Schneider Electric METSEION7413 power analyzer PowerLogic ION7413, DC, for DIN rail
|
-16% 3.202,75 EUR 3.803,27 EUR |
|
|
( 3.811,27 EUR incl. VAT ) ≈ £2,677.50 | ≈ $3,539.04 plus delivery charges: 55,00 € |
|
| Made to order · Delivery time approx. 30 workdaysinfo_outline | |
| Datasheet: | file_download Download |
|---|---|
| Lieske Part No.: | 1866007 |
| Mfg Part No: | METSEION7413 |
| UPC/EAN: | 3606481384584 |
| Weight: | 1.03 kg |
| Type: | METSEION7413 |
Product information for Schneider Electric METSEION7413:
| Additional features | |
| Power quality analysis | Complies with EN 50160: 2010 conformity report; complies with IEEE 519: 2014 conformity report; complies with IEC 61000-4-30: Class S power quality measurement; up to the 63rd harmonic; harmonic distortion; waveform capture; detection of voltage sags and overvoltages; programmability (logical and mathematical functions); complies with IEC 62586 power quality monitoring; complies with IEC 61000-4-15 disturbance direction detection; rapid voltage change |
| Device application | Capture of S0 pulses for measurement of water, air, gas, electricity, steam; current monitoring; data aggregation; revenue settlement |
| Measured value type | current; voltage; frequency; total active and reactive power; total apparent power; total power factor; active and reactive power per phase, RMS; apparent power per phase, RMS; power factor per phase, RMS; active and reactive energy; apparent energy |
| Supply voltage | 20 - 60 V DC ± 10 % |
| Network frequency | 50 Hz; 60 Hz |
| [In] Rated current | 10 A; 1 A; 5 A |
| Pole description | 1P + N; 3P; 3P + N |
| Power consumption in W | 17 W |
| Display type | Without display |
| Scanning interval | 256 samples/cycle |
| Measurement current | 50…10000 mA |
| Analogue input type | Voltage (impedance 5 MOhm); current (impedance 0.3 mOhm) |
| Measuring voltage | 57…400 V AC 42 - 69 Hz between phase and neutral; 100…690 V AC 42 - 69 Hz between phases |
| Measuring range for frequency | 42…69 Hz |
| Number of inputs | 3 digital 30 V AC; 3 digital 60 V DC |
| Accuracy of measurement | Current ± 0.1 %; Voltage ± 0.1 %; Active energy ± 0.2 % |
| Accuracy class | Class 0.2S active energy corresponds to IEC 62053-22; Class 0.2 active energy corresponds to ANSI C12.20; Class 0.2 active power corresponds to IEC 61557-12; Class 0.5S reactive energy corresponds to IEC 62053-24; Class 0.5 power factor corresponds to IEC 61557-12; Class 0.2 voltage corresponds to IEC 61557-12; Class 0.2 current corresponds to IEC 61557-12; Class 0.2 frequency corresponds to IEC 61557-12; Class 0.2 active energy corresponds to IEC 61557-12 |
| Number of outputs | 1 impulse |
| Displayed information | Voltage; current; frequency; power; energy consumption; harmonic distortion |
| Communications protocol | Modbus RTU at 115 kBaud - 2-wire; ION at 115 kBaud - 2-wire; DNP3; IEC 61850; Modbus TCP/IP; Ethernet Modbus TCP/IP daisy chain at 10/100 Mbit/s; RSTP 801.1d 2004; DLMS |
| Support for communication interfaces | Ethernet; Screw terminal block: RS485; Mini-B-USB: USB |
| Communication network type | IPv6 (Internet protocol) |
| Data logging | Sequence of event recording; trend curves/forecasts; harmonic logs; timestamping; GPS synchronization; waveform logs; minimum/maximum values of real-time values; capture of voltage sags and overvoltages; data logs; event recording; alarm logs; 50 data loggers |
| Memory capacity | 512 MB |
| Web services | Customizable homepage; uploading/downloading files via FTP; uploading/downloading files via SFTP; web server; alarm notification by email; display of captured waveform (FTP); display of captured waveform (web); HTTPS server |
| Communication service | NTP time synchronization; E-mail notification via SMTP; RSTP support; DHCP; SNMP; PTP time synchronization |
