simple operation via rotary switches and visual indication via LED reduce maintenance and operational effort. The device requires no additional pre-stage device, simplifying installation and reducing system costs.