Zander Aachen SR3A 115V 50-60Hz Safety switching device
|
on request |
|
| Delivery time on requestinfo_outline | |
| Lieske Part No.: | 1599676 |
|---|---|
| Mfg Part No: | SR3A 115V 50-60Hz |
| Weight: | 310 kg |
Product information for Zander Aachen SR3A 115V 50-60Hz:
The SR3D is a universal safety control device with three safe relay outputs that ensures the fast and safe shutdown of moving parts of a machine or system in the event of danger. It is specifically designed for use in continuous operation of firing systems in accordance with EN 50156-1 and EN 746-2, as well as for use on ships, for which it has been certified by TÜV Rheinland and Germanischer Lloyd.
---
### Key Features of the SR3D
- Two start modes available: - Monitored manual start
- Cross-fault and ground-fault monitoring
- Use up to PL e, SILCL 3, Category 4 – Meets the highest safety requirements
- Automatic start
---
### Technical Functions of the SR3D
- 3 safe relay outputs (redundant and diverse)
- 1 auxiliary contact (signal contact) for status indication
- Force-guided relays for maximum operational safety
- Cyclic monitoring of relay contacts – Ensures that the safety function is maintained even in the event of internal faults
- Feedback circuit to monitor downstream contactors or expansion modules
- Status display via LED – Clear visualization of the switching states
---
### Connection Options
The SR3D allows direct connection of the following devices:
- Emergency stop buttons
- Safety switches
- Contactless safety switches
- Safety components with OSSD outputs
This flexibility makes the SR3D ideal for a wide range of machines and systems requiring diverse safety requirements.
---
### Application Areas of the SR3D
- Emergency stop circuits (single- or dual-channel)
- Protective guard monitoring on machines and systems
- Control of firing systems
- Ship applications (certified by Germanischer Lloyd)
---
### Safety Functions in Detail
The SR3D guarantees the safe separation of safety circuits in accordance with EN 60204-1, enabling a safety stop function up to PL e / SIL 3 in accordance with EN ISO 13849-1 and IEC 61508.
- Standard-compliant shutdown: When an emergency stop button is pressed, the release paths are immediately opened, and the machine is safely shut down.
- Redundant relays: Even if one relay fails, the function is maintained, as the cyclic self-monitoring detects and addresses errors.
---
### Mounting Instructions
For flawless operation, the following guidelines must be observed:
- Mounting on a 35 mm DIN rail according to EN 60715 TH35
- Minimum protection class IP54 – Must be installed in control cabinets with sufficient heat dissipation
- Distance from adjacent devices: For the AC 115 V / 230 V variant, a distance of at least 10 mm from adjacent devices must be maintained.
---
### Certificates and Conformity
- EN ISO 13849-1 – Functional safety up to PL e
- EN 50156-1 – Safety of firing systems
- Germanischer Lloyd certificate – Approved for use on ships
Questions & answers
What is the delivery time of Zander Aachen SR3A 115V 50-60Hz Safety switching device?
The article Zander Aachen SR3A 115V 50-60Hz Safety switching device is currently not in stock und muss auftragsbezogen bestellt werden.
According to our experience the article is ready for dispatch within 5 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Zander Aachen SR3A 115V 50-60Hz to our sales team for an exact delivery time.