| Complementary |
| Device connection | In the motor supply line; Inside delta |
| Overload current profile | 400 % Ie for 13 s |
| On-load factor | 50 % |
| Operating cycles/hour | 10 cyc/h |
| [Us] control circuit voltage | 110...230 V AC 50...60 Hz - 15...10 % |
| Apparent power | 90 VA |
| Integrated motor overload protection | True |
| motor thermal protection class | Class 10E |
| Protection type | Phase failure: mains; Thermal protection: starter; Thermal protection: motor; Current overload: motor; Motor underload: motor; Excessive acceleration time: motor; Motor phase loss detection: motor; Protection against line phase inversion: mains; External thermal protection: motor; Protection delta inside wiring: starter; Short-circuit between motor phase and earth: motor |
| current limiting %In (5 x Ie maximum) | 150…700 % |
| Rated current pwr loss specification | 250 A |
| Power loss static current independent | 19 W |
| Power loss per device current dependent | 64 W |
| Power loss during starting | 3034 W during starting at 40 °C at 400% Ie |
| Standards | EN/IEC 60947-4-2; UL 60947-4-2; IEC 60664-1 |
| Product certifications | CE; cULus; UKCA; RCM; CCC; DNV; ATEX; EAC; KC |
| Marking | CE; CULus; UKCA; RCM; CCC; ATEX; EAC; KC |
| [Uc] control circuit voltage | 24 V DC |
| Discrete input number | 5 |
| Discrete input type | (DI1) digital input, 4.4 kOhm; (DI2) digital input, 4.4 kOhm; (DI3) digital input, 4.4 kOhm; (DI4) digital input, 4.4 kOhm; (STO) digital input, > 1 kOhm |
| Input compatibility | DI1: discrete input level 1 PLC conforming to EN/IEC 61131-2; DI2: discrete input level 1 PLC conforming to EN/IEC 61131-2; DI3: discrete input level 1 PLC conforming to EN/IEC 61131-2; DI4: discrete input level 1 PLC conforming to EN/IEC 61131-2; STO: discrete input level 1 PLC conforming to EN/IEC 61131-2 |
| Discrete input logic | Digital input DI1 at State 0: 0...< 5 V and 11 V, >= 5 mA; Digital input DI2 at State 0: 0...< 5 V and 11 V, >= 5 mA; Digital input DI3 at State 0: 0...< 5 V and 11 V, >= 5 mA; Digital input DI4 at State 0: 0...< 5 V and 11 V, >= 5 mA; Digital input STO at State 0: 0...< 5 V and 11 V, >= 5 mA |
| Relay output number | 3 |
| Relay output type | Relay outputs R1A, R1C NO; Relay outputs R2A, R2C NO; Relay outputs R3A, R3C NO |
| Minimum switching current | 100 mA at 12 V DC for relay outputs |
| Maximum switching current | Relay outputs 2 A / 250 V AC for AC-15 100000 cycles following IEC 60947-5-1; Relay outputs 2 A / 30 V DC for DC-13 150000 cycles following IEC 60947-5-1 |
| Discrete output number | 2 |
| Discrete output type | Programmable digital output DQ1 |
| Output compatibility | Open collector level 1 PLC conforming to IEC 65A-68 |
| Analogue input number | 1 |
| Analogue input type | AI1/PTC1 : PTC/PT 100/PT 1000/KTY84 temperature probe; PTC2 : PTC/PT 100/PT 1000/KTY84 temperature probe; PTC3 : PTC/PT 100/PT 1000/KTY84 temperature probe |
| Analogue output number | 1 |
| Analogue output type | Current output AQ1 : 0...20 mA/4...20 mA , impedance< 500 Ohm; Voltage output AQ1 : 0...10 V , impedance> 470 Ohm |
| Connector type | 1 RJ45 for connecting Modbus serial; 1 RJ45 for connecting Modbus TCP/EtherNet/IP |
| Physical interface | 2-wire RS 485; 100-BASE-TX category 5 or industrial Ethernet |
| Transmission frame | RTU; TCP/UDP |
| Transmission rate | 4.8…38.4 kbps; 100 BASE TX |
| Data format | 8 bits, configurable odd, even or no parity 1or 2 stop |
| Number of addresses | 0…247 for Modbus serial |
| Method of access | Slave Modbus serial |
| Type of polarization | No impedance for Modbus serial |
| Display screen available | True |
| Operating position | Vertical +/- 10 degree |
