Product information for Dold 0030807:
Applications
The BA 9043 is designed for use in industrial and railway applications where reliable voltage monitoring of three-phase networks is required. It is particularly suitable for systems where a power interruption could lead to production downtime or safety risks. The robust design and compliance with the IEC/EN 60255-1 standard ensure high reliability in demanding environments. The devices are designed for use in enclosures and have a width of 45 mm, enabling compact mounting in standard control panels.
Functions and Equipment in Detail
The relay features two changeover contacts as output contacts, used for switching operations in control and protection circuits. The contacts are rated for a thermal current of up to 6 A per contact and meet switching capacity requirements for AC 15 (make: 2 A / AC 230 V, break: 1 A / AC 230 V) and DC 13 (1 A / DC 24 V). The electrical life expectancy is at least 200,000 switching operations at 3 A and AC 230 V, while the mechanical life expectancy exceeds 30 million switching operations. LED indicators on the front panel signal operational readiness (red LED) and activation of the output relay (green LED), enabling quick fault localization. The device is insensitive to harmonics, ensuring stable operation even with distorted voltage waveforms.
Technology Explained Simply
The arithmetic mean measurement is performed by measuring each phase against the neutral conductor. In systems without a neutral conductor (variants /001 and /003), L1 and L2 are measured against L3. The pickup delay is not activated in this model, although time delay in other variants (e.g. BA 9043/002) is continuously adjustable from 0.5 to 10 seconds. Below 0.4 times the nominal voltage, the output relay drops out immediately. The operating power consumption is AC 4 VA, and the device is designed for continuous operation. The operating temperature range is -20 to +60 °C, with storage temperatures ranging from -25 to +60 °C. The maximum operating altitude is limited to 2000 m above sea level.
Compatibility and Accessories
The BA 9043 is suitable for networks with or without a neutral conductor, with the variant described here specifically designed for systems with a neutral conductor. Devices are available for nominal voltages ranging from 3/N AC 100/57 V to 690/400 V, with the version specified here configured for 127/220 V. Mounting is on DIN rail in accordance with IEC/EN 60715. The terminals are designed for 2 x 2.5 mm² solid or 2 x 1.5 mm² stranded cable with heat-shrink tubing, with a stripping length of 10 mm and a tightening torque of 0.8 Nm. The rated impulse voltage is 6 kV at pollution degree 2, and the overvoltage category is III.
Mounting and Installation
Mounting is on a DIN rail within the enclosure. The connection terminals are designed for connection with solid or stranded cables. Wiring is performed via terminals L1, L2, L3, and N for the power supply side, and contacts 11, 12, 14 and 21, 22, 24 for the output side. Adjustment of pickup and dropout values is done via the rotary potentiometers on the front panel. The devices are designed for industrial environments and comply with electromagnetic compatibility (EMC) requirements according to IEC/EN 61000-4-2 to -4-5.
Operational Advantages
Preventive maintenance is supported by clear indication of operating states and rapid fault localization. The long contact life and robust construction ensure long-term operation with minimal maintenance effort. Compliance with the IEC/EN 60255-1 standard and certifications UKCA and CCC guarantee conformity with European and Chinese safety requirements. The device is suitable for industrial and railway applications, where reliable voltage monitoring is of critical importance.
More spare projector bulbs for your Epson Beamer
| Technical data | |
| 1- / 3-phase | 3 |
| Auxiliary voltage | Without |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | 3/N AC 690 / 400 V |
| Output contacts | 2 C/O contacts |
| Width | 45 mm |
| Type | BA 9043 |
| Operate delay | |
| Variant | |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | 3/N 127/220 V |
| Time delay | without |
| Approvals and Markings | UKCA, CCC |
| Variant | For 3p4w systems |
Questions & answers
What is the delivery time of Dold 0030807 BA9043 3/N AC50-400Hz 127/220V undervoltage relay?
The article Dold 0030807 BA9043 3/N AC50-400Hz 127/220V undervoltage relay is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0030807 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0030807 BA9043 3/N AC50-400Hz 127/220V undervoltage relay always at the best possible price. We can give you a discount of 2% on Dold 0030807 BA9043 3/N AC50-400Hz 127/220V undervoltage relay if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0030807 BA9043 3/N AC50-400Hz 127/220V undervoltage relay we can offer you a price of 250,40 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.