Schneider Electric RM35HZ21FM Frequency monitor 50/60 Hz 120–277 V 2 W
|
172,90 EUR 180,18 EUR |
|||||||||||
|
( 205,75 EUR incl. VAT ) ≈ £144.54 | ≈ $192.44 plus delivery charges: 55,00 € |
|||||||||||
| Made to order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 840608 | ||||||||||
| Mfg Part No: | RM35HZ21FM | ||||||||||
| UPC/EAN: | 3389119405201 | ||||||||||
| Weight: | 0.126 kg | ||||||||||
| Type: | RM35HZ21FM | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Schneider Electric RM35HZ21FM:
| Complementary | |
| Reset time | 2000 ms time delay |
| Maximum switching voltage | 250 V AC/DC |
| [Us] rated supply voltage | 120...277 V AC |
| [Un] rated nominal voltage | 120...277 V AC, non self-powered |
| Supply voltage limits | 102…308 V AC |
| Control circuit frequency | 40...70 Hz |
| Width | 35 mm |
| Output contacts | 1 C/O + 1 C/O |
| Contacts material | Cadmium free |
| nominal output current | 5 A |
| maximum input frequency | 70 Hz |
| Maximum measuring cycle | 200 ms measurement cycle as true rms value |
| delay at power up | 0.5 s |
| Hysteresis | 0.3 % fixed |
| Measurement accuracy | +/- 10 % of the full scale value in input; +/- 10 % of the full scale value in time delay |
| Repeat accuracy | +/- 0.5 % for input and measurement circuit; +/- 0.5 % for time delay |
| Measurement error | +/- 0.05 %/°C with temperature variation; < +/- 1 % over the whole range with voltage variation |
| Threshold setting | -2...10 Hz; -10...2 Hz |
| Marking | CE : 73/23/EEC; CE : EMC 89/336/EEC |
| Overvoltage category | III conforming to IEC 60664-1 |
| Insulation resistance | > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5; > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1; > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5; > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1; > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5; > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1 |
| [Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
| operating voltage tolerance | - 15 % + 10 % Un |
| Supply frequency | 50/60 Hz +/- 10 % |
| Insulation | No galvanic insulation between supply and measurement |
| Operating position | Any position without derating |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (20 AWG...11 AWG) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...12 AWG) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| local signalling | 1 LED green for power ON; 1 LED yellow for correct frequency (high R1); 1 LED yellow for correct frequency (low R2) |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| Control type | Without test button |
| Contractual warranty | |
| Warranty (in months) | 18 |
| Environment | |
| Immunity to microbreaks | 10 ms |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
| Standards | IEC 60255-6; NF EN 60255-6 |
| Product certifications | GL; UL; CSA; C-Tick; GOST |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| Vibration resistance | 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1; 1 gn (f= 57.6…150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60255-21-1 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV AC 50 Hz |
| Non-dissipating shock wave | 4 kV |
| Logistical informations | |
| Country of origin | ID |
| Main | |
| Range of product | Harmony Control Relays |
| Relay type | Frequency control relays |
| Product or component type | Frequency control relay |
| Relay name | RM35HZ21FM |
| Relay monitored parameters | Overfrequency and underfrequency 50 or 60 Hz |
| Time delay type | Adjustable 0.1...10 s, +/- 10 % Tt- time delay upon fault |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum power consumption in VA | 6 VA AC |
| Measurement range | 40...70 Hz |
| Utilisation category | AC-12 conforming to IEC 60947-5-1; AC-13 conforming to IEC 60947-5-1; AC-14 conforming to IEC 60947-5-1; AC-15 conforming to IEC 60947-5-1; DC-12 conforming to IEC 60947-5-1; DC-13 conforming to IEC 60947-5-1; DC-14 conforming to IEC 60947-5-1 |
| Packing Units | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.600 cm |
| Package 1 Width | 8.000 cm |
| Package 1 Length | 9.700 cm |
| Package 1 Weight | 126.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 48 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.838 kg |
Questions & answers
What is the delivery time of Schneider Electric RM35HZ21FM Frequency monitor 50/60 Hz 120–277 V 2 W?
The article Schneider Electric RM35HZ21FM Frequency monitor 50/60 Hz 120–277 V 2 W is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Schneider Electric RM35HZ21FM to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Schneider Electric RM35HZ21FM Frequency monitor 50/60 Hz 120–277 V 2 W always at the best possible price. We can give you a discount of 2% on Schneider Electric RM35HZ21FM Frequency monitor 50/60 Hz 120–277 V 2 W if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 5 pieces of Schneider Electric RM35HZ21FM Frequency monitor 50/60 Hz 120–277 V 2 W we can offer you a price of 166,42 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.
Fitting accessory for Schneider Electric RM35HZ21FM Frequency monitor 50/60 Hz 120–277 V 2 W
|
Schneider Electric RM35TF30 multifunction phase monitor 194-528 VAC
Harmony Control. This network monitoring relay monitors three-phase networks (220-480 VAC in 6 stages) for phase sequence, phase failure, phase asymmetry (5-15%), overvoltage and undervoltage in ...Lieske Part No.: 601987 Mfg Part No: RM35TF30 |
200,45 EUR 208,89 EUR
![]() ≈ £167.58 | ≈ $223.10
Made to order · Delivery time approx. 20 workdaysinfo_outline
|
|
Schneider Electric RM17TE00 multifunction phase monitor 183-528 VAC
Harmony Control. This network monitoring relay monitors three-phase networks for phase sequence, phase failure, phase asymmetry (5-15%), overvoltage and undervoltage in window mode (2-20%). A relay ...Lieske Part No.: 602197 Mfg Part No: RM17TE00 |
159,13 EUR 165,83 EUR
![]() ≈ £133.03 | ≈ $177.11
Made to order · Delivery time approx. 20 workdaysinfo_outline
|
|
Schneider Electric RM22TR33 network monitoring phase sequence/failure, over- and under-voltage 380–480 V AC, 2 AC
Harmony Control. This network monitoring relay monitors three-phase networks (380-480 VAC) for phase sequence, phase failure, undervoltage and overvoltage. Two relay changeovers are available for ...Lieske Part No.: 633304 Mfg Part No: RM22TR33 |
153,42 EUR 159,89 EUR
![]() ≈ £128.26 | ≈ $170.76
Delivery time from supplier's stock (ca.) 2 workdaysinfo_outline
|
|
Schneider Electric RM22TG20 voltage monitoring on phase sequence/failure 208–480 VAC 2W
Harmony Control. Dieses Netzüberwachungsrelais überwacht Drehstromnetze (208-480 VAC) auf Phasenfolge und Phasenausfall. Zur Meldung sind zwei Relaiswechsler vorhanden, die bis 8 A belastbar ist.Lieske Part No.: 872768 Mfg Part No: RM22TG20 |
79,61 EUR 82,96 EUR
![]() ≈ £66.55 | ≈ $88.61
Delivery time from supplier's stock (ca.) 2 workdaysinfo_outline
|
|
Schneider Electric RMNF22TB30 network monitoring multifunctional 208-480 VAC
This 3-phase control relay belongs to the Harmony control relay range from Schneider Electric. This 3-phase control relay is equipped with NFC technology which allows digital operation instead of ...Lieske Part No.: 1778522 Mfg Part No: RMNF22TB30 |
149,15 EUR 155,43 EUR
![]() ≈ £124.69 | ≈ $166.00
Made to order · Delivery time approx. 20 workdaysinfo_outline
|