Schneider Electric ATS490C25Y ALTIVAR soft starter ATS490 250A 208 to 690V
|
3.067,05 EUR |
|
|
( 3.649,79 EUR incl. VAT ) ≈ £2,564.05 | ≈ $3,413.63 plus delivery charges: 235,00 € |
|
| Made to order · Delivery time approx. 20 workdaysinfo_outline | |
| Datasheet: | file_download Download |
|---|---|
| Lieske Part No.: | 803714 |
| Mfg Part No: | ATS490C25Y |
| UPC/EAN: | 3606486948873 |
| Weight: | 23 kg |
More spare projector bulbs for your Toshiba Beamer
| Complementary | |
| Device connection | In the motor supply line; Inside delta |
| Overload current profile | 400 % Ie for 13 s |
| On-load factor | 50 % |
| Operating cycles/hour | 10 cyc/h |
| [Us] control circuit voltage | 110...230 V AC 50...60 Hz - 15...10 % |
| Apparent power | 90 VA |
| Integrated motor overload protection | True |
| motor thermal protection class | Class 10E |
| Protection type | Phase failure: mains; Thermal protection: starter; Thermal protection: motor; Current overload: motor; Motor underload: motor; Excessive acceleration time: motor; Motor phase loss detection: motor; Protection against line phase inversion: mains; External thermal protection: motor; Protection delta inside wiring: starter; Short-circuit between motor phase and earth: motor |
| current limiting %In (5 x Ie maximum) | 150…700 % |
| Rated current pwr loss specification | 250 A |
| Power loss static current independent | 19 W |
| Power loss per device current dependent | 64 W |
| Power loss during starting | 3034 W during starting at 40 °C at 400% Ie |
| Standards | EN/IEC 60947-4-2; UL 60947-4-2; IEC 60664-1 |
| Product certifications | CE; cULus; UKCA; RCM; CCC; DNV; ATEX; EAC; KC |
| Marking | CE; CULus; UKCA; RCM; CCC; ATEX; EAC; KC |
| [Uc] control circuit voltage | 24 V DC |
| Discrete input number | 5 |
| Discrete input type | (DI1) digital input, 4.4 kOhm; (DI2) digital input, 4.4 kOhm; (DI3) digital input, 4.4 kOhm; (DI4) digital input, 4.4 kOhm; (STO) digital input, > 1 kOhm |
| Input compatibility | DI1: discrete input level 1 PLC conforming to EN/IEC 61131-2; DI2: discrete input level 1 PLC conforming to EN/IEC 61131-2; DI3: discrete input level 1 PLC conforming to EN/IEC 61131-2; DI4: discrete input level 1 PLC conforming to EN/IEC 61131-2; STO: discrete input level 1 PLC conforming to EN/IEC 61131-2 |
| Discrete input logic | Digital input DI1 at State 0: 0...< 5 V and 11 V, >= 5 mA; Digital input DI2 at State 0: 0...< 5 V and 11 V, >= 5 mA; Digital input DI3 at State 0: 0...< 5 V and 11 V, >= 5 mA; Digital input DI4 at State 0: 0...< 5 V and 11 V, >= 5 mA; Digital input STO at State 0: 0...< 5 V and 11 V, >= 5 mA |
| Relay output number | 3 |
| Relay output type | Relay outputs R1A, R1C NO; Relay outputs R2A, R2C NO; Relay outputs R3A, R3C NO |
| Minimum switching current | 100 mA at 12 V DC for relay outputs |
| Maximum switching current | Relay outputs 2 A / 250 V AC for AC-15 100000 cycles following IEC 60947-5-1; Relay outputs 2 A / 30 V DC for DC-13 150000 cycles following IEC 60947-5-1 |
| Discrete output number | 2 |
| Discrete output type | Programmable digital output DQ1 |
| Output compatibility | Open collector level 1 PLC conforming to IEC 65A-68 |
| Analogue input number | 1 |
| Analogue input type | AI1/PTC1 : PTC/PT 100/PT 1000/KTY84 temperature probe; PTC2 : PTC/PT 100/PT 1000/KTY84 temperature probe; PTC3 : PTC/PT 100/PT 1000/KTY84 temperature probe |
| Analogue output number | 1 |
| Analogue output type | Current output AQ1 : 0...20 mA/4...20 mA , impedance< 500 Ohm; Voltage output AQ1 : 0...10 V , impedance> 470 Ohm |
| Connector type | 1 RJ45 for connecting Modbus serial; 1 RJ45 for connecting Modbus TCP/EtherNet/IP |
| Physical interface | 2-wire RS 485; 100-BASE-TX category 5 or industrial Ethernet |
| Transmission frame | RTU; TCP/UDP |
| Transmission rate | 4.8…38.4 kbps; 100 BASE TX |
| Data format | 8 bits, configurable odd, even or no parity 1or 2 stop |
| Number of addresses | 0…247 for Modbus serial |
| Method of access | Slave Modbus serial |
| Type of polarization | No impedance for Modbus serial |
| Display screen available | True |
| Operating position | Vertical +/- 10 degree |
| Height | 443 mm |
| Width | 206 mm |
| Depth | 265 mm |
| Net weight | 19 kg |
| internal bypass | True |
