Further information for Dold 0030807 BA9043 3/N AC50-400Hz 127/220V undervoltage relay
Technical data
1- / 3-phase
3
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
3/N AC 690 / 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9043
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3/N 127/220 V
Time delay
without
Approvals and Markings
UKCA, CCC
Variant
For 3p4w systems
The under-voltage relay BA 9043 from Dold is an industrial device for monitoring 3-phase AC networks. It is designed for continuous voltage monitoring in three-phase systems with neutral conductor (3/N) and is rated for nominal voltages of 127/220 V. The device operates on the rest current principle, whereby the output relay is not activated in the event of a fault, ensuring safe and reliable signal transmission. Measurement is performed via arithmetic mean calculation of the three phases against the neutral conductor, enabling precise and robust voltage monitoring. Device settings are adjusted via rotary potentiometers on the front panel, allowing user-friendly and continuous adjustment of the pickup and dropout values. The pickup value is adjustable within a range of 0.85 to 1.05 of the nominal voltage, with hysteresis ranging from 0.75 to 0.95 of the pickup value. The operating frequency is between 50 and 400 Hz, making the device suitable for a wide range of industrial and railway applications.
Applications
The BA 9043 is designed for use in industrial and railway applications where reliable voltage monitoring of three-phase networks is required. It is particularly suitable for systems where a power interruption could lead to production downtime or safety risks. The robust design and compliance with the IEC/EN 60255-1 standard ensure high reliability in demanding environments. The devices are designed for use in enclosures and have a width of 45 mm, enabling compact mounting in standard control panels.
Functions and Equipment in Detail
The relay features two changeover contacts as output contacts, used for switching operations in control and protection circuits. The contacts are rated for a thermal current of up to 6 A per contact and meet switching capacity requirements for AC 15 (make: 2 A / AC 230 V, break: 1 A / AC 230 V) and DC 13 (1 A / DC 24 V). The electrical life expectancy is at least 200,000 switching operations at 3 A and AC 230 V, while the mechanical life expectancy exceeds 30 million switching operations. LED indicators on the front panel signal operational readiness (red LED) and activation of the output relay (green LED), enabling quick fault localization. The device is insensitive to harmonics, ensuring stable operation even with distorted voltage waveforms.
Technology Explained Simply
The arithmetic mean measurement is performed by measuring each phase against the neutral conductor. In systems without a neutral conductor (variants /001 and /003), L1 and L2 are measured against L3. The pickup delay is not activated in this model, although time delay in other variants (e.g. BA 9043/002) is continuously adjustable from 0.5 to 10 seconds. Below 0.4 times the nominal voltage, the output relay drops out immediately. The operating power consumption is AC 4 VA, and the device is designed for continuous operation. The operating temperature range is -20 to +60 °C, with storage temperatures ranging from -25 to +60 °C. The maximum operating altitude is limited to 2000 m above sea level.
Compatibility and Accessories
The BA 9043 is suitable for networks with or without a neutral conductor, with the variant described here specifically designed for systems with a neutral conductor. Devices are available for nominal voltages ranging from 3/N AC 100/57 V to 690/400 V, with the version specified here configured for 127/220 V. Mounting is on DIN rail in accordance with IEC/EN 60715. The terminals are designed for 2 x 2.5 mm² solid or 2 x 1.5 mm² stranded cable with heat-shrink tubing, with a stripping length of 10 mm and a tightening torque of 0.8 Nm. The rated impulse voltage is 6 kV at pollution degree 2, and the overvoltage category is III.
Mounting and Installation
Mounting is on a DIN rail within the enclosure. The connection terminals are designed for connection with solid or stranded cables. Wiring is performed via terminals L1, L2, L3, and N for the power supply side, and contacts 11, 12, 14 and 21, 22, 24 for the output side. Adjustment of pickup and dropout values is done via the rotary potentiometers on the front panel. The devices are designed for industrial environments and comply with electromagnetic compatibility (EMC) requirements according to IEC/EN 61000-4-2 to -4-5.
Operational Advantages
Preventive maintenance is supported by clear indication of operating states and rapid fault localization. The long contact life and robust construction ensure long-term operation with minimal maintenance effort. Compliance with the IEC/EN 60255-1 standard and certifications UKCA and CCC guarantee conformity with European and Chinese safety requirements. The device is suitable for industrial and railway applications, where reliable voltage monitoring is of critical importance.