Dold 0067354 PH9260.91/000/01 AC48-600V AC25A semiconductor contactor UH=DC4-32V
|
109,82 EUR |
|||||||||||
|
( 130,69 EUR incl. VAT ) ≈ £92.03 | ≈ $120.58 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1001593 | ||||||||||
| Mfg Part No: | 0067354 | ||||||||||
| UPC/EAN: | 4030641673543 | ||||||||||
| Weight: | 0.52 kg | ||||||||||
| Type: | PH9260.91/000/01 AC48-600V AC25A | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0067354:
Applications
This device is designed for use in machine building and automation technology, particularly in plants of the plastics and rubber industry, packaging machines, soldering systems, and in the food industry. It is suitable for switching heating elements, motors, valves, and lighting systems where high switching frequency and long service life are required. The zero-voltage switching version minimizes electrical interference and extends the service life of load components.
Functions and equipment in detail
The semiconductor relay operates with two antiparallel-connected thyristors, which are standardly operated in zero-voltage switching mode. This means that the output is activated at the next zero crossing of the sinusoidal mains voltage as soon as the control voltage is applied. After switching off the control voltage, deactivation also occurs at the next zero crossing of the load current. The LED status indicator signals the state of the control input. The DCB technology (Direct-Copper-Bonding process) ensures excellent heat transfer, reducing thermal stress and increasing reliability.
Technology explained simply
The use of thyristors enables contactless switching, avoiding wear and noise. The zero-voltage switching function ensures that current flow begins at minimal voltage, reducing stress on the load and the relay. The peak blocking voltage is 1200 V or 1600 V, and the insulation voltage is 4000 V, ensuring high electrical safety. The shock protection class IP20 protects against direct contact with conductive parts. The box terminals allow for secure and easy connection of wires.
Compatibility and accessories
The device is compliant with IEC/EN 60947-4-3 and designed for use in industrial environments. Optionally, it is available with overtemperature protection, where a temperature limit switch (normally open) can be inserted into a designated pocket on the underside. If the heatsink temperature exceeds the limit (e.g. 100 °C), the switch opens and protects the device. Mounting is done on the DIN rail, with the heatsink snap-fitting into place. The maximum load current is 125 A (AC-51), with the limiting load integral value (I²t) reaching up to 18000 A²s.
Mounting and installation
Mounting is done on the DIN rail, with the heatsink snapping directly into place. The box terminals allow for easy and secure connection of wires. The operating temperature range is from -20 °C to +40 °C, and the storage temperature range is from -20 °C to +80 °C. The mechanical durability is designed for vibrations with an amplitude of 0.35 mm and a frequency of 10 to 55 Hz, in accordance with IEC/EN 60068-2-6.
Advantages in operation
The device offers high switching capacity with minimal wear, as it operates contactlessly. The zero-voltage switching function reduces electrical interference and extends the service life of load components. The DCB technology ensures efficient heat dissipation, increasing operational safety. The LED indicator allows for quick status checking. Compatibility with various control voltages (DC 4–32 V) and compliance with IEC/EN 60947-4-3 standards make this device a reliable solution for industrial applications.
| Technical data | |
| Load current up to | 125 A |
| Load voltage up to | AC 600 V |
| Number of poles | 1-pole |
| On/Off Input Control | AC/DC, DC |
| Width | 45 mm |
| Type | PH 9260 |
| Variant | |
| Control voltage | DC 4 - 32 V |
| Load current | AC 25 A |
| Load voltage | AC 48 - 600 V |
| Semiconductor output | 1-pole |
| Variant | Switching at zero crossing. With heat sink |
Questions & answers
What is the delivery time of Dold 0067354 PH9260.91/000/01 AC48-600V AC25A semiconductor contactor UH=DC4-32V?
The article Dold 0067354 PH9260.91/000/01 AC48-600V AC25A semiconductor contactor UH=DC4-32V is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0067354 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0067354 PH9260.91/000/01 AC48-600V AC25A semiconductor contactor UH=DC4-32V always at the best possible price. We can give you a discount of 2% on Dold 0067354 PH9260.91/000/01 AC48-600V AC25A semiconductor contactor UH=DC4-32V if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 5 pieces of Dold 0067354 PH9260.91/000/01 AC48-600V AC25A semiconductor contactor UH=DC4-32V we can offer you a price of 104,88 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.