| Function available | Pre-heating; Smoke extraction; Second motor set; Deceleration with torque control; Braking; Boost; Line contactor control; Reverse contactor control; Anti-jam; Jog; Borehole pump starting; Condition monitoring; Power monitoring; Cybersecure firmware update |
| material declaration | True |
| Contractual warranty | |
| Warranty (in months) | 18 |
| Environment | |
| Pollution degree | Level 3 |
| [Uimp] rated impulse withstand voltage | 6 kV |
| [Ui] rated insulation voltage | 690 V |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3; Class 3S3 according to IEC 60721-3-3 |
| Ambient air temperature for operation | -25…40 °C (without derating); 40…60 °C (with current derating of 1 % per °C above 40 °C) |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air transport temperature | -40…70 °C |
| Operating altitude | 2000...4800 m with current derating 1 % per 100 m above 2000 m |
| Relative humidity | 5…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3 |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Maximum deflection under vibratory load (during storage) | 1.75 mm at 2...9 Hz |
| Maximum deflection under vibratory load (during transport) | 1.75 mm at 2...9 Hz |
| Maximum acceleration under vibrational stress (during operation) | 1 gn at 13…200 Hz |
| Maximum acceleration under vibratory load (during storage) | 1 gn at 9…200 Hz; 1.5 gn at 200…500 Hz |
| Maximum acceleration under vibratory load (during transport) | 1 gn at 9…200 Hz; 1.5 gn at 200…500 Hz |
| Maximum acceleration under shock impact (during operation) | 15 gn at 11 ms |
| Maximum acceleration under shock load (during storage) | 10 gn at 11 ms |
| Maximum acceleration under shock load (during transport) | 10 gn at 11 ms |
| Logistical informations | |
| Country of origin | ID |
| Main | |
| Range of product | Altivar Soft Starter ATS490 |
| Product or component type | Soft starter |
| Product destination | Asynchronous motors |
| Product specific application | Process and infrastructures |
| Device short name | ATS490 |
| Network number of phases | 3 phases |
| Utilisation category | AC-3A; AC-53A |
| Ue power supply voltage | 208...690 V AC (- 15...10 %) |
| power supply frequency | 50...60 Hz - 20...20 % |
| [Ie] rated operational current | Normal duty: 250 A in line (at |
| Service factor at Ie | 100 |
| rated current in heavy duty | 210 A at 40 °C for heavy duty |
| Torque control | True |
| IP degree of protection | IP00 |
| Motor power hp | 75 hp at 208 V normal duty; 100 hp at 230 V normal duty; 200 hp at 460 V normal duty; 250 hp at 575 V normal duty; 60 hp at 208 V heavy duty; 75 hp at 230 V heavy duty; 150 hp at 460 V heavy duty; 200 hp at 575 V heavy duty |
| With safety function Safe torque off (STO) | True |
| Safe Torque Off (STO) | STO (safe torque off): SIL 1 conforming to IEC 61508; STO (safe torque off): PL c/category 2 conforming to ISO 13849 |
| Cybersecurity functions | True |
| Cybersecurity level and standard | Security level (SL) 1 conforming to IEC 62443-4-2 |
| Communication port protocol | Modbus serial; Modbus TCP/EtherNet/IP |
| Option card | Communication module for CANopen daisy chain; Communication module for CANopen Sub-D; Communication module for CANopen open style; Communication module for Profibus DP V1; Communication module for PROFINET |
| Packing Units | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 26.200 cm |
| Package 1 Width | 47.500 cm |
| Package 1 Length | 58.000 cm |
| Package 1 Weight | 23.000 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 3 |
| Package 2 Height | 61.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 90.400 kg |
Questions & answers
What is the delivery time of Schneider Electric ATS490C25Y ALTIVAR soft starter ATS490 250A 208 to 690V?
The article Schneider Electric ATS490C25Y ALTIVAR soft starter ATS490 250A 208 to 690V is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Schneider Electric ATS490C25Y to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Schneider Electric ATS490C25Y ALTIVAR soft starter ATS490 250A 208 to 690V always at the best possible price. We can give you a discount of 2% on Schneider Electric ATS490C25Y ALTIVAR soft starter ATS490 250A 208 to 690V if you choose payment in advance on ordering.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.