Dold 0053718 BA9054/012 AC50-500V UH AC230V voltage relay Tv=0-20S
|
263,30 EUR |
|||||||||||
|
( 313,33 EUR incl. VAT ) ≈ £220.38 | ≈ $289.37 plus delivery charges: 55,00 € |
|||||||||||
| Made to order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 458546 | ||||||||||
| Mfg Part No: | 0053718 | ||||||||||
| UPC/EAN: | 4030641537180 | ||||||||||
| Weight: | 0.31 kg | ||||||||||
| Type: | BA9054/012AC50-500VUHAC230V | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0053718:
Applications
This relay is suitable for monitoring DC and AC voltages in industrial plants as well as in railway applications. It enables early detection of voltage drops to prevent electrical system failures and enhance operational safety. The device is installed in enclosures, with a width of 45 mm allowing compact mounting in standard control panels.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which can be used to control auxiliary circuits or warning systems. The auxiliary voltage is AC 230 V, allowing power supply via standard low-voltage networks. The switching delay is adjustable within a range of 0 to 20 seconds, enabling a delayed response to short-term voltage fluctuations and preventing false tripping. The pickup delay is also integrated to ensure stable response to voltage fluctuations.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measured voltage. For AC voltages, the device is calibrated to the RMS value, enabling precise measurement even with sinusoidal voltages. The hysteresis depends on the set pickup value, ensuring that feedback only occurs after exceeding a specific threshold. Galvanic isolation between the auxiliary circuit and the measurement circuit ensures safe and interference-free operation. LED indicators signal operational readiness (green LED) and activation of the output relay (yellow LED).
Compatibility and Accessories
The device complies with standards IEC/EN 60255-1 and IEC/EN 60947-1 and carries UKCA and CCC certifications. It is designed for a maximum rated voltage of AC 1000 V and DC 900 V, with the measurement range specifically set to AC 50–500 V. The terminal connections are clearly labeled: A1/A2 for auxiliary voltage, e/f for voltage input, and contacts 11/12/14 and 21/22/24 for the two changeover contacts. The measurement frequency can reach up to 5 kHz, enabling use in applications with high frequencies.
Mounting and Installation
Mounting is performed in enclosures using screw fastening. The width of 45 mm corresponds to the standard for DIN rail mounting, allowing easy integration into existing control systems. The terminals are designed for secure and reliable connections, with connection designations directly marked on the device. Adjustment of pickup and hysteresis values is done via rotary switches on the front panel, without requiring additional tools.
Operational Advantages
Precise and reliable voltage monitoring increases operational safety. Early detection of voltage drops enables preventive maintenance and prevents damage to connected devices. LED indicators facilitate diagnostics during operation, and the switching delay reduces the number of false tripping events during short-term disturbances. Galvanic isolation between the measurement and auxiliary circuits ensures high system safety and stability.
| Technical data | |
| 1- / 3-phase | 1 |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | AC 1000 V, DC 900 V |
| Output contacts | 2 C/O contacts |
| Width | 45 mm |
| Type | BA 9054 |
| Operate delay | |
| Variant | |
| Auxiliary voltage | AC 230 V |
| Contact equipping | 2 changeover contacts |
| Measuring range | AC 50 - 500 V |
| Start up delay | Without |
| Switching delay | 0 - 20 s |
| Approvals and Markings | UKCA, CCC |
| Variant | Undervoltage relay. De-energized on trip. Time delay at hysteresis value |
Questions & answers
What is the delivery time of Dold 0053718 BA9054/012 AC50-500V UH AC230V voltage relay Tv=0-20S ?
The article Dold 0053718 BA9054/012 AC50-500V UH AC230V voltage relay Tv=0-20S is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0053718 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0053718 BA9054/012 AC50-500V UH AC230V voltage relay Tv=0-20S always at the best possible price. We can give you a discount of 2% on Dold 0053718 BA9054/012 AC50-500V UH AC230V voltage relay Tv=0-20S if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0053718 BA9054/012 AC50-500V UH AC230V voltage relay Tv=0-20S we can offer you a price of 253,43 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.