Product information for Dold 0057213:
Applications
This relay is suitable for use in industrial and railway applications where reliable voltage monitoring is required. It monitors DC and AC voltages within the measurement range of AC 5 to 50 V. Galvanic isolation between the auxiliary circuit and the measurement circuit ensures safe and interference-free measurement. The maximum rated voltage is AC 1000 V and DC 900 V, with the maximum permissible continuous voltage in the measurement range of AC 5–50 V being 500 V. The measurement frequency can reach up to 5 kHz, enabling use in dynamic systems.
Functions and Features in Detail
The device features two changeover contacts as output contacts, which can be used to control auxiliary circuits or alarms. The auxiliary voltage is supplied via AC/DC 24 to 80 V. The switching delay t_v delays switching after exceeding the set value, preventing reactions to short-term voltage spikes. The pickup delay is also integrated to ensure stable response to voltage fluctuations. The start-up bypass is not available in this variant.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measurement voltage. For AC voltages, the device is calibrated to the RMS value. Settings are adjusted via rotary switches, allowing both the pickup value and the hysteresis value to be set. The hysteresis depends on the set value to ensure stable switching behavior. LED indicators signal operational readiness (green LED) and activation of the output relay (yellow LED). The width is 45 mm, enabling installation in standard enclosures.
Compatibility and Accessories
The relay complies with IEC/EN 60255-1 and IEC/EN 60947-1 standards. It is designed for use in industrial installations where high overload capacity and reliability are required. Galvanic isolation between the measurement and auxiliary circuits enables safe integration into existing systems. The UKCA and CCC certifications are available for this variant.
Mounting and Installation
Mounting is performed in enclosures with a width of 45 mm. The terminal connections are clearly labeled: A1/A2 for auxiliary voltage, e/f for measurement voltage input, and contacts 11-14 and 21-24 for the two changeover contacts. Installation requires no special tools, as settings are adjusted via rotary switches on the front panel. The terminal connections are designed for secure connections.
Operational Advantages
Early detection of voltage anomalies enables preventive maintenance and prevents damage to electrical devices. LED indicators simplify diagnosis and fault localization. The switching delay reduces false triggers caused by short-term voltage spikes. High overload capacity and galvanic isolation increase reliability and safety during operation. The device is designed for use in demanding environments where continuous and precise monitoring is required.
| Technical data | |
| 1- / 3-phase | 1 |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | AC 1000 V, DC 900 V |
| Output contacts | 2 C/O contacts |
| Width | 45 mm |
| Type | BA 9054 |
| Operate delay | |
| Variant | |
| Auxiliary voltage | AC/DC 24 - 80 V |
| Contact equipping | 2 changeover contacts |
| Measuring range | AC 5 - 50 V |
| Start up delay | Without |
| Switching delay | 0 - 20 s |
| Approvals and Markings | UKCA, CCC |
| Variant | Overvoltage relay. Energized on trip. Time delay at setting value |
Questions & answers
What is the delivery time of Dold 0057213 BA9054/010 AC5-50V UH=AC/DC24-80V voltage relay Tv=0-20s?
The article Dold 0057213 BA9054/010 AC5-50V UH=AC/DC24-80V voltage relay Tv=0-20s is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0057213 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0057213 BA9054/010 AC5-50V UH=AC/DC24-80V voltage relay Tv=0-20s always at the best possible price. We can give you a discount of 2% on Dold 0057213 BA9054/010 AC5-50V UH=AC/DC24-80V voltage relay Tv=0-20s if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0057213 BA9054/010 AC5-50V UH=AC/DC24-80V voltage relay Tv=0-20s we can offer you a price of 310,99 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.