Further information for Dold 0057213 voltage relay AC5-50V UH=AC/DC24-80V
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Nominal voltage max.
AC 1000 V, DC 900 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9054
Operate delay
Variant
Auxiliary voltage
AC/DC 24 - 80 V
Contact equipping
2 changeover contacts
Measuring range
AC 5 - 50 V
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overvoltage relay. Energized on trip. Time delay at setting value
The voltage relay BA9054/010 from Dold is an overvoltage relay of the VARIMETER series, designed for monitoring single-phase DC and AC voltage networks. It is used for early detection of voltage anomalies to prevent electrical system failures and enhance operational safety. The device operates on the principle of operating current and switches when the set threshold value is exceeded, with the switching delay adjustable between 0 and 20 seconds. Device settings are adjusted via rotary switches on the front panel, enabling simple and user-friendly configuration.
Applications
This relay is suitable for use in industrial and railway applications where reliable voltage monitoring is required. It monitors DC and AC voltages within the measurement range of AC 5 to 50 V. Galvanic isolation between the auxiliary circuit and the measurement circuit ensures safe and interference-free measurement. The maximum rated voltage is AC 1000 V and DC 900 V, with the maximum permissible continuous voltage in the measurement range of AC 5–50 V being 500 V. The measurement frequency can reach up to 5 kHz, enabling use in dynamic systems.
Functions and Features in Detail
The device features two changeover contacts as output contacts, which can be used to control auxiliary circuits or alarms. The auxiliary voltage is supplied via AC/DC 24 to 80 V. The switching delay t_v delays switching after exceeding the set value, preventing reactions to short-term voltage spikes. The pickup delay is also integrated to ensure stable response to voltage fluctuations. The start-up bypass is not available in this variant.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measurement voltage. For AC voltages, the device is calibrated to the RMS value. Settings are adjusted via rotary switches, allowing both the pickup value and the hysteresis value to be set. The hysteresis depends on the set value to ensure stable switching behavior. LED indicators signal operational readiness (green LED) and activation of the output relay (yellow LED). The width is 45 mm, enabling installation in standard enclosures.
Compatibility and Accessories
The relay complies with IEC/EN 60255-1 and IEC/EN 60947-1 standards. It is designed for use in industrial installations where high overload capacity and reliability are required. Galvanic isolation between the measurement and auxiliary circuits enables safe integration into existing systems. The UKCA and CCC certifications are available for this variant.
Mounting and Installation
Mounting is performed in enclosures with a width of 45 mm. The terminal connections are clearly labeled: A1/A2 for auxiliary voltage, e/f for measurement voltage input, and contacts 11-14 and 21-24 for the two changeover contacts. Installation requires no special tools, as settings are adjusted via rotary switches on the front panel. The terminal connections are designed for secure connections.
Operational Advantages
Early detection of voltage anomalies enables preventive maintenance and prevents damage to electrical devices. LED indicators simplify diagnosis and fault localization. The switching delay reduces false triggers caused by short-term voltage spikes. High overload capacity and galvanic isolation increase reliability and safety during operation. The device is designed for use in demanding environments where continuous and precise monitoring is required.