Dold 0069291 LK5895.12/801/61 DC24V 1k–250k insulation monitor 20k–2M
|
2.322,39 EUR |
|||||||||||
|
( 2.763,64 EUR incl. VAT ) ≈ £1,946.16 | ≈ $2,549.98 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1001672 | ||||||||||
| Mfg Part No: | 0069291 | ||||||||||
| UPC/EAN: | 4030641692919 | ||||||||||
| Weight: | 0.5 kg | ||||||||||
| Type: | LK5895.12/801/61 DC24V 1k-250k | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0069291:
Insulation monitoring is achieved via an integrated measurement circuit that remains active even when the network is de-energized. The trip thresholds are easily and user-friendly adjustable via two ratchet rotary switches on the front of the device. The alarm threshold ranges from 1 kΩ to 250 kΩ, and the pre-alarm threshold ranges from 20 kΩ to 2 MΩ. These adjustment ranges allow flexible adaptation to different system conditions. The measurement is performed using an adapted measurement algorithm that optimizes response time for network capacitances up to 3000 μF.
Functions and equipment in detail include two independent relay contacts: one for pre-alarm and one for alarm, each configured as 1 changeover contact. The current insulation resistance is displayed via an LED bar, visually indicating the status. Additionally, a green PWR LED lights up when supplied with DC auxiliary voltage. Device states such as measurement circuit activity, earth fault, or internal faults are also indicated by LEDs. An automatic and manual self-test ensures functional verification of the device.
Technology explained simply is based on VARIMETER IMD technology, enabling selective earth fault detection for L+ and L−, which supports rapid fault localization. The measurement circuits can be deactivated via control terminals, for example, during network coupling. Power supply is via DC 24 V, and the device continues to monitor even when the network is de-energized. Wire break detection at L(+) and L(−) provides additional safety by detecting interruptions in the measurement circuit. An analog output with a linear output function enables display of the insulation resistance.
Compatibility and accessories include use in various application areas such as photovoltaics, battery systems, and hybrid vehicles. The device is designed for network capacitances up to 3000 μF and does not require an additional pre-stage device. The control terminals allow connection of external test and reset buttons, as well as selection between memory behavior and hysteresis behavior. The operating or rest current principle for the output relays is selectable, facilitating integration into existing circuits.
Mounting and installation is carried out in an enclosure with a width of 90 mm. The connection terminals are clearly labeled: A1+ and A2 for DC auxiliary voltage, L(+) and L(−) for the measurement circuit, KE and PE for the protective conductor, and G, R, T, and HM for control and test functions. Adjustment is done with a screwdriver, making operation simple and clear.
Advantages in operation include preventive fire and system protection, rapid fault localization, and universal applicability in various IT systems. The optimized measurement times are typically shorter than with conventional methods, increasing responsiveness. The display of insulation resistance via the LED bar enables quick visual inspection of the system status. The integrated measurement circuit monitoring for wire break enhances system reliability.
Approvals and markings include UL-listed C/US and UKCA, enabling use in various markets. The device is classified for use in photovoltaic systems and meets safety and reliability requirements for such systems. The device class LK 5895 is part of the VARIMETER IMD family, known for its reliability in industrial electrical engineering.
| Technical data | |
| Approvals | UL |
| Classification | For photovoltaic systems |
| Enclosure design | Switch cabinet |
| IMD type | AC, AC/DC, DC |
| Nominal voltage IT system | AC 0 - 1000 V, DC 0 - 1000 V |
| Response value | 1 - 250 kΩ |
| Response value type | Adjustable |
| Width | 90 mm |
| Type | LK 5895 |
| Earth fault indicator | |
| Variant | |
| Alarm value | 1 - 250 kOhm |
| Auxiliary voltage | DC 24 V |
| Contact equipping | 2 x 1 changeover contact |
| Prewarning value | 20 kOhm - 2 MOhm |
| Approvals and Markings | UL-listed C/US, UKCA |
| Variant | With wire-break detection at L(+)/L(-). Analogue output with linear output function to indicate the insulation resistance value. With adapted measurement algorithm |
Questions & answers
What is the delivery time of Dold 0069291 LK5895.12/801/61 DC24V 1k–250k insulation monitor 20k–2M?
The article Dold 0069291 LK5895.12/801/61 DC24V 1k–250k insulation monitor 20k–2M is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0069291 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0069291 LK5895.12/801/61 DC24V 1k–250k insulation monitor 20k–2M always at the best possible price. We can give you a discount of 2% on Dold 0069291 LK5895.12/801/61 DC24V 1k–250k insulation monitor 20k–2M if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 2 pieces of Dold 0069291 LK5895.12/801/61 DC24V 1k–250k insulation monitor 20k–2M we can offer you a price of 2.217,88 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.