Product information for DEHN 961105:
Applications
The arrester is intended for indoor use and is installed at the interface between the lightning protection system and the electrical installation. It is particularly suitable for TT systems, where the neutral conductor and protective conductor are separated in the consumer system. The application is carried out within the framework of lightning protection concepts according to DIN EN 62305-4, where it diverts overvoltages in the N-PE connection area to protect the electrical installation and connected devices.
Functions and Equipment in Detail
The DGP M 255 FM features RADAX-Flow spark gap technology, enabling reliable and rapid diversion of overvoltages. The response time is ≤ 100 ns, ensuring a very fast reaction to overvoltage events. The functional and fault indication is provided via a viewing window with green (functional) and red (faulty) markings, allowing visual inspection of the status without additional measuring instruments. The arrester is optionally equipped with a remote signaling contact (voltage-free changeover contact) that can be used for monitoring systems.
Technology Explained Simply
The arrester is designed for a maximum continuous voltage (UC) of 255 V (50/60 Hz) and can divert a lightning impulse current of 100 kA (10/350 µs). The protection level (UP) is ≤ 1.5 kV, meaning the voltage in the protected area is limited to below this value. The follow current interruption capability is 100 Aeff, describing the ability to safely interrupt the follow current flowing after the lightning impulse. The TOV withstand (1200 V / 200 ms) ensures the stability of the device under temporary overvoltages. The specific energy (W/R) of 2.50 MJ/Ohm indicates the energy absorption capacity of the arrester.
Compatibility and Accessories
The arrester is modular in design and can be used in combination with other DEHNgap modules. It is directly compatible with the N-PE arrester DEHNgap C S from the Red/Line family. Installation is carried out on a 35 mm DIN rail according to EN 60715. The connection cross-sections are at least 10 mm² (single- or fine-stranded) and up to 50 mm² (multi-stranded) or 35 mm² (fine-stranded) for N and PE, and up to 35 mm² (multi-stranded) or 25 mm² (fine-stranded) for the remote signaling contact. The switching capacity of the remote signaling contact is 250 V / 0.5 A (AC) and 250 V / 0.1 A (DC), 125 V / 0.2 A (DC), as well as 75 V / 0.5 A (DC).
Installation and Mounting
Mounting is carried out on a 35 mm DIN rail according to EN 60715. The device has a mounting width of 2 TE (DIN 43880) and is intended for indoor use. The operating temperature ranges are -40 °C to +80 °C (parallel wiring) and -40 °C to +60 °C (through wiring). The housing is made of a thermoplastic material in red, certified to UL 94 V-0, and offers a protection rating of IP 20.
Operational Advantages
The arrester offers high reliability through RADAX-Flow spark gap technology and integrated fault indication. The modular design allows flexible adaptation to different circuit variants. The remote signaling function enables integration into monitoring systems, allowing the status of the arrester to be continuously monitored. The certifications from VDE, KEMA, and UL underscore the quality and safety of the product.
| General | |
| SPD according to EN 61643-11 / IEC 61643-11 | type 1 / class I |
| Max. continuous operating voltage (AC) (UC) | 255 V (50 / 60 Hz) |
| Lightning impulse current (10/350 µs) (Iimp) | 100 kA |
| Voltage protection level (UP) | ≤ 1.5 kV |
| Approvals | VDE, KEMA, UL |
| Type of remote signalling contact | changeover contact |
Questions & answers
What is the delivery time of DEHN 961105 DGP M 255 FM gap M N-PE lightning surge arrester for TT systems?
The article DEHN 961105 DGP M 255 FM gap M N-PE lightning surge arrester for TT systems is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of DEHN 961105 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you DEHN 961105 DGP M 255 FM gap M N-PE lightning surge arrester for TT systems always at the best possible price. We can give you a discount of 2% on DEHN 961105 DGP M 255 FM gap M N-PE lightning surge arrester for TT systems if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of DEHN 961105 DGP M 255 FM gap M N-PE lightning surge arrester for TT systems we can offer you a price of 389,44 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.