Dold 0062759 RK9871.72 3/N AC400/230V 50/60Hz undervoltage relay
|
131,87 EUR |
|||||||||||
|
( 156,93 EUR incl. VAT ) ≈ £110.38 | ≈ $144.93 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1153820 | ||||||||||
| Mfg Part No: | 0062759 | ||||||||||
| UPC/EAN: | 4030641627591 | ||||||||||
| Weight: | 0.123 kg | ||||||||||
| Type: | RK9871.72 3/N AC400/230V 50/60HZ | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0062759:
Applications
This relay is designed for use in single-phase and three-phase networks and can be used in both single-phase and three-phase systems. In single-phase operation, terminals L1, L2, and L3 must be connected together; in two-phase operation, L2 and L3 must be connected. Measurement is performed via the arithmetic mean of the three phase voltages against the neutral conductor. It is designed for nominal voltages of 3/N AC 400/230 V and operates in the frequency range of 45 to 65 Hz. The overload capacity is 1.15 times the nominal voltage continuously.
Functions and Equipment in Detail
The device operates on the standby current principle, meaning the output relay is not activated in the event of a fault. Undervoltage detection occurs at a fixed pickup value of 195.5 V. The switching threshold is not adjustable but is fixed. Detection occurs when the voltage on one or more phases remains below the threshold for longer than 0.5 seconds. After detection, the relay drops out. Return to the normal state occurs only when the voltage remains above the threshold for at least 1 minute. During this waiting period, the yellow LED blinks. The LED indicators also show the operating voltage (green LED) and contact position (yellow LED). An optional test button is available to check functionality.
Technology Explained Simply
The nominal power consumption is approximately 6 VA. The contact configuration includes 2 changeover contacts, suitable for operating safety functions. The thermal current rating is 4 A. The switching capacity according to AC 15 is 2 A / AC 230 V for closing contacts and 1 A / AC 230 V for opening contacts. The electrical life expectancy is at least 100,000 switching operations at 1 A and AC 230 V. The hysteresis is approximately 5 %, accuracy ±5 %, and repeatability is less than 2 %. The temperature influence on measurement is less than 1 %. The overvoltage category is III according to IEC 60664-1.
Compatibility and Accessories
The device is compliant with installations according to DIN VDE 0100-718:2005-10 and DIN VDE 0108-100:2005-01. It conforms to the standard IEC/EN 60255-1. The width is 17.5 mm, making it suitable for installation in standard installation distributors. Terminal markings are designated L1, L2, L3, N for the input side and 11, 12, 14 as well as 21, 22, 24 for the two output relays. The connection terminals are designed for use in distributors.
Mounting and Installation
Mounting is done in an installation distributor. Connections must be made in a de-energized state. Terminals L1, L2, and L3 must be connected according to the connection type. The connection terminals are designed for use in distributors. Mounting and wiring must comply with local, legal, and technical regulations (e.g. VDE, TÜV, occupational safety associations). Adjustments may only be performed by qualified personnel following safety regulations.
Operational Advantages
The relay increases safety in buildings by automatically switching to a safety power supply during voltage dips. The LED indicators allow for quick visual monitoring of the operating status. The fixed time delay of 0.5 seconds for fault detection and 1 minute for returning to normal state ensures stable and reliable response. The integrated power supply from the measured voltage reduces the number of required auxiliary lines. The width of 17.5 mm allows for compact installation in standard distribution boxes.
More spare projector bulbs for your Epson Beamer
| Technical data | |
| 1- / 3-phase | 1, 3 |
| Auxiliary voltage | Without |
| Enclosure design | Distribution board |
| Nominal voltage max. | 3/N AC 400 / 230 V |
| Output contacts | 1 C/O contact, 2 C/O contacts |
| Width | 17,5 mm |
| Type | RK 9871 |
| Operate delay | |
| Variant | |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | 3/N AC 400 / 230 V |
| Variant | De-Energized on trip |
Questions & answers
What is the delivery time of Dold 0062759 RK9871.72 3/N AC400/230V 50/60Hz undervoltage relay?
The article Dold 0062759 RK9871.72 3/N AC400/230V 50/60Hz undervoltage relay is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0062759 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0062759 RK9871.72 3/N AC400/230V 50/60Hz undervoltage relay always at the best possible price. We can give you a discount of 2% on Dold 0062759 RK9871.72 3/N AC400/230V 50/60Hz undervoltage relay if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 5 pieces of Dold 0062759 RK9871.72 3/N AC400/230V 50/60Hz undervoltage relay we can offer you a price of 125,94 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.