Further information for Dold 0069291 insulation monitor DC24V 1k-250k

Technical data
ApprovalsUL
ClassificationFor photovoltaic systems
Enclosure designSwitch cabinet
IMD typeAC, AC/DC, DC
Nominal voltage IT systemAC 0 - 1000 V, DC 0 - 1000 V
Response value1 - 250 kΩ
Response value typeAdjustable
Width90 mm
TypeLK 5895
Earth fault indicatorYes
Variant
Alarm value1 - 250 kOhm
Auxiliary voltageDC 24 V
Contact equipping2 x 1 changeover contact
Prewarning value20 kOhm - 2 MOhm
Approvals and MarkingsUL-listed C/US, UKCA
VariantWith wire-break detection at L(+)/L(-). Analogue output with linear output function to indicate the insulation resistance value. With adapted measurement algorithm
The insulation monitor LK5895.12/801/61 from Dold is a device for monitoring insulation quality in IT systems, particularly in ungrounded AC, DC, and mixed AC/DC networks with a nominal voltage up to 1000 V. It is specifically designed for use in photovoltaic systems, including those with thin-film technology, as well as in UPS systems, networks with frequency converters, battery networks, and DC drives. The device enables precise and reliable detection of insulation faults, detecting both symmetrical and asymmetrical faults. Monitoring is carried out in accordance with the standard IEC/EN 61557-8, ensuring compliance with international standards for insulation monitoring.

Insulation monitoring is achieved via an integrated measurement circuit that remains active even when the network is de-energized. The trip thresholds are easily and user-friendly adjustable via two ratchet rotary switches on the front of the device. The alarm threshold ranges from 1 kΩ to 250 kΩ, and the pre-alarm threshold ranges from 20 kΩ to 2 MΩ. These adjustment ranges allow flexible adaptation to different system conditions. The measurement is performed using an adapted measurement algorithm that optimizes response time for network capacitances up to 3000 μF.

Functions and equipment in detail include two independent relay contacts: one for pre-alarm and one for alarm, each configured as 1 changeover contact. The current insulation resistance is displayed via an LED bar, visually indicating the status. Additionally, a green PWR LED lights up when supplied with DC auxiliary voltage. Device states such as measurement circuit activity, earth fault, or internal faults are also indicated by LEDs. An automatic and manual self-test ensures functional verification of the device.

Technology explained simply is based on VARIMETER IMD technology, enabling selective earth fault detection for L+ and L−, which supports rapid fault localization. The measurement circuits can be deactivated via control terminals, for example, during network coupling. Power supply is via DC 24 V, and the device continues to monitor even when the network is de-energized. Wire break detection at L(+) and L(−) provides additional safety by detecting interruptions in the measurement circuit. An analog output with a linear output function enables display of the insulation resistance.

Compatibility and accessories include use in various application areas such as photovoltaics, battery systems, and hybrid vehicles. The device is designed for network capacitances up to 3000 μF and does not require an additional pre-stage device. The control terminals allow connection of external test and reset buttons, as well as selection between memory behavior and hysteresis behavior. The operating or rest current principle for the output relays is selectable, facilitating integration into existing circuits.

Mounting and installation is carried out in an enclosure with a width of 90 mm. The connection terminals are clearly labeled: A1+ and A2 for DC auxiliary voltage, L(+) and L(−) for the measurement circuit, KE and PE for the protective conductor, and G, R, T, and HM for control and test functions. Adjustment is done with a screwdriver, making operation simple and clear.

Advantages in operation include preventive fire and system protection, rapid fault localization, and universal applicability in various IT systems. The optimized measurement times are typically shorter than with conventional methods, increasing responsiveness. The display of insulation resistance via the LED bar enables quick visual inspection of the system status. The integrated measurement circuit monitoring for wire break enhances system reliability.

Approvals and markings include UL-listed C/US and UKCA, enabling use in various markets. The device is classified for use in photovoltaic systems and meets safety and reliability requirements for such systems. The device class LK 5895 is part of the VARIMETER IMD family, known for its reliability in industrial electrical engineering.