DEHN 961105, EAN: 4013364118683

DEHN 961105 DGP M 255 FM surge arrester TT system

Installation > Grounding Systems > Lightning protection material

DEHN 961105 DGP M 255 FM surge arrester TT system

Lieske Part No. 270013
Mfg Part No 961105
EAN-Code 4013364118683
Manufacturer DEHN
Here only 414,30 EUR
493,02 EUR incl. VAT

Further information for DEHN 961105 DGP M 255 FM surge arrester TT system

General
SPD according to EN 61643-11 / IEC 61643-11type 1 / class I
Max. continuous operating voltage (AC) (UC)255 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) (Iimp)100 kA
Voltage protection level (UP)≤ 1.5 kV
ApprovalsVDE, KEMA, UL
Type of remote signalling contactchangeover contact
The DEHN DGP M 255 FM is a single-pole, modular N-PE surge arrester from the DEHNgap product family, specifically designed for use in TT systems. It serves as a total current arrester in 3+1 and 1+1 configurations according to DIN VDE 0100-534 between the neutral conductor (N) and the protective conductor (PE). The arrester is designed to protect low-voltage consumer installations against overvoltages, even in the event of direct lightning strikes, and is used in the lightning protection zone concept at interfaces 0A to 1. It complies with standard EN 61643-11 / IEC 61643-11 as Type 1 / Class I and is therefore suitable for diverting high lightning currents.

Applications

The arrester is intended for indoor use and is installed at the interface between the lightning protection system and the electrical installation. It is particularly suitable for TT systems, where the neutral conductor and protective conductor are separated in the consumer system. The application is carried out within the framework of lightning protection concepts according to DIN EN 62305-4, where it diverts overvoltages in the N-PE connection area to protect the electrical installation and connected devices.

Functions and Equipment in Detail

The DGP M 255 FM features RADAX-Flow spark gap technology, enabling reliable and rapid diversion of overvoltages. The response time is ≤ 100 ns, ensuring a very fast reaction to overvoltage events. The functional and fault indication is provided via a viewing window with green (functional) and red (faulty) markings, allowing visual inspection of the status without additional measuring instruments. The arrester is optionally equipped with a remote signaling contact (voltage-free changeover contact) that can be used for monitoring systems.

Technology Explained Simply

The arrester is designed for a maximum continuous voltage (UC) of 255 V (50/60 Hz) and can divert a lightning impulse current of 100 kA (10/350 µs). The protection level (UP) is ≤ 1.5 kV, meaning the voltage in the protected area is limited to below this value. The follow current interruption capability is 100 Aeff, describing the ability to safely interrupt the follow current flowing after the lightning impulse. The TOV withstand (1200 V / 200 ms) ensures the stability of the device under temporary overvoltages. The specific energy (W/R) of 2.50 MJ/Ohm indicates the energy absorption capacity of the arrester.

Compatibility and Accessories

The arrester is modular in design and can be used in combination with other DEHNgap modules. It is directly compatible with the N-PE arrester DEHNgap C S from the Red/Line family. Installation is carried out on a 35 mm DIN rail according to EN 60715. The connection cross-sections are at least 10 mm² (single- or fine-stranded) and up to 50 mm² (multi-stranded) or 35 mm² (fine-stranded) for N and PE, and up to 35 mm² (multi-stranded) or 25 mm² (fine-stranded) for the remote signaling contact. The switching capacity of the remote signaling contact is 250 V / 0.5 A (AC) and 250 V / 0.1 A (DC), 125 V / 0.2 A (DC), as well as 75 V / 0.5 A (DC).

Installation and Mounting

Mounting is carried out on a 35 mm DIN rail according to EN 60715. The device has a mounting width of 2 TE (DIN 43880) and is intended for indoor use. The operating temperature ranges are -40 °C to +80 °C (parallel wiring) and -40 °C to +60 °C (through wiring). The housing is made of a thermoplastic material in red, certified to UL 94 V-0, and offers a protection rating of IP 20.

Operational Advantages

The arrester offers high reliability through RADAX-Flow spark gap technology and integrated fault indication. The modular design allows flexible adaptation to different circuit variants. The remote signaling function enables integration into monitoring systems, allowing the status of the arrester to be continuously monitored. The certifications from VDE, KEMA, and UL underscore the quality and safety of the product.