Dold 0067688 PI9260.92/200/06 AC48-480V 30/25A semiconductor contactor UH=AC100-240V
|
168,36 EUR |
|||||||||||
|
( 200,35 EUR incl. VAT ) ≈ £141.09 | ≈ $184.86 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1001568 | ||||||||||
| Mfg Part No: | 0067688 | ||||||||||
| UPC/EAN: | 4030641676889 | ||||||||||
| Weight: | 0.97 kg | ||||||||||
| Type: | PI9260.92/200/06 AC48-480V 30/25A | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0067688:
Applications
This semiconductor contactor is intended for use in systems requiring frequent, wear-free, and noiseless switching operations. Typical applications include controlling heating systems, cooling systems, valves, and lighting systems. The noiseless and vibration-free operation makes it particularly suitable for environments where mechanical switches cause problems due to noise or mechanical stress. The high switching frequency and long service life reduce maintenance requirements and downtime.
Functions and Features in Detail
The device is equipped with two antiparallel thyristors per pole, enabling safe switching of alternating current loads. The DCB technology (Direct-Copper-Bonding process) ensures excellent heat transfer, allowing high load currents to be dissipated stably over extended periods. The self-releasing box terminals simplify installation and ensure a secure electrical connection. An LED indicator displays the status of the control input, supporting diagnostics during operation.
Technology Explained Simply
Control is achieved via a digital input that can be operated with AC or DC voltage. The control voltage range is AC 100–230 V, enabling control via PLC systems or simple temperature controllers. The load voltage is AC 48–480 V, and the load current is 30/30 A. The peak blocking voltage reaches up to 1600 Vp, ensuring high electrical strength and stability under load conditions. The device complies with IEC/EN 60947-4-3 standards and carries the UL-listed C/US certification, enabling use in specific markets. The IP20 shock protection class protects against direct contact with moving parts, but is not suitable for outdoor use or in damp environments.
Compatibility and Accessories
The semiconductor contactor is available in a 2-pole configuration and can be mounted on existing cooling surfaces. The version with integrated heat sink is designed for mounting on a DIN rail. For optimal heat dissipation, sufficient ventilation and cooling within the enclosure must be ensured, especially when multiple devices are mounted side by side. The use of special superflink fuses for short-circuit protection is recommended depending on the application.
Mounting and Installation
Mounting is done by snapping the heat sink onto a DIN rail. The terminals are designed for easy and secure connections. Control is via the digital input, which can be operated with AC or DC. The LED indicator allows visual inspection of the operating status. Adherence to cooling requirements is crucial for operational safety.
Operational Advantages
The device features high EMC resistance, minimising network interference. The high switching frequency and long service life reduce maintenance intervals. The noiseless and vibration-free operation ensures a quiet working environment. The DCB technology ensures efficient heat dissipation, increasing reliability under load. The device is supplied without thermal protection, making it suitable for applications where automatic shutdown due to overheating is not required.
| Technical data | |
| Auxiliary voltage | DC 24 V |
| Load current up to | 60 A |
| Load voltage up to | AC 600 V |
| Number of poles | 2-pole, 3-pole |
| On/Off Input Control | AC, DC |
| Peak reverse voltage up to | 1600 Vp |
| Width | 67,5 mm |
| Type | PI 9260 |
| Variant | |
| Control voltage | AC 100 - 230 V |
| Load current | 30 / 30 A |
| Load voltage | AC 48 - 480 V |
| Semiconductor output | 2-pole |
| Approvals and Markings | UL-listed C/US |
| Variant | Switching at zero crossing. With high I2t-value > 18000 A2s. Without temperature protection. With heat sink |
Questions & answers
What is the delivery time of Dold 0067688 PI9260.92/200/06 AC48-480V 30/25A semiconductor contactor UH=AC100-240V?
The article Dold 0067688 PI9260.92/200/06 AC48-480V 30/25A semiconductor contactor UH=AC100-240V is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0067688 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0067688 PI9260.92/200/06 AC48-480V 30/25A semiconductor contactor UH=AC100-240V always at the best possible price. We can give you a discount of 2% on Dold 0067688 PI9260.92/200/06 AC48-480V 30/25A semiconductor contactor UH=AC100-240V if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 5 pieces of Dold 0067688 PI9260.92/200/06 AC48-480V 30/25A semiconductor contactor UH=AC100-240V we can offer you a price of 160,78 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.