Dold 0028423 BA9043/001 3AC50-400Hz 100V undervoltage relay
|
262,20 EUR |
|||||||||||
|
( 312,02 EUR incl. VAT ) ≈ £219.46 | ≈ $288.16 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1153814 | ||||||||||
| Mfg Part No: | 0028423 | ||||||||||
| UPC/EAN: | 4030641284237 | ||||||||||
| Weight: | 0.34 kg | ||||||||||
| Type: | BA9043/001 3AC50-400HZ 100V | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0028423:
Applications
This relay is suitable for industrial applications as well as railway applications. It monitors 3-phase AC networks and is mounted in enclosures. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is from -25 °C to +60 °C. The operating altitude is limited to a maximum of 2000 m above sea level. The devices comply with IEC/EN 60255-1 standards and meet the requirements of overvoltage category III.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, designed for switching operations with a thermal current of up to 6 A per contact. The switching capacities are 2 A/AC 230 V for make contacts and 1 A/AC 230 V for break contacts according to IEC/EN 60947-5-1. The electrical life expectancy is at least 200,000 switching operations at 3 A/AC 230 V and cos ϕ = 1. The mechanical life expectancy exceeds 30 million switching operations. The nominal power consumption is 4 VA.
Technology Explained Simply
The arithmetic mean value measurement enables precise voltage monitoring by averaging the voltage values of the individual phases. In case of undervoltage below the set pickup value, the relay disconnects the output contacts. The LED indicators signal operational readiness (red LED) and contact position (green LED). The device is insensitive to harmonics, meaning it operates reliably even during network disturbances caused by harmonics. The pickup delay ensures that short-term voltage dips do not trigger false alarms.
Compatibility and Accessories
The relay is designed for networks without a neutral conductor and can be used in 3p3w systems. It is certified with UKCA and CCC approvals. Mounting is done on a DIN rail in accordance with IEC/EN 60715. The terminals are designed for 2 x 2.5 mm² solid or 2 x 1.5 mm² flexible conductors with shrink tubing. Fixing is achieved using M3.5 plus-minus screws with self-lifting clips. Dimensions are 45 mm width, 73 mm height, and 132 mm depth.
Mounting and Installation
Installation is carried out in an enclosure on a DIN rail. The connection terminals are intended for connection to the phases L1, L2, and L3 to be monitored. The output contacts (11, 12, 14 and 21, 22, 24) are connected to the loads to be protected. Adjustment of the pickup and dropout values is done via the rotary potentiometers on the front panel. The devices are designed for continuous operation and do not require additional auxiliary voltage.
Advantages in Operation
Preventive maintenance is supported by continuous monitoring of the network voltage. Rapid fault localization enables efficient troubleshooting. The high service life and reliability of the relay contribute to increased productivity. The LED indicators facilitate visual monitoring of the operating status. Insensitivity to harmonics ensures stable operation even in electrically stressed networks. Simple operation via rotary potentiometers reduces installation and maintenance time.
More spare projector bulbs for your Epson Beamer
| Technical data | |
| 1- / 3-phase | 3 |
| Auxiliary voltage | Without |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | 3/N AC 690 / 400 V |
| Output contacts | 2 C/O contacts |
| Width | 45 mm |
| Type | BA 9043 |
| Operate delay | |
| Variant | |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | 3AC 100 V |
| Time delay | without |
| Approvals and Markings | UKCA, CCC |
| Variant | For 3p3w systems |
Questions & answers
What is the delivery time of Dold 0028423 BA9043/001 3AC50-400Hz 100V undervoltage relay?
The article Dold 0028423 BA9043/001 3AC50-400Hz 100V undervoltage relay is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0028423 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0028423 BA9043/001 3AC50-400Hz 100V undervoltage relay always at the best possible price. We can give you a discount of 2% on Dold 0028423 BA9043/001 3AC50-400Hz 100V undervoltage relay if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0028423 BA9043/001 3AC50-400Hz 100V undervoltage relay we can offer you a price of 250,40 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.