Applications
The insulation monitor is universally applicable in systems with rated voltages up to AC 230 V or DC 230 V. When used with an external pre-stage device (e.g. RL 5898, RP 5898 or RR 5898), higher voltages can be monitored, up to AC 1000 V and DC 1500 V. The maximum network capacitance is 1000 μF, and the device offers optimized response time at high capacitances. Monitoring also occurs when the network is de-energized, ensuring continuous safety functionality.
Functions and Equipment in Detail
The device features two independently adjustable threshold settings: a pre-alarm level (Pre-Alarm) ranging from 20 kΩ to 2 MΩ and an alarm level from 1 kΩ to 250 kΩ. Adjustment is performed via two rotary switches on the front of the device, enabling user-friendly parameterization. Measured values, device parameters, and operating status are displayed on a multi-colored illuminated display. The display allows for quick fault localization through selective earth fault detection for L+ and L-. A trigger output is provided for connection to an insulation fault detection system.
Technology Explained Simply
The insulation monitor measures the insulation resistance between the network conductors and the protective earth conductor PE. When the set threshold values are exceeded, an alarm is triggered. Measurement is performed via a measuring circuit connected to the network under surveillance through terminals L(+) and L(-). The auxiliary voltage is supplied via terminals A1(+) and A2 and is rated at AC/DC 24 to 60 V. The response time is optimized based on the setting of the maximum network capacitance. An automatic and manual self-test ensures device functionality verification. Alarm memory is selectable, and wire break monitoring of the measuring circuit can be disabled, while monitoring of the protective earth connection PE1/PE2 cannot be disabled.
Compatibility and Accessories
The device can be operated both without a pre-stage device and with external pre-stage devices RL 5898, RP 5898 or RR 5898. The pre-stage devices extend the voltage range and enable monitoring of higher rated voltages. Combining with a pre-stage device requires observing the maximum network voltages and connection examples. The auxiliary voltage is available in three wide voltage ranges, with the specified variant using AC/DC 24 to 60 V.
Mounting and Installation
The insulation monitor is designed as an installation distributor with a width of 52.5 mm. Mounting is performed in standard distributor enclosures. The connection terminals are clearly labeled, with auxiliary voltage supplied via A1(+) and A2. Connections L(+) and L(-) are directly connected to the network under surveillance. The PE1/PE2 terminals are used for connection to the protective earth conductor. A tamper-proof transparent cover protects the device against unauthorized manipulation.
Advantages in Operation
Selective earth fault detection for L+ and L- enables quick fault localization. The two independent threshold settings allow for differentiated alarm signaling, e.g. for pre-alarm and alarm. Display of the current insulation resistance and device status on the display supports maintenance and diagnostics. Monitoring even when the network is de-energized ensures continuous safety functionality. Simple adjustment via rotary switches and the option for external control via a test/reset input enhance the device’s usability and flexibility. Certifications UL-listed C/US, CCC and DNV confirm suitability for use in various markets and application areas.
| Technical data | |
| Approvals | DNV, UL |
| Enclosure design | Distribution board |
| IMD type | AC, AC/DC, DC |
| Nominal voltage IT system | AC 0 - 230 V, AC 0 - 1000 (Coupling device) V, DC 0 - 230 V, DC 0 - 1500 (Coupling device) V |
| Response value | 1 - 250 kΩ |
| Response value type | Adjustable |
| Width | 52,5 mm |
| Type | RN 5897/010 |
| Earth fault indicator | |
| Variant | |
| Alarm value | 1 - 250 kOhm |
| Auxiliary voltage | AC/DC 24 - 60 V |
| Contact equipping | 2 x 1 changeover contact |
| Prewarning value | 20 kOhm - 2 MOhm |
| Approvals and Markings | UL-listed C/US, CCC, DNV |
Questions & answers
What is the delivery time of Dold 0070011 RN5897.12/010/61 AC/DC24-60V insulation monitor 1k-250k 20k-2M?
The article Dold 0070011 RN5897.12/010/61 AC/DC24-60V insulation monitor 1k-250k 20k-2M is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0070011 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0070011 RN5897.12/010/61 AC/DC24-60V insulation monitor 1k-250k 20k-2M always at the best possible price. We can give you a discount of 2% on Dold 0070011 RN5897.12/010/61 AC/DC24-60V insulation monitor 1k-250k 20k-2M if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 3 pieces of Dold 0070011 RN5897.12/010/61 AC/DC24-60V insulation monitor 1k-250k 20k-2M we can offer you a price of 604,20 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.