Dold 0039122 BA9043/003 3AC50-400Hz 400V 0.5-10S undervoltage relay
|
302,01 EUR |
|||||||||||
|
( 359,39 EUR incl. VAT ) ≈ £252.78 | ≈ $331.91 plus delivery charges: 55,00 € |
|||||||||||
| Made to order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 916050 | ||||||||||
| Mfg Part No: | 0039122 | ||||||||||
| UPC/EAN: | 4030641391225 | ||||||||||
| Weight: | 0.34 kg | ||||||||||
| Type: | BA9043/003 3AC50/60HZ 400V 0,5-10S | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0039122:
Applications
This relay is designed for use in industrial and railway applications where reliable voltage monitoring is required. It is particularly suitable for systems that depend on stable power supply, such as production plants, conveyor systems, or vehicle drives.
Functions and Features in Detail
The device features two changeover contacts, which can be used for protecting loads or signaling faults. The contact configuration allows control of auxiliary relays, warning lights, or disconnection mechanisms. The output relays operate on the rest current principle, meaning they are inactive in the normal state and only energized in the event of a fault. This increases safety and reduces false alarm rates. Two LED indicators signal the operating status: a red LED lights up when operating voltage is present, and a green LED indicates activation of the output relay.
Technology Explained Simply
Voltage monitoring is performed by measuring individual phases against the reference phase (L3), thereby determining the arithmetic mean of the supply voltage. The time delay is adjustable and ranges from 0.5 to 10 seconds. This delay is only effective if the voltage is at least 60 % of the nominal voltage. Below 40 % of the nominal voltage, disconnection occurs immediately. The adjustable time delay allows adaptation to the specific requirements of the installation, enabling short-term voltage dips to be ignored and responding only to sustained disturbances.
Compatibility and Accessories
The relay is suitable for networks with or without a neutral conductor, with the BA9043/003 variant specifically designed for systems without a neutral conductor. It complies with standards IEC/EN 60255-1 and is certified with UKCA and CCC approvals. The devices are designed for use in enclosures and mount on a DIN rail. The width is 45 mm, enabling compact installation in standard control panels. The electrical life expectancy is at least 200,000 switching operations at 3 A and AC 230 V, while the mechanical life exceeds 30 million switching operations.
Mounting and Installation
Mounting is done on a DIN rail according to IEC/EN 60715. The terminal connections are rated for 2 x 2.5 mm² rigid or 2 x 1.5 mm² flexible conductors with heat-shrink tubing. Fixing is achieved using M3.5 plus-minus screws with self-lifting clips. The required stripping length is 10 mm, and the tightening torque for the screws is 0.8 Nm. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is from -25 °C to +60 °C. The maximum operating altitude is 2000 m above sea level.
Operational Advantages
Thanks to the continuous adjustability of pickup and dropout values as well as time delay, the device can be optimally adapted to the specific requirements of each installation. The LED indicators enable quick fault localization. The immunity to harmonics ensures stable operation even in networks with high harmonic content. The ability to operate without auxiliary power reduces installation complexity and increases reliability. Compliance with the IEC/EN 60255-1 standard ensures the quality and safety of the device.
| Technical data | |
| 1- / 3-phase | 3 |
| Auxiliary voltage | Without |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | 3/N AC 690 / 400 V |
| Output contacts | 2 C/O contacts |
| Width | 45 mm |
| Type | BA 9043 |
| Operate delay | |
| Variant | |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | 3AC 400 V |
| Time delay | 0,5 - 10 s |
| Approvals and Markings | UKCA, CCC |
| Variant | For 3p3w systems. With adjustable time delay |
Questions & answers
What is the delivery time of Dold 0039122 BA9043/003 3AC50-400Hz 400V 0.5-10S undervoltage relay ?
The article Dold 0039122 BA9043/003 3AC50-400Hz 400V 0.5-10S undervoltage relay is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0039122 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0039122 BA9043/003 3AC50-400Hz 400V 0.5-10S undervoltage relay always at the best possible price. We can give you a discount of 2% on Dold 0039122 BA9043/003 3AC50-400Hz 400V 0.5-10S undervoltage relay if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0039122 BA9043/003 3AC50-400Hz 400V 0.5-10S undervoltage relay we can offer you a price of 290,68 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.