Dold 0057106 BA9054/010 AC0.5-5V AC/DC80-230V voltage relay Tv=0-100S
|
335,41 EUR |
|||||||||||
|
( 399,14 EUR incl. VAT ) ≈ £280.74 | ≈ $368.62 plus delivery charges: 55,00 € |
|||||||||||
| Made to order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1583471 | ||||||||||
| Mfg Part No: | 0057106 | ||||||||||
| UPC/EAN: | 4030641571061 | ||||||||||
| Weight: | 0.23 kg | ||||||||||
| Type: | BA9054/010 AC0,5-5V AC/DC80-230V | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0057106:
Applications
This relay is intended for use in industrial and railway applications where reliable voltage monitoring is required. It monitors DC and AC voltages in the range of AC 0.5 to 5 V, making it suitable for applications with low measurement voltages. The galvanic isolation between auxiliary and measurement circuits ensures safe and interference-free measurement, even at high network voltages. Typical application areas include monitoring auxiliary voltages in control systems, enclosures, or vehicle systems.
Functions and Equipment in Detail
The device features two changeover contacts (11-14 and 21-24) for controlling external loads or signals. The switching delay ranges from 0 to 100 seconds and is activated when the set threshold value is exceeded. This delay prevents false tripping caused by short-term voltage spikes. The pickup delay is also integrated, ensuring the relay does not react immediately to voltage fluctuations but introduces a short delay to filter disturbances. The start-up bypass is not available in this variant, meaning the device becomes active immediately upon applying the auxiliary voltage.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measurement voltage. For AC voltages, the device is calibrated to the RMS value, enabling precise measurement even with sinusoidal signals. The measurement frequency can reach up to 5 kHz, allowing use in applications with rapid voltage changes. The auxiliary voltage is supplied via terminals A1 and A2 and can range from AC/DC 80 to 230 V. The maximum rated voltage is AC 1000 V and DC 900 V, enabling use in high-voltage installations. The internal resistances of the measurement ranges depend on the range and are 500 kΩ for the AC 0.5–5 V range.
Compatibility and Accessories
The relay complies with standards IEC/EN 60255-1 and IEC/EN 60947-1 and carries the UKCA and CCC certifications. It is designed for installation in enclosures and has a width of 45 mm, making it suitable for standard switchboards. LED indicators (green for operational readiness, yellow for activated output relay) provide visual status indication. Terminal labeling follows the scheme A1/A2 for auxiliary voltage, e/f for measurement voltage input, and 11/12/14 and 21/22/24 for the two changeover contacts.
Mounting and Installation
Mounting is performed in standard switchboards or enclosures. The terminals are designed for direct connection to wires. Threshold values are adjusted via rotary switches on the front panel. The auxiliary voltage must be within the range of AC/DC 80–230 V. The connection terminals are clearly labeled, ensuring error-free installation. Galvanic isolation between the measurement and auxiliary circuits reduces interference risk and enhances safety.
Operational Advantages
Precise and reliable measurement, combined with integrated switching delay, minimizes false tripping. Early detection of voltage anomalies enables preventive maintenance and prevents damage to connected devices. LED indicators facilitate diagnostics during operation. The device is designed for high overload capacity, increasing reliability in industrial environments. Compliance with international standards and UKCA and CCC certifications ensure suitability for various markets.
| Technical data | |
| 1- / 3-phase | 1 |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | AC 1000 V, DC 900 V |
| Output contacts | 2 C/O contacts |
| Width | 45 mm |
| Type | BA 9054 |
| Operate delay | |
| Variant | |
| Auxiliary voltage | AC/DC 80 - 230 V |
| Contact equipping | 2 changeover contacts |
| Measuring range | AC 0,5 - 5 V |
| Start up delay | Without |
| Switching delay | 0 - 100 s |
| Approvals and Markings | UKCA, CCC |
| Variant | Overvoltage relay. Energized on trip. Time delay at setting value |
Questions & answers
What is the delivery time of Dold 0057106 BA9054/010 AC0.5-5V AC/DC80-230V voltage relay Tv=0-100S ?
The article Dold 0057106 BA9054/010 AC0.5-5V AC/DC80-230V voltage relay Tv=0-100S is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0057106 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0057106 BA9054/010 AC0.5-5V AC/DC80-230V voltage relay Tv=0-100S always at the best possible price. We can give you a discount of 2% on Dold 0057106 BA9054/010 AC0.5-5V AC/DC80-230V voltage relay Tv=0-100S if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0057106 BA9054/010 AC0.5-5V AC/DC80-230V voltage relay Tv=0-100S we can offer you a price of 332,89 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.