| Technical data |
| 1- / 3-phase | 1, 3 |
| Approvals | UL |
| Auxiliary voltage | Without |
| Enclosure design | Distribution board |
| Measuring range max. | 525 V |
| Output contacts | 1 C/O contact |
| Standard measuring range | 3/N AC 175 - 525 V / 100 - 300 V |
| Width | 52,5 mm |
| Type | RN 9877 |
| Variant |
| Contact equipping | 1 changeover contact |
| Measuring voltage | 3/N AC 175 - 525 V |
| Switching delay | 0 - 30 s |
| Approvals and Markings | UL-listed C/US |
| Variant | Detect phase failure. Indications of the missing phase via LED. Can be used with or without neutral |
The Dold phase monitor RN9877.11/120/61 is an industrial measuring relay type from the VARIMETER series, specifically designed for monitoring 3-phase and 1-phase alternating voltages in the range of AC 175 to 525 V. The device is used for continuous monitoring of electrical networks to detect fault conditions such as overvoltage, undervoltage, phase asymmetry, incorrect phase sequence, and phase failure at an early stage. It is suitable for use in industrial installations, particularly with motor loads such as pumps or motors, where a safe and reliable power supply is critical.
Applications
The phase monitor is used in installations that require stable and symmetrical network voltage. It is particularly suitable for monitoring three-phase networks, where correct phase sequence is essential for the proper rotation direction of motors. Detection of phase failures or missing neutral conductor enables preventive maintenance and prevents damage to installations. The function is also usable in single-phase networks with a measurement range of 100 to 300 V, although the device variant RN9877.11/120/61 is specifically designed for 3/N AC 175–525 V.
Functions and equipment in detail
The device features a function selector switch that allows selection between various monitoring functions such as overvoltage, undervoltage, voltage range exceedance, phase asymmetry, and phase failure. Selection is made without complex menu navigation, simplifying commissioning and maintenance. Upon detection of a fault, the relay switches the output via a 1-changeover contact, enabling, for example, activation of a safety power supply or triggering an alarm. The indication of the failed phase is provided by LED indicators, enabling quick fault localization.
Technology explained simply
The required power is generated from the measurement voltage of all three phases, reducing wiring effort. The switching delay is adjustable in the range of 0 to 30 seconds to filter out short-term voltage fluctuations and avoid unnecessary switching operations. An adjustable hysteresis ensures that the relay only returns to the good state after exceeding a defined threshold, increasing the stability of the installation. Measurement is performed in both 3-phase and 1-phase systems, with operation possible with or without neutral conductor connection.
Compatibility and accessories
The device is designed for use in installation distributors and complies with the standard IEC/EN 60255-1. It is UL-listed C/US, certifying its approval for use in North America. The width is 52.5 mm, making it suitable for standard distributor enclosures. The connection terminals are designed for direct connection to the phase conductors (L1, L2, L3) and the neutral conductor (N). The output contacts (11, 12, 14) allow integration into existing control and protection systems.
Mounting and installation
Mounting is carried out in an installation distributor. The connection terminals are clearly labeled (L1, L2, L3, N) and allow for simple and error-free wiring. Adjustment of the monitoring functions is performed via a rotary selector switch mounted directly on the device. The LED indicators provide visual feedback on the operating status and facilitate commissioning and diagnosis.
Advantages in operation
Early detection of voltage anomalies and phase faults increases operational safety. Preventive maintenance helps avoid damage to motors or installations. High repeatability and a wide measurement voltage range ensure reliable operation under various operating conditions. Simple operation and integrated LED display reduce maintenance effort and increase system availability.