Further information for Dold 0050218 IK9171.11/001 3AC400V undervoltage relay
Technical data
1- / 3-phase
1, 3
Auxiliary voltage
Without
Enclosure design
Distribution board
Nominal voltage max.
3/N AC 500 / 290 V
Output contacts
1 C/O contact
Width
17,5 mm
Type
IK 9171
Operate delay
Variant
Contact equipping
1 changeover contact
Nominal voltage
3AC 400 V
Response value
0,55 - 1,05 Un 4%
Time delay
without
Approvals and Markings
UKCA
Variant
Without N. NC circuit operation. Without time delay. Settable response value
The Dold undervoltage relay IK9171.11/001 is an industrial-grade monitoring device for detecting undervoltage in three-phase power networks. It is designed for network monitoring and automatic switching to safety power supply or safety lighting in accordance with DIN VDE 0100-710 or DIN VDE 0108. The device operates on the stand-by current principle, whereby the output relay is not activated in the event of a fault, and is operational without auxiliary voltage. The nominal voltage is 3AC 400 V, and the device can also be connected single-phase. The width of 17.5 mm allows mounting in installation distributors according to DIN 43 880, with connection terminals located at the bottom (I-type construction). The maximum nominal voltage is 3/N AC 500 / 290 V.
Applications
This relay is used in systems where continuous voltage monitoring is required to activate safety-critical functions such as emergency lighting or emergency power supply in the event of undervoltage or phase failure. It is particularly suitable for applications in industrial and commercial electrical installations where power supply reliability is critical. The device is also used in unstable networks, for example with local power generation, where a staged re-start of consumers after a network failure is necessary.
Functions and Equipment in Detail
The device features an adjustable pickup value ranging from 0.55 to 1.05 times nominal voltage with a hysteresis of approximately 4 %. The contact configuration includes a changeover contact, which switches state when undervoltage is detected. The LED indicator signals the contact position – yellow illumination indicates that the output relay is activated (contacts 11-14 closed). Phase sequence is arbitrary, enabling flexible installation. The device is designed without time delay, reacting immediately to voltage deviations.
Technology Explained Simply
Measurement is performed via the arithmetic mean of the three phases against the neutral conductor (N). In variants without neutral conductor connection, L1 and L3 are measured against L2 (IK/SK 9171) or L1 and L2 against L3 (IL/SL 9171). For single-phase connection, terminals L1, L2, and L3 must be connected together. The device’s response time is short, with pickup delay activated to prevent false alarms during brief voltage fluctuations. The frequency range is between 45 and 65 Hz.
Compatibility and Accessories
The relay is suitable for 1- and 3-phase networks and can be configured in various variants with or without neutral conductor connection, with or without time delay, and with fixed or adjustable pickup value. It is part of the IK 9171 product family, which is also available in other construction types (e.g. SK 9171, IL 9171). The devices are manufactured in accordance with IEC/EN 60255-1 and carry the UKCA mark.
Mounting and Installation
Mounting is performed in installation distributors with a depth of 59 mm. The connection terminals are located at the bottom, facilitating integration into standard distributors. The devices are suitable for use in enclosures with mounting plate and cable duct. Installation requires no additional auxiliary voltage, simplifying wiring.
Operational Advantages
The relay provides reliable and low-maintenance voltage monitoring without external power supply. The adjustable pickup threshold allows application-specific adjustment. The LED indicator facilitates diagnostics during operation. The stand-by current principle ensures that the output relay is not unintentionally activated in the event of a fault, increasing safety. Compatibility with various network configurations (1- and 3-phase, with/without N) expands the range of applications.