Dold 0050218 IK9171.11/001 3AC400V 0.55-1.05UN4% undervoltage relay
|
114,68 EUR |
|||||||||||
|
( 136,47 EUR incl. VAT ) ≈ £95.99 | ≈ $126.03 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1002313 | ||||||||||
| Mfg Part No: | 0050218 | ||||||||||
| UPC/EAN: | 4030641502188 | ||||||||||
| Weight: | 0.123 kg | ||||||||||
| Type: | IK9171.11/001 3AC400V 0,55-1,05UN4% | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0050218:
Applications
This relay is used in systems where continuous voltage monitoring is required to activate safety-critical functions such as emergency lighting or emergency power supply in the event of undervoltage or phase failure. It is particularly suitable for applications in industrial and commercial electrical installations where power supply reliability is critical. The device is also used in unstable networks, for example with local power generation, where a staged re-start of consumers after a network failure is necessary.
Functions and Equipment in Detail
The device features an adjustable pickup value ranging from 0.55 to 1.05 times nominal voltage with a hysteresis of approximately 4 %. The contact configuration includes a changeover contact, which switches state when undervoltage is detected. The LED indicator signals the contact position – yellow illumination indicates that the output relay is activated (contacts 11-14 closed). Phase sequence is arbitrary, enabling flexible installation. The device is designed without time delay, reacting immediately to voltage deviations.
Technology Explained Simply
Measurement is performed via the arithmetic mean of the three phases against the neutral conductor (N). In variants without neutral conductor connection, L1 and L3 are measured against L2 (IK/SK 9171) or L1 and L2 against L3 (IL/SL 9171). For single-phase connection, terminals L1, L2, and L3 must be connected together. The device’s response time is short, with pickup delay activated to prevent false alarms during brief voltage fluctuations. The frequency range is between 45 and 65 Hz.
Compatibility and Accessories
The relay is suitable for 1- and 3-phase networks and can be configured in various variants with or without neutral conductor connection, with or without time delay, and with fixed or adjustable pickup value. It is part of the IK 9171 product family, which is also available in other construction types (e.g. SK 9171, IL 9171). The devices are manufactured in accordance with IEC/EN 60255-1 and carry the UKCA mark.
Mounting and Installation
Mounting is performed in installation distributors with a depth of 59 mm. The connection terminals are located at the bottom, facilitating integration into standard distributors. The devices are suitable for use in enclosures with mounting plate and cable duct. Installation requires no additional auxiliary voltage, simplifying wiring.
Operational Advantages
The relay provides reliable and low-maintenance voltage monitoring without external power supply. The adjustable pickup threshold allows application-specific adjustment. The LED indicator facilitates diagnostics during operation. The stand-by current principle ensures that the output relay is not unintentionally activated in the event of a fault, increasing safety. Compatibility with various network configurations (1- and 3-phase, with/without N) expands the range of applications.
| Technical data | |
| 1- / 3-phase | 1, 3 |
| Auxiliary voltage | Without |
| Enclosure design | Distribution board |
| Nominal voltage max. | 3/N AC 500 / 290 V |
| Output contacts | 1 C/O contact |
| Width | 17,5 mm |
| Type | IK 9171 |
| Operate delay | |
| Variant | |
| Contact equipping | 1 changeover contact |
| Nominal voltage | 3AC 400 V |
| Response value | 0,55 - 1,05 Un 4% |
| Time delay | without |
| Approvals and Markings | UKCA |
| Variant | Without N. NC circuit operation. Without time delay. Settable response value |
Questions & answers
What is the delivery time of Dold 0050218 IK9171.11/001 3AC400V 0.55-1.05UN4% undervoltage relay?
The article Dold 0050218 IK9171.11/001 3AC400V 0.55-1.05UN4% undervoltage relay is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0050218 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0050218 IK9171.11/001 3AC400V 0.55-1.05UN4% undervoltage relay always at the best possible price. We can give you a discount of 2% on Dold 0050218 IK9171.11/001 3AC400V 0.55-1.05UN4% undervoltage relay if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 5 pieces of Dold 0050218 IK9171.11/001 3AC400V 0.55-1.05UN4% undervoltage relay we can offer you a price of 109,52 EUR per piece. The more you buy, the cheaper the article will be.