Dold 0026431 BA9036 AC50Hz 220V voltage relay
|
233,82 EUR |
|||||||||||
|
( 278,25 EUR incl. VAT ) ≈ £195.71 | ≈ $256.97 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1002183 | ||||||||||
| Mfg Part No: | 0026431 | ||||||||||
| UPC/EAN: | 4030641264314 | ||||||||||
| Weight: | 0.34 kg | ||||||||||
| Type: | BA9036 AC50HZ 220V | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0026431:
Applications
This relay is suitable for use in industrial installations, machine controls, pump and fan systems, as well as in systems requiring high operational safety. It monitors voltages in the range of 24 to 400 V, with the nominal voltage for this variant being AC 220 V at 50 Hz. The maximum nominal voltage is AC 400 V. The devices comply with IEC/EN 60255-1, confirming adherence to international standards for measuring and protective devices in electrical installations.
Functions and Equipment in Detail
The relay features 2 changeover contacts as output contacts, which can be used to control auxiliary circuits or warning signals. The contact configuration allows both closing and opening functions. The pickup delay is built-in and can be adjusted between 0.5 and 10 seconds, with this function only active when the voltage exceeds 60 % of the nominal voltage. The reset values are hysteresis-controlled and range between 75 % and 95 % of the set pickup value, ensuring stable and jerk-free switching operation. The repeatability accuracy is ± 0.5 %, ensuring high precision in repeated measurements.
Technology Explained Simply
The device operates without auxiliary power, meaning it is directly connected to the voltage source to be monitored and does not require additional power supply. Operational readiness is indicated by an LED display, which lights up when the operating voltage is present. A second LED indicates the state of the output relay, i.e., whether the contact is closed or open. For DC voltages above 60 V, an external resistor is required, connected to terminals e and z. The measured voltage is connected to terminals e and f. The use of an external resistor is necessary to reduce the voltage to a level suitable for the device.
Compatibility and Accessories
The relay is designed for use with external resistors, which are required for DC voltages above 60 V. The combination with these resistors enables the relay's application in DC systems with higher voltages.
Mounting and Installation
Mounting is carried out in enclosures, with a width of 45 mm allowing standard installation in DIN or enclosure formats. Connections are made via terminals, with terminals e, f, and z designated for voltage monitoring and the external resistor. Installation requires adherence to safety instructions, particularly when using external resistors, which become very hot during operation and must be mounted with appropriate shielding.
Advantages in Operation
By detecting voltage dips early, the relay enables preventive maintenance and reduces the likelihood of system failures. The LED indicators facilitate diagnosis and fault localization. The adjustable pickup and reset values, as well as the pickup delay, offer flexibility in adapting to different applications. The high mechanical life of 30 million switching operations and the electrical life of 150,000 switching operations at 6 A and AC 230 V ensure long service life. Short-circuit resistance is ensured with a maximum fuse rating of 4 A gG / gL according to IEC/EN 60947-5-1.
| Technical data | |
| 1- / 3-phase | 1 |
| Auxiliary voltage | Without |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | AC 400 V |
| Output contacts | 2 C/O contacts |
| Width | 45 mm |
| Type | BA 9036 |
| Operate delay | |
| Variant | |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | AC 220 V 50 Hz |
| Time delay | without |
| Approvals and Markings | CCC |
| Variant | Undervoltage relay. Closed circuit operation |
Questions & answers
What is the delivery time of Dold 0026431 BA9036 AC50Hz 220V voltage relay?
The article Dold 0026431 BA9036 AC50Hz 220V voltage relay is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0026431 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0026431 BA9036 AC50Hz 220V voltage relay always at the best possible price. We can give you a discount of 2% on Dold 0026431 BA9036 AC50Hz 220V voltage relay if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 5 pieces of Dold 0026431 BA9036 AC50Hz 220V voltage relay we can offer you a price of 223,30 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.