VDE-Kabel G128096 NHXH-J E30 5x25 mm² orange halogen-free sheathed cable
|
24,88 EUR |
|
|
incl. 15,78 EUR copper surcharge ( 29,61 EUR incl. VAT ) ≈ £20.80 | ≈ $27.49 plus delivery charges: 55,00 € |
|
| Made to order · Delivery time approx. 20 workdaysinfo_outline | |
| Lieske Part No.: | 983327 |
|---|---|
| Mfg Part No: | G128096 |
| Weight: | 1.785 kg |
| Type: | NHXH-E30 5 X 25,0 |
Product information for VDE-Kabel G128096:
Applications
This cable is used in areas where a high fire protection standard is required, such as hospitals, administrative buildings, schools, or public facilities. It is particularly suitable for systems that must continue to function during a fire to enable evacuation or ensure user safety. Installation is carried out indoors, with mechanical protection ensured by appropriate support systems such as cable trays, cable ladders, or ceiling installations. Conduit installation is permitted, provided the conduits are not filled with water.
Functions and Equipment in Detail
The cable features a cross-linked, halogen-free, ceramizing two-layer insulation (HXI2), providing high heat resistance and fire retardancy. Conductor identification follows VDE 0293-308, enabling clear identification of conductors. The common conductor sheathing and orange outer jacket made of halogen-free polymer mixture ensure clear visual distinction and additional protection. Conductors are made of bare copper, either single or multi-strand, ensuring good electrical conductivity.
Technology Explained Simply
The ceramization of the insulation means that at high temperatures, the insulation transforms into a ceramic layer, preventing electrical contact between conductors and thus maintaining cable functionality during a fire. The E30 functional integrity test according to DIN 4102-12 ensures the cable retains its electrical function for 30 minutes at a fire temperature of 800 °C. Flame retardancy according to EN 50266-2-4 and IEC 60332-3 Cat.C, as well as insulation integrity FE 180 according to VDE 0472 T. 814, guarantee safe behavior in case of fire. The halogen-free composition prevents the release of toxic and corrosive gases and smoke formation, facilitating evacuation.
Compatibility and Accessories
The cable is designed for use in standard support systems such as cable trays, cable ladders, and ceiling installations. It is suitable for systems intended for emergency lighting, fire alarm systems, and alarm systems according to VDE 108. Installation requires adherence to specified bending radii: 15 times the cable diameter for single-core and 12 times for multi-core conductors. The rated voltage is 300/500 V, the test voltage is 2000 V. Temperature ranges are +5 °C to +70 °C during installation and -30 °C to +70 °C after installation.
Installation and Mounting
During installation, the cable must be protected against external mechanical influences. Installation is carried out indoors, with conduit installation only permitted if no water accumulation occurs. Bending radii must be observed to avoid damage to conductors or insulation. Installation in earth or water is not allowed. Conductor identification according to VDE 0293-308 facilitates correct assignment of conductors during installation.
Operational Advantages
The cable provides high safety in case of fire through E30 functional integrity, flame retardancy, and minimal smoke emission. The halogen-free composition protects people from toxic gases and prevents corrosion effects on electrical equipment. The ceramizing insulation ensures stable electrical insulation even at high temperatures. Use in safety systems guarantees that critical functions such as lighting or alarm systems continue to operate in emergencies.
| General | |
| Nominal voltage | 300/500 V |
| Test voltage | 2000 V |
| Installation temperature range | +5 °C |
| Temperature range after installation | -30 °C |
| Bend radius single-core | 15 x cable diameter |
| Bending radius multi-core | 12 x cable diameter |
| Flame retardancy | EN 50266-2-4, IEC 60332-3 Cat.C |
| Insulation integrity | FE 180 according to VDE 0472 T. 814 |
| Circuit integrity | E30 according to DIN 4102-12 |
| Conductor marking | VDE 0293-308 |
| Sheath colour | Orange |
| Conductor material | bare copper |
| Insulation type | Networked, halogen-free, ceramizing 2-layer insulation HXI2 |
| Features | halogen-free, flame-retardant, minimal smoke emission, no corrosive gases |
The final cable weight will be determined before invoicing. The calculation is based on the copper content and any additional weight due to drums, pallets, or outer packaging. Prices are subject to this subsequent calculation.
Please note that for cables, that are not in stock and must be produced, the manufacturer may need an order of a minimum length that can be 5-10km depending on cable type!
Questions & answers
What is the delivery time of VDE-Kabel G128096 NHXH-J E30 5x25 mm² orange halogen-free sheathed cable?
The article VDE-Kabel G128096 NHXH-J E30 5x25 mm² orange halogen-free sheathed cable is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of VDE-Kabel G128096 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you VDE-Kabel G128096 NHXH-J E30 5x25 mm² orange halogen-free sheathed cable always at the best possible price. We can give you a discount of 2% on VDE-Kabel G128096 NHXH-J E30 5x25 mm² orange halogen-free sheathed cable if you choose payment in advance on ordering.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.