Product information for Dold 0066428:
Applications
The phase monitor is used in installations that require stable and symmetrical network voltage. It is particularly suitable for monitoring three-phase networks, where correct phase sequence is essential for the proper rotation direction of motors. Detection of phase failures or missing neutral conductor enables preventive maintenance and prevents damage to installations. The function is also usable in single-phase networks with a measurement range of 100 to 300 V, although the device variant RN9877.11/120/61 is specifically designed for 3/N AC 175–525 V.
Functions and equipment in detail
The device features a function selector switch that allows selection between various monitoring functions such as overvoltage, undervoltage, voltage range exceedance, phase asymmetry, and phase failure. Selection is made without complex menu navigation, simplifying commissioning and maintenance. Upon detection of a fault, the relay switches the output via a 1-changeover contact, enabling, for example, activation of a safety power supply or triggering an alarm. The indication of the failed phase is provided by LED indicators, enabling quick fault localization.
Technology explained simply
The required power is generated from the measurement voltage of all three phases, reducing wiring effort. The switching delay is adjustable in the range of 0 to 30 seconds to filter out short-term voltage fluctuations and avoid unnecessary switching operations. An adjustable hysteresis ensures that the relay only returns to the good state after exceeding a defined threshold, increasing the stability of the installation. Measurement is performed in both 3-phase and 1-phase systems, with operation possible with or without neutral conductor connection.
Compatibility and accessories
The device is designed for use in installation distributors and complies with the standard IEC/EN 60255-1. It is UL-listed C/US, certifying its approval for use in North America. The width is 52.5 mm, making it suitable for standard distributor enclosures. The connection terminals are designed for direct connection to the phase conductors (L1, L2, L3) and the neutral conductor (N). The output contacts (11, 12, 14) allow integration into existing control and protection systems.
Mounting and installation
Mounting is carried out in an installation distributor. The connection terminals are clearly labeled (L1, L2, L3, N) and allow for simple and error-free wiring. Adjustment of the monitoring functions is performed via a rotary selector switch mounted directly on the device. The LED indicators provide visual feedback on the operating status and facilitate commissioning and diagnosis.
Advantages in operation
Early detection of voltage anomalies and phase faults increases operational safety. Preventive maintenance helps avoid damage to motors or installations. High repeatability and a wide measurement voltage range ensure reliable operation under various operating conditions. Simple operation and integrated LED display reduce maintenance effort and increase system availability.
| Technical data | |
| 1- / 3-phase | 1, 3 |
| Approvals | UL |
| Auxiliary voltage | Without |
| Enclosure design | Distribution board |
| Measuring range max. | 525 V |
| Output contacts | 1 C/O contact |
| Standard measuring range | 3/N AC 175 - 525 V / 100 - 300 V |
| Width | 52,5 mm |
| Type | RN 9877 |
| Variant | |
| Contact equipping | 1 changeover contact |
| Measuring voltage | 3/N AC 175 - 525 V |
| Switching delay | 0 - 30 s |
| Approvals and Markings | UL-listed C/US |
| Variant | Detect phase failure. Indications of the missing phase via LED. Can be used with or without neutral |
Questions & answers
What is the delivery time of Dold 0066428 RN9877.11/120/61 3/N AC175-525/ phase monitor 0-30 s 100-300 V?
The article Dold 0066428 RN9877.11/120/61 3/N AC175-525/ phase monitor 0-30 s 100-300 V is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0066428 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0066428 RN9877.11/120/61 3/N AC175-525/ phase monitor 0-30 s 100-300 V always at the best possible price. We can give you a discount of 2% on Dold 0066428 RN9877.11/120/61 3/N AC175-525/ phase monitor 0-30 s 100-300 V if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 5 pieces of Dold 0066428 RN9877.11/120/61 3/N AC175-525/ phase monitor 0-30 s 100-300 V we can offer you a price of 166,32 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.