Dold 0050642 BA9094.28/100 AC230V temperature monitor P1=20-100°C P2=20-100°C
|
330,27 EUR |
|||||||||||
|
( 393,02 EUR incl. VAT ) ≈ £276.44 | ≈ $362.97 plus delivery charges: 55,00 € |
|||||||||||
| Made to order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 725107 | ||||||||||
| Mfg Part No: | 0050642 | ||||||||||
| UPC/EAN: | 4030641506421 | ||||||||||
| Weight: | 0.35 kg | ||||||||||
| Type: | BA9094.28/100AC230VP1=20-100C | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0050642:
Applications
The temperature monitor is used for continuous temperature monitoring in industrial applications, particularly in motors, bearings, or rooms where overheating must be prevented. The 2-wire technology and wire break detection ensure that a reaction occurs even if the sensor is defective or the wire is broken. This function is especially important in systems where temperature exceedance can lead to damage or failure.
Functions and equipment in detail
The device features a PT100 input, connected to a resistance thermometer. The setpoint values are adjustable in the range of 20 °C to 100 °C, with the hysteresis (reset value) lying between 85 % and 95 % of the setpoint. The output contacts consist of a changeover contact for the first output (P1) and a normally closed contact for the second output (P2). When the setpoint is exceeded or a wire break occurs, the output relay drops out, which corresponds to the de-energized operation principle. The LED indicators (red and green) signal the operating status.
Technology explained simply
The wire break detection recognizes when the sensor wire is interrupted and triggers a reaction as well. The device operates on the de-energized operation principle, where the output relays are activated in the normal state and drop out in case of a fault (over-temperature or wire break). The auxiliary voltage of AC 230 V is supplied via terminals A1 and A2.
Compatibility and accessories
The device is designed for PT100 sensors, which are common in industrial applications. It can be operated with a single PT100 sensor, where two separate switching points (P1 and P2) can be defined. The settings for setpoint and reset value are independent of each other, enabling flexible use. The standard IEC/EN 60255-1 is complied with, ensuring reliability and safety in industrial use.
Mounting and installation
The temperature monitor is mounted in enclosures and requires a width of 45 mm. Connections are made via terminals: A1 and A2 for auxiliary voltage, P0, P1, P2 for PT100 sensors, and contacts 11-12, 14, 23-24 for outputs. The device is designed for continuous operation and is rated for operating temperatures from -20 °C to +60 °C. The operating altitude is limited to a maximum of 2000 m above sea level.
Advantages in operation
The separate adjustment of setpoint and reset values for each output enables precise control of switching operations. The wire break detection increases safety, as a reaction occurs even if the sensor is defective. The high mechanical life of over 30 million switching operations and the electrical life of over 100,000 switching operations at 5 A and AC 230 V ensure a long service life. The EMC testing according to IEC/EN 61000-4-2 to -4-6 ensures immunity against electromagnetic interference.
| Technical data | |
| Classification | Temperaturüberwachung |
| Enclosure design | Switch cabinet |
| Measuring range max. | 100 °C |
| Output contacts | 1 C/O contact, 1 NO contact |
| Width | 45 mm |
| Type | BA 9094 |
| Variant | |
| Auxiliary voltage | AC 230 V |
| Contact equipping | 1 changeover contact for P1, 1 NO contact for P2 |
| Response value / Reset value P1 | only response value |
| Response value / Reset value P2 | only response value |
| Response value P1 = P2 | 20 - 100 C |
| Variant | 1 PT 100 input. 2 outputs. Seperate adjustable response and release value for every output |
Questions & answers
What is the delivery time of Dold 0050642 BA9094.28/100 AC230V temperature monitor P1=20-100°C P2=20-100°C ?
The article Dold 0050642 BA9094.28/100 AC230V temperature monitor P1=20-100°C P2=20-100°C is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0050642 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0050642 BA9094.28/100 AC230V temperature monitor P1=20-100°C P2=20-100°C always at the best possible price. We can give you a discount of 2% on Dold 0050642 BA9094.28/100 AC230V temperature monitor P1=20-100°C P2=20-100°C if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0050642 BA9094.28/100 AC230V temperature monitor P1=20-100°C P2=20-100°C we can offer you a price of 317,88 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.