| Height | 443 mm |
| Width | 206 mm |
| Depth | 265 mm |
| Net weight | 19 kg |
| internal bypass | True |
| Function available | Pre-heating; Smoke extraction; Second motor set; Deceleration with torque control; Braking; Boost; Line contactor control; Reverse contactor control; Anti-jam; Jog; Borehole pump starting; Condition monitoring; Power monitoring; Cybersecure firmware update |
| material declaration | True |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Pollution degree | Level 3 |
| [Uimp] rated impulse withstand voltage | 6 kV |
| [Ui] rated insulation voltage | 690 V |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3; Class 3S3 according to IEC 60721-3-3 |
| Ambient air temperature for operation | -25…40 °C (without derating); 40…60 °C (with current derating of 1 % per °C above 40 °C) |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air transport temperature | -40…70 °C |
| Operating altitude | 2000...4800 m with current derating 1 % per 100 m above 2000 m |
| Relative humidity | 5…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3 |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Maximum deflection under vibratory load (during storage) | 1.75 mm at 2...9 Hz |
| Maximum deflection under vibratory load (during transport) | 1.75 mm at 2...9 Hz |
| Maximum acceleration under vibrational stress (during operation) | 1 gn at 13…200 Hz |
| Maximum acceleration under vibratory load (during storage) | 1 gn at 9…200 Hz; 1.5 gn at 200…500 Hz |
| Maximum acceleration under vibratory load (during transport) | 1 gn at 9…200 Hz; 1.5 gn at 200…500 Hz |
| Maximum acceleration under shock impact (during operation) | 15 gn at 11 ms |
| Maximum acceleration under shock load (during storage) | 10 gn at 11 ms |
| Maximum acceleration under shock load (during transport) | 10 gn at 11 ms |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Altivar Soft Starter ATS490 |
| Product or component type | Soft starter |
| Product destination | Asynchronous motors |
| Product specific application | Process and infrastructures |
| Device short name | ATS490 |
| Network number of phases | 3 phases |
| Utilisation category | AC-3A; AC-53A |
| Ue power supply voltage | 208...690 V AC (- 15...10 %) |
| power supply frequency | 50...60 Hz - 20...20 % |
| [Ie] rated operational current | Normal duty: 250 A in line (at |
| Service factor at Ie | 100 |
| rated current in heavy duty | 210 A at 40 °C for heavy duty |
| Torque control | True |
| IP degree of protection | IP00 |
| Motor power hp | 75 hp at 208 V normal duty; 100 hp at 230 V normal duty; 200 hp at 460 V normal duty; 250 hp at 575 V normal duty; 60 hp at 208 V heavy duty; 75 hp at 230 V heavy duty; 150 hp at 460 V heavy duty; 200 hp at 575 V heavy duty |
| With safety function Safe torque off (STO) | True |
| Safe Torque Off (STO) | STO (safe torque off): SIL 1 conforming to IEC 61508; STO (safe torque off): PL c/category 2 conforming to ISO 13849 |
| Cybersecurity functions | True |
| Cybersecurity level and standard | Security level (SL) 1 conforming to IEC 62443-4-2 |
| Communication port protocol | Modbus serial; Modbus TCP/EtherNet/IP |
| Option card | Communication module for CANopen daisy chain; Communication module for CANopen Sub-D; Communication module for CANopen open style; Communication module for Profibus DP V1; Communication module for PROFINET |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 26.200 cm |
| Package 1 Width | 47.500 cm |
| Package 1 Length | 58.000 cm |
| Package 1 Weight | 23.000 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 3 |
| Package 2 Height | 61.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 90.400 kg |