Further information for Dold 0057106 voltage relay AC0,5-5V AC/DC80-230V
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Nominal voltage max.
AC 1000 V, DC 900 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9054
Operate delay
Variant
Auxiliary voltage
AC/DC 80 - 230 V
Contact equipping
2 changeover contacts
Measuring range
AC 0,5 - 5 V
Start up delay
Without
Switching delay
0 - 100 s
Approvals and Markings
UKCA, CCC
Variant
Overvoltage relay. Energized on trip. Time delay at setting value
The Dold voltage relay BA9054/010 AC0,5-5V AC/DC80-230V is an industrial monitoring switch from the VARIMETER series, designed for continuous monitoring of single-phase DC and AC voltage networks. The device operates as an overvoltage relay and can optionally be configured as an undervoltage relay. Adjustment is performed via rotary switches on the front panel, ensuring simple and user-friendly parameterization. The function enables early detection of voltage anomalies to prevent electrical system failures and enhance operational safety.
Applications
This relay is intended for use in industrial and railway applications where reliable voltage monitoring is required. It monitors DC and AC voltages in the range of AC 0.5 to 5 V, making it suitable for applications with low measurement voltages. The galvanic isolation between auxiliary and measurement circuits ensures safe and interference-free measurement, even at high network voltages. Typical application areas include monitoring auxiliary voltages in control systems, enclosures, or vehicle systems.
Functions and Equipment in Detail
The device features two changeover contacts (11-14 and 21-24) for controlling external loads or signals. The switching delay ranges from 0 to 100 seconds and is activated when the set threshold value is exceeded. This delay prevents false tripping caused by short-term voltage spikes. The pickup delay is also integrated, ensuring the relay does not react immediately to voltage fluctuations but introduces a short delay to filter disturbances. The start-up bypass is not available in this variant, meaning the device becomes active immediately upon applying the auxiliary voltage.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measurement voltage. For AC voltages, the device is calibrated to the RMS value, enabling precise measurement even with sinusoidal signals. The measurement frequency can reach up to 5 kHz, allowing use in applications with rapid voltage changes. The auxiliary voltage is supplied via terminals A1 and A2 and can range from AC/DC 80 to 230 V. The maximum rated voltage is AC 1000 V and DC 900 V, enabling use in high-voltage installations. The internal resistances of the measurement ranges depend on the range and are 500 kΩ for the AC 0.5–5 V range.
Compatibility and Accessories
The relay complies with standards IEC/EN 60255-1 and IEC/EN 60947-1 and carries the UKCA and CCC certifications. It is designed for installation in enclosures and has a width of 45 mm, making it suitable for standard switchboards. LED indicators (green for operational readiness, yellow for activated output relay) provide visual status indication. Terminal labeling follows the scheme A1/A2 for auxiliary voltage, e/f for measurement voltage input, and 11/12/14 and 21/22/24 for the two changeover contacts.
Mounting and Installation
Mounting is performed in standard switchboards or enclosures. The terminals are designed for direct connection to wires. Threshold values are adjusted via rotary switches on the front panel. The auxiliary voltage must be within the range of AC/DC 80–230 V. The connection terminals are clearly labeled, ensuring error-free installation. Galvanic isolation between the measurement and auxiliary circuits reduces interference risk and enhances safety.
Operational Advantages
Precise and reliable measurement, combined with integrated switching delay, minimizes false tripping. Early detection of voltage anomalies enables preventive maintenance and prevents damage to connected devices. LED indicators facilitate diagnostics during operation. The device is designed for high overload capacity, increasing reliability in industrial environments. Compliance with international standards and UKCA and CCC certifications ensure suitability for various markets.