Dold 0028807 BA9036/012 DC127V 10S+RV D.FOLG.POS voltage relay
|
266,52 EUR |
|||||||||||
|
( 317,16 EUR incl. VAT ) ≈ £223.08 | ≈ $292.91 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1002196 | ||||||||||
| Mfg Part No: | 0028807 | ||||||||||
| UPC/EAN: | 4030641288075 | ||||||||||
| Weight: | 0.34 kg | ||||||||||
| Type: | BA9036/012 DC127V 10S+RV D.FOLG.POS | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0028807:
Applications
This relay is suitable for voltage monitoring in industrial and technical installations where continuous power supply is critical. It monitors DC voltages up to 127 V and AC voltages up to 400 V. Applications include systems with electric drives, pumps, lighting systems, or automation technology, where voltage interruption can cause disruptions. The 45 mm width allows for compact mounting in standard control panels.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, used for switching operations in control and protection circuits. The pickup delay is adjustable and amounts to 10 seconds for this variant, allowing short-term voltage fluctuations to be ignored. The adjustment range lies between 0.85 and 1.05 times the nominal voltage, while for variant /1_ _ a range of 0.9 to 1.25 times nominal voltage is specified. The drop-out ratio (hysteresis) is 0.75 to 0.95 of the set value, ensuring stable switching behavior. Repeatability is ±0.5 %, enabling high precision in voltage monitoring.
Technology Explained Simply
The relay operates without auxiliary voltage, meaning it connects directly to the voltage source to be monitored. For DC voltages above 60 V, such as 127 V DC here, an external resistor is required, connected to terminals e and z. The measured voltage is connected to terminals e and f. LED indicators show the operating status: the upper LED lights up when operating voltage is present, the lower LED when the output relay is activated. The nominal consumption is 6 VA / 10 W, and the device is designed for an operating temperature range of -20 to +60 °C.
Compatibility and Accessories
For operation with 127 V DC, the external resistor ZWS 20 SL 1.6 kΩ 20 W is required, available as an accessory. The connection terminals are designed for connecting the external resistor and the measured voltage. Switching capacity is up to 2 A at 230 V AC for make contacts and 1 A for break contacts (AC 15). For DC (DC 13), switching capacity is 1 A at 24 V DC. Electrical life is 1.5 x 10⁵ switching operations at 6 A and AC 230 V, mechanical life is 30 x 10⁶ switching operations.
Mounting and Installation
The relay is mounted in enclosures and designed for continuous operation. Mounting is done in a 45 mm width, standard in enclosure technology. Connection terminals are clearly labeled, with terminal z reserved exclusively for the external resistor. The heat generation of the resistor requires appropriate mounting position with sufficient distance from adjacent components to ensure adequate shock protection.
Operational Advantages
Early detection of voltage drops enables preventive maintenance and reduces the likelihood of system downtime. The adjustable pickup delay prevents false alarms caused by short-term voltage fluctuations. LED indicators provide visual feedback on operating status, speeding up fault localization. Compliance with IEC/EN 60255-1 ensures reliability and safety in industrial applications. Operation without auxiliary voltage reduces installation complexity and lowers connection costs.
Approvals and Markings
The device carries CCC certification, confirming compliance with relevant safety and quality standards. Compliance with IEC/EN 60255-1 ensures suitability for use in industrial monitoring systems. Maximum nominal voltage is AC 400 V, with this device variant designed for DC 127 V. Frequency range is ±5 % at nominal frequencies of 50 or 60 Hz. Temperature dependence of the measured value is less than 0.05 % per Kelvin, enabling high stability under varying ambient conditions.
| Technical data | |
| 1- / 3-phase | 1 |
| Auxiliary voltage | Without |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | AC 400 V |
| Output contacts | 2 C/O contacts |
| Width | 45 mm |
| Type | BA 9036 |
| Operate delay | |
| Variant | |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | DC 127 V |
| Time delay | 10 s |
| Approvals and Markings | CCC |
| Variant | Undervoltage relay. Closed circuit operation. With time delay |
Questions & answers
What is the delivery time of Dold 0028807 BA9036/012 DC127V 10S+RV D.FOLG.POS voltage relay?
The article Dold 0028807 BA9036/012 DC127V 10S+RV D.FOLG.POS voltage relay is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0028807 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0028807 BA9036/012 DC127V 10S+RV D.FOLG.POS voltage relay always at the best possible price. We can give you a discount of 2% on Dold 0028807 BA9036/012 DC127V 10S+RV D.FOLG.POS voltage relay if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0028807 BA9036/012 DC127V 10S+RV D.FOLG.POS voltage relay we can offer you a price of 254,53 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.