| Cybersecurity | Activation/deactivation of communication ports; robust security protocols; hardening; password protection; Syslog logging support |
| Mounting mode | Plug-in |
| Mounting bracket | DIN rail |
| Installation type | Indoor installation |
| Installation category | III |
| Safety design | III400…690 V complies with IEC 61010-1:Ed. 3; III400…690 V complies with EN 61010-1:Ed. 3; III347…600 V complies with UL 61010-1:Ed. 3; III347…600 V complies with CSA C22.2 No. 61010-1:Ed. 3 |
| Standards | IEC 61326-1; IEC 62053-22; IEC 62053-24; IEC 62052-11; IEC 61557-12; IEEE 1588; IEC 62586 |
| Product certifications | CE; CULus; N998 |
| Width | 90,5 mm |
| Depth | 90,8 mm |
| Height | 90,5 mm |
| Product weight | 528 g |
| Contractual warranty | |
| Warranty (in months) | 18 |
| Main features | |
| Product series | PowerLogic |
| Product name | PowerLogic ION7400 |
| Product or component type | Power meter |
| Device short name | ION7413 |
| Model type | Standard |
| Mounting | |
| Degree of protection (IP) | IP30 corresponds to IEC 60529 |
| Relative humidity | 5…95 % |
| Operating ambient temperature | -25…70 °C |
| Ambient temperature during storage | -40…85 °C |
| Operating altitude | 3.000 m |
| Packaging units | |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 14,000 cm |
| VPE 1 width | 14,000 cm |
| VPE 1 length | 18,500 cm |
| Packaging weight (Lbs) | 1,030 kg |
| VPE 2 type | S03 |
| VPE 2 quantity | 6 |
| VPE 2 height | 30,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 6,621 kg |
| VPE 3 type | P12 |
| VPE 3 quantity | 48 |
| VPE 3 height | 45,000 cm |
| VPE 3 width | 80,000 cm |
| VPE 3 length | 120,000 cm |
| VPE 3 weight | 64,968 kg |
Questions & answers
What is the delivery time of Schneider Electric METSEION7413 power analyzer PowerLogic ION7413, DC, for DIN rail?
The article Schneider Electric METSEION7413 power analyzer PowerLogic ION7413, DC, for DIN rail is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 30 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Schneider Electric METSEION7413 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Schneider Electric METSEION7413 power analyzer PowerLogic ION7413, DC, for DIN rail always at the best possible price. We can give you a discount of 2% on Schneider Electric METSEION7413 power analyzer PowerLogic ION7413, DC, for DIN rail if you choose payment in advance on ordering.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.
Fitting accessory for Schneider Electric METSEION7413 power analyzer PowerLogic ION7413, DC, for DIN rail
|
Schneider Electric METSEPM89M0024 I/O module analog 4 inputs + 2 outputs
Optional input output module compatible with PowerLogic PM8000, ION7400 and ION9000 devices that provides additional analog inputs and analog outputs. This analog module provides 4 analog inputs ...Lieske Part No.: 323104 Mfg Part No: METSEPM89M0024 |
-16% 449,65 EUR 533,96 EUR
![]() ≈ £375.91 | ≈ $496.86
Made to order · Delivery time approx. 8 workdaysinfo_outline
|
|
Schneider Electric METSEPMFIBER communication module, fiber optics for LWL networks
Bei diesem Gerät handelt es sich um ein optionales Modul für Advanced Messgeräte, die eine SC-Duplex-Glasfaserverbindung bieten, die vom integrierten Ethernet-Anschluss umgewandelt wird. Das ...Lieske Part No.: 1301430 Mfg Part No: METSEPMFIBER |
-16% 425,50 EUR 505,29 EUR
![]() ≈ £355.72 | ≈ $470.18
Made to order · Delivery time approx. 23 workdaysinfo_outline
|
|
Schneider Electric METSEPM89M2600 I/O module digital 6 inputs + 2 relay outputs
Optional input/output module compatible with PowerLogic PM8000, ION7400 and ION9000 devices to provide additional digital inputs and relay outputs. This digital module provides 6 digital inputs ...Lieske Part No.: 1852616 Mfg Part No: METSEPM89M2600 |
-16% 299,00 EUR 355,06 EUR
![]() ≈ £249.96 | ≈ $330.40
Made to order · Delivery time approx. 8 workdaysinfo_outline
|
|