Dold 0069298 LK5895.12/801/61 DC24V 1k-250k insulation monitor 1k-250k
|
2.322,39 EUR |
|||||||||||
|
( 2.763,64 EUR incl. VAT ) ≈ £1,946.16 | ≈ $2,549.98 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1001670 | ||||||||||
| Mfg Part No: | 0069298 | ||||||||||
| UPC/EAN: | 4030641692988 | ||||||||||
| Weight: | 0.5 kg | ||||||||||
| Type: | LK5895.12/801/61 DC24V 1k-250k | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0069298:
Applications
The insulation monitor is universally applicable in IT systems with a rated voltage up to 1000 V AC or DC. It is suitable for installations such as photovoltaic systems, UPS systems, networks with frequency converters, battery networks, and DC drives. Monitoring is also performed when the network is de-energized, making it suitable for applications with intermittent power supply. The maximum network capacitance is 3000 μF, allowing even systems with high capacitance to be monitored.
Functions and Equipment in Detail
The device features two 1-changeover contacts, one for pre-alarm and one for alarm. The trip values are adjustable: the alarm value ranges from 1 kΩ to 250 kΩ, and the pre-alarm value ranges from 20 kΩ to 2 MΩ. The current insulation resistance is displayed via an LED chain, visually indicating the status. Additionally, the operating status of the measuring circuit is indicated by a separate LED. Measuring circuit monitoring includes wire break detection at terminals L(+) and L(-), preventing false alarms due to broken conductors.
Technology Explained Simply
Insulation monitoring is performed according to standard IEC/EN 61557-8. The device detects both symmetrical and asymmetrical insulation faults. The measuring circuit can be deactivated via control terminals, for example, during network coupling. The output relays can operate in either energized or de-energized mode, with the setting adjusted via control terminals G and R. An automatic and manual device self-test ensures functional reliability. Alarm memory is selectable, and external test and reset buttons can be connected.
Compatibility and Accessories
The device is designed for IT systems with AC and DC voltages up to 1000 V. It is intended for use in enclosures, with a width of 90 mm. The auxiliary voltage is DC 24 V. Approvals include UL-listed C/US and UKCA. The terminal connections allow integration into existing control systems, with signals such as DC auxiliary voltage, measuring circuit connection, protective earth, and control inputs clearly labeled.
Mounting and Installation
Mounting is done in an enclosure. The terminal connections are clearly labeled, with the assignment of L(+), L(-), KE, PE, G, R, T, HM, and relay contacts (11-14 for alarm, 21-24 for pre-alarm) directly visible on the device. The trip value settings are adjusted using a screwdriver on the rotary switches on the front. The LED indicators allow for quick visual control of the operating status.
Advantages in Operation
The insulation monitor provides preventive fire and system protection through early detection of insulation faults. Selective earth fault detection according to L+ and L- enables fast fault localization. Optimized measurement times are typically shorter than with conventional methods. The integrated wire break detection and the ability to deactivate the measuring circuit via control terminals increase the reliability and flexibility of the device. No additional pre-stage device is required, simplifying installation.
| Technical data | |
| Approvals | UL |
| Classification | For photovoltaic systems |
| Enclosure design | Switch cabinet |
| IMD type | AC, AC/DC, DC |
| Nominal voltage IT system | AC 0 - 1000 V, DC 0 - 1000 V |
| Response value | 1 - 250 kΩ |
| Response value type | Adjustable |
| Width | 90 mm |
| Type | LK 5895 |
| Earth fault indicator | |
| Variant | |
| Alarm value | 1 - 250 kOhm |
| Auxiliary voltage | DC 24 V |
| Contact equipping | 2 x 1 changeover contact |
| Prewarning value | 1 - 250 kOhm |
| Approvals and Markings | UL-listed C/US, UKCA |
| Variant | With wire-break detection at L(+)/L(-). Analogue output with linear output function to indicate the insulation resistance value. With adapted measurement algorithm |
Questions & answers
What is the delivery time of Dold 0069298 LK5895.12/801/61 DC24V 1k-250k insulation monitor 1k-250k?
The article Dold 0069298 LK5895.12/801/61 DC24V 1k-250k insulation monitor 1k-250k is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0069298 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0069298 LK5895.12/801/61 DC24V 1k-250k insulation monitor 1k-250k always at the best possible price. We can give you a discount of 2% on Dold 0069298 LK5895.12/801/61 DC24V 1k-250k insulation monitor 1k-250k if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 2 pieces of Dold 0069298 LK5895.12/801/61 DC24V 1k-250k insulation monitor 1k-250k we can offer you a price of 2.217,88 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.