Further information for Dold 0053138 current relay BA9053/010 AC1-10A AC230V 0-20S
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9053
Operate delay
Variant
Auxiliary voltage
AC 230 V
Contact equipping
2 changeover contacts
Measuring range
AC 1 - 10 A
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overcurrent relay. Energized on trip. Time delay at response value
The Dold current relay BA9053/010 is an overcurrent relay of the VARIMETER series, designed for monitoring single-phase AC networks in the range of AC 1 to 10 A. It is used for continuous monitoring of the current consumption of electrical loads and enables preventive maintenance by early detection of deviations, thus avoiding failures in industrial plants. The device operates on the operating current principle and switches when the set threshold is exceeded, with a switching delay of 0 to 20 seconds. The auxiliary voltage is AC 230 V, allowing operation in standard enclosures. The width of 45 mm corresponds to the standard format for enclosure devices and enables easy installation in existing control systems.
Applications
This relay is designed for use in industrial and railway applications, where reliable current monitoring is required. It is particularly suitable for monitoring motors, transformer installations, or other loads where a sudden current increase or interruption of power supply can be critical. The galvanic isolation between the auxiliary circuit and the measuring circuit ensures safe and interference-free measurement, even with high interference voltages in the network.
Functions and Equipment in Detail
Device settings are adjusted via rotary switches on the front, enabling user-friendly and precise adjustment of the pickup and dropout values. The hysteresis, i.e., the difference between pickup and dropout values, depends on the set threshold and ensures stable switching behavior without oscillations. The device features 2 changeover contacts as output contacts, which can be used for controlling auxiliary relays, signal indication, or switching operations. The LED indicator shows operational readiness (green LED) and the active contact position (yellow LED), facilitating diagnosis during operation.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measuring current. For AC current, the device is calibrated to the RMS value, enabling accurate measurement even with sinusoidal loads. The measuring frequency can reach up to 5 kHz, allowing use with high-frequency loads. The switching delay tv delays switching after exceeding the set value, preventing the relay from tripping undesirably during short-term current peaks, such as during motor start-up. In this variant, no start-up bypass is provided, so switching occurs immediately upon exceeding the threshold.
Compatibility and Accessories
The device complies with IEC/EN 60255-1 and IEC/EN 60947-1 standards and carries the approvals UKCA and CCC. It is designed for use in enclosures and can be combined with other devices from the VARIMETER series. Terminal markings follow the standard: A1/A2 for auxiliary voltage, i/k for current input, and 11/12/14 and 21/22/24 for the two changeover contacts. The measuring ranges are fixed for each variant; for this version, the range is AC 1 to 10 A.
Mounting and Installation
The device is mounted in an enclosure and requires secure fastening to a mounting rail. The terminal connections are designed for cable connections, with maximum permissible current loading and conductor cross-sections to be observed according to the manufacturer’s technical data. The auxiliary voltage of AC 230 V is supplied via terminals A1/A2. Current measurement is performed via terminals i/k, with the measuring current flowing through the internal shunt resistor.
Advantages in Operation
Precise and reliable current monitoring enables higher operational safety and reduces maintenance intervals. The LED indicator and clear front operation simplify commissioning and fault diagnosis. The switching delay prevents unnecessary shutdowns during short-term load peaks, increasing plant availability. The device is designed for industrial environments and offers high overload capacity, making it suitable for demanding applications.