Dold 0062796 LG7928.97/61 AC/DC24V 1-10S delay module, drop-out delayed
|
261,74 EUR |
|||||||||||
|
( 311,47 EUR incl. VAT ) ≈ £219.08 | ≈ $287.65 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1153834 | ||||||||||
| Mfg Part No: | 0062796 | ||||||||||
| UPC/EAN: | 4030641627966 | ||||||||||
| Weight: | 0.2 kg | ||||||||||
| Type: | LG7928.97/61 AC/DC24V 1-10S | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0062796:
Applications
This module is used in systems where controlled, time-delayed shutdown is required, for example, during machine shutdown or drive disconnection after emergency stop activation. It is suitable for applications requiring high long-term stability and reliability, particularly in manufacturing and processing industries. The function of delayed de-energization ensures that the output returns to its resting state only after a set delay time following the deactivation of the input signal.
Functions and Equipment in Detail
The device features contact configuration with 3 NO contacts and 2 NC contacts, where the output contacts are forced-guided. This ensures secure signal transmission, even in the event of mechanical disturbances. The connection technology includes fixed screw terminals, as well as optional removable spring-cage terminals and removable screw terminals, enabling flexible installation and maintenance. Wire connections can be made with stranded wires up to 2 x 1.5 mm² with ferrules and plastic collars, or with solid conductors up to 2 x 2.5 mm² in accordance with DIN 46228-1/-2/-3/-4. LED indicators for Channel 1, Channel 2, and supply voltage provide visual status indication and facilitate diagnostics.
Technology Explained Simply
The time delay is digitally controlled, ensuring high long-term stability and minimal deviation over time. The delay time is adjustable and can be set within the range of 1 to 10 seconds depending on requirements. The maximum time delay is 600 seconds, with the exact setting varying according to application. The nominal voltage is AC/DC 24 V, enabling universal use in many industrial control systems. The thermal current Ith max. is 5 A, defining the maximum load capacity of the contacts.
Compatibility and Accessories
The module is designed for use in conjunction with suitable switching devices and controls in safety applications. It meets requirements up to Category 3 and PL d according to EN ISO 13849-1, as well as SIL 2 according to IEC/EN 62061. Certifications include UL-listed C/US, TÜV, and CCC, enabling use in various markets. Optional plug-in terminal blocks are available, allowing for quick device replacement.
Mounting and Installation
Mounting is performed in standard control panels with a module width of 22.5 mm. The standard terminal type is fixed screw terminals, with removable spring-cage and screw terminals available as optional. The terminals are designed for use with stranded and solid conductors in accordance with DIN 46228. Installation is carried out by direct connection to the control system and load, with LED indicators used to check operational states.
Advantages in Operation
The adjustable time delay allows precise adaptation to the specific requirements of the system. The forced-guided contacts ensure high safety, as contact failure can be detected and signaled. LED indicators simplify maintenance and fault diagnosis. The compact design and universal power supply (AC/DC 24 V) make the module a flexible solution for various industrial applications. Certifications according to UL, TÜV, and CCC ensure compliance with international safety standards.
More spare projector bulbs for your Epson Beamer
| Technical data | |
| 1- / 2-channel | 1 |
| Approvals | UL |
| Cat. / PL acc. to EN ISO 13849-1 | 3/d |
| Connection | Pluggable cage clamp terminals, Pluggable screw terminals, Screw terminals |
| Output contacts max. | 1 NC contact, 4 NO contacts |
| SIL CL acc. to IEC/EN 62061 | 2 |
| SIL acc. to IEC/EN 62061 | 2 |
| Thermal current Ith max. | 5 A |
| Time delay max. | 600 s |
| Width | 22,5 mm |
| Type | LG 7928 |
| Variant | |
| Contact equipping | 3 NO contacts, 2 NC contacts |
| Nominal voltage | AC/DC 24 V |
| Terminal type | fixed terminal blocks with screw terminals |
| Time range | 1 - 10 s |
| Approvals and Markings | UL-listed C/US, TÜV, CCC |
| Variant | Time delay, adjustable |
Questions & answers
What is the delivery time of Dold 0062796 LG7928.97/61 AC/DC24V 1-10S delay module, drop-out delayed?
The article Dold 0062796 LG7928.97/61 AC/DC24V 1-10S delay module, drop-out delayed is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0062796 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0062796 LG7928.97/61 AC/DC24V 1-10S delay module, drop-out delayed always at the best possible price. We can give you a discount of 2% on Dold 0062796 LG7928.97/61 AC/DC24V 1-10S delay module, drop-out delayed if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0062796 LG7928.97/61 AC/DC24V 1-10S delay module, drop-out delayed we can offer you a price of 249,96 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.