Product information for Dold 0053138:
Applications
This relay is designed for use in industrial and railway applications, where reliable current monitoring is required. It is particularly suitable for monitoring motors, transformer installations, or other loads where a sudden current increase or interruption of power supply can be critical. The galvanic isolation between the auxiliary circuit and the measuring circuit ensures safe and interference-free measurement, even with high interference voltages in the network.
Functions and Equipment in Detail
Device settings are adjusted via rotary switches on the front, enabling user-friendly and precise adjustment of the pickup and dropout values. The hysteresis, i.e., the difference between pickup and dropout values, depends on the set threshold and ensures stable switching behavior without oscillations. The device features 2 changeover contacts as output contacts, which can be used for controlling auxiliary relays, signal indication, or switching operations. The LED indicator shows operational readiness (green LED) and the active contact position (yellow LED), facilitating diagnosis during operation.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measuring current. For AC current, the device is calibrated to the RMS value, enabling accurate measurement even with sinusoidal loads. The measuring frequency can reach up to 5 kHz, allowing use with high-frequency loads. The switching delay tv delays switching after exceeding the set value, preventing the relay from tripping undesirably during short-term current peaks, such as during motor start-up. In this variant, no start-up bypass is provided, so switching occurs immediately upon exceeding the threshold.
Compatibility and Accessories
The device complies with IEC/EN 60255-1 and IEC/EN 60947-1 standards and carries the approvals UKCA and CCC. It is designed for use in enclosures and can be combined with other devices from the VARIMETER series. Terminal markings follow the standard: A1/A2 for auxiliary voltage, i/k for current input, and 11/12/14 and 21/22/24 for the two changeover contacts. The measuring ranges are fixed for each variant; for this version, the range is AC 1 to 10 A.
Mounting and Installation
The device is mounted in an enclosure and requires secure fastening to a mounting rail. The terminal connections are designed for cable connections, with maximum permissible current loading and conductor cross-sections to be observed according to the manufacturer’s technical data. The auxiliary voltage of AC 230 V is supplied via terminals A1/A2. Current measurement is performed via terminals i/k, with the measuring current flowing through the internal shunt resistor.
Advantages in Operation
Precise and reliable current monitoring enables higher operational safety and reduces maintenance intervals. The LED indicator and clear front operation simplify commissioning and fault diagnosis. The switching delay prevents unnecessary shutdowns during short-term load peaks, increasing plant availability. The device is designed for industrial environments and offers high overload capacity, making it suitable for demanding applications.
| Technical data | |
| 1- / 3-phase | 1 |
| Enclosure design | Switch cabinet |
| Output contacts | 2 C/O contacts |
| Width | 45 mm |
| Type | BA 9053 |
| Operate delay | |
| Variant | |
| Auxiliary voltage | AC 230 V |
| Contact equipping | 2 changeover contacts |
| Measuring range | AC 1 - 10 A |
| Start up delay | Without |
| Switching delay | 0 - 20 s |
| Approvals and Markings | UKCA, CCC |
| Variant | Overcurrent relay. Energized on trip. Time delay at response value |
Questions & answers
What is the delivery time of Dold 0053138 BA9053/010 AC1-10A AC230V 0-20S current relay ?
The article Dold 0053138 BA9053/010 AC1-10A AC230V 0-20S current relay is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0053138 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0053138 BA9053/010 AC1-10A AC230V 0-20S current relay always at the best possible price. We can give you a discount of 2% on Dold 0053138 BA9053/010 AC1-10A AC230V 0-20S current relay if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0053138 BA9053/010 AC1-10A AC230V 0-20S current relay we can offer you a price of 253,43 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.