Further information for Dold 0028807 BA9036/012 DC127V 10S+RV D.FOLG.POS voltage relay
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
AC 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9036
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
DC 127 V
Time delay
10 s
Approvals and Markings
CCC
Variant
Undervoltage relay. Closed circuit operation. With time delay
The voltage relay BA9036/012 DC127V 10S+RV D.FOLG.POS from Dold is an undervoltage relay for monitoring single-phase DC or AC power networks. It operates on the principle of residual current and is designed for mounting in enclosures. Device settings are adjusted via rotary switches on the front, enabling simple and user-friendly configuration. The relay enables early detection of voltage drops and thus supports preventive maintenance of electrical systems to avoid failures and enhance operational safety.
Applications
This relay is suitable for voltage monitoring in industrial and technical installations where continuous power supply is critical. It monitors DC voltages up to 127 V and AC voltages up to 400 V. Applications include systems with electric drives, pumps, lighting systems, or automation technology, where voltage interruption can cause disruptions. The 45 mm width allows for compact mounting in standard control panels.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, used for switching operations in control and protection circuits. The pickup delay is adjustable and amounts to 10 seconds for this variant, allowing short-term voltage fluctuations to be ignored. The adjustment range lies between 0.85 and 1.05 times the nominal voltage, while for variant /1_ _ a range of 0.9 to 1.25 times nominal voltage is specified. The drop-out ratio (hysteresis) is 0.75 to 0.95 of the set value, ensuring stable switching behavior. Repeatability is ±0.5 %, enabling high precision in voltage monitoring.
Technology Explained Simply
The relay operates without auxiliary voltage, meaning it connects directly to the voltage source to be monitored. For DC voltages above 60 V, such as 127 V DC here, an external resistor is required, connected to terminals e and z. The measured voltage is connected to terminals e and f. LED indicators show the operating status: the upper LED lights up when operating voltage is present, the lower LED when the output relay is activated. The nominal consumption is 6 VA / 10 W, and the device is designed for an operating temperature range of -20 to +60 °C.
Compatibility and Accessories
For operation with 127 V DC, the external resistor ZWS 20 SL 1.6 kΩ 20 W is required, available as an accessory. The connection terminals are designed for connecting the external resistor and the measured voltage. Switching capacity is up to 2 A at 230 V AC for make contacts and 1 A for break contacts (AC 15). For DC (DC 13), switching capacity is 1 A at 24 V DC. Electrical life is 1.5 x 10⁵ switching operations at 6 A and AC 230 V, mechanical life is 30 x 10⁶ switching operations.
Mounting and Installation
The relay is mounted in enclosures and designed for continuous operation. Mounting is done in a 45 mm width, standard in enclosure technology. Connection terminals are clearly labeled, with terminal z reserved exclusively for the external resistor. The heat generation of the resistor requires appropriate mounting position with sufficient distance from adjacent components to ensure adequate shock protection.
Operational Advantages
Early detection of voltage drops enables preventive maintenance and reduces the likelihood of system downtime. The adjustable pickup delay prevents false alarms caused by short-term voltage fluctuations. LED indicators provide visual feedback on operating status, speeding up fault localization. Compliance with IEC/EN 60255-1 ensures reliability and safety in industrial applications. Operation without auxiliary voltage reduces installation complexity and lowers connection costs.
Approvals and Markings
The device carries CCC certification, confirming compliance with relevant safety and quality standards. Compliance with IEC/EN 60255-1 ensures suitability for use in industrial monitoring systems. Maximum nominal voltage is AC 400 V, with this device variant designed for DC 127 V. Frequency range is ±5 % at nominal frequencies of 50 or 60 Hz. Temperature dependence of the measured value is less than 0.05 % per Kelvin, enabling high stability under varying ambient conditions.