Product information for Dold 0054502:
Applications
This phase monitor is designed for monitoring 3/N-AC networks with a nominal voltage of 400/230 V and a frequency of 50/60 Hz. It is used in industrial and commercial installations where power interruption can lead to production downtime or damage to drive technology. The devices are designed for continuous operation and function within a temperature range of -20 °C to +60 °C. The operating altitude is limited to a maximum of 2000 m above sea level.
Functions and Equipment in Detail
The device detects undervoltage at approximately 70 % of nominal voltage (0.7 ± 0.15 x U_N) and responds to an asymmetry of approximately 20° angular asymmetry. The response delay is 100 to 300 ms, and the switching-on delay is 15 to 30 ms. When a network fault is detected, the output contact 11-14 (or 21-24 for the second contact stage) opens. The device operates on the residual current principle, meaning the output relay is not activated in the event of a fault. Indication is provided via two green LEDs: the left LED indicates the operating voltage, and the right LED indicates correct measurement voltage. Both LEDs illuminate during fault-free operation.
Technology Explained Simply
The current consumption is approximately 7 mA at L1 and L2, and approximately 1.5 mA at L3. The nominal power consumption is about 3.5 VA. The contact configuration includes two changeover contacts (IL9087.12), made of a silver-nickel alloy contact material (AgNi 0.15 + 0.3 μm AU). The switching capacity is rated at AC 15 3 A / AC 230 V for closing contacts and 1 A / AC 230 V for opening contacts. The electrical life at 1 A and AC 230 V is 600,000 switching cycles, and the mechanical life is at least 100 million switching cycles.
Compatibility and Accessories
The device is designed for mounting in installation distributors with a 35 mm mounting width. The connection terminals are located at the bottom, enabling integration into standard distributors according to DIN 43880. Devices in the IL 9087 series are available in two housing types: IL 9087 with 59 mm depth and bottom-mounted terminals, and SL 9087 with 98 mm depth and top-mounted terminals for enclosures with a mounting plate.
Mounting and Installation
Mounting is performed in a standard distributor with 35 mm mounting width. The connection terminals are designed for direct connection to network conductors L1, L2, L3, and N. Terminal marking follows the scheme 11, 12, 14 for the first changeover contact and 21, 22, 24 for the second changeover contact. Installation requires no additional auxiliary voltage, as the device is powered directly from the monitored network. Wiring is simple and requires no additional effort.
Advantages in Operation
By detecting network faults early, the phase monitor enables preventive maintenance and prevents costly damage. The operational safety and availability of the system are increased. The LED indicators provide visual feedback on the operating status. The design without auxiliary voltage reduces installation complexity and lowers maintenance costs. The device complies with IEC/EN 60255-1 and is designed for use in industrial environments with electromagnetic compatibility (EMC) according to IEC/EN 61000-4-2, -4-3, -4-4, -4-5, and -4-6. The rated impulse withstand voltage is 4 kV at pollution degree 2.
| Technical data | |
| 1- / 3-phase | 3 |
| Auxiliary voltage | Without |
| Enclosure design | Distribution board |
| Measuring range max. | 400 V |
| Output contacts | 1 C/O contact, 2 C/O contacts |
| Standard measuring range | 3/N AC 400/230 V |
| Width | 35 mm |
| Type | IL 9087 |
| Variant | |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | 3AC 400/230 V |
Questions & answers
What is the delivery time of Dold 0054502 IL9087.12 3AC 50/60 Hz 400/230 V phase monitor ?
The article Dold 0054502 IL9087.12 3AC 50/60 Hz 400/230 V phase monitor is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0054502 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0054502 IL9087.12 3AC 50/60 Hz 400/230 V phase monitor always at the best possible price. We can give you a discount of 2% on Dold 0054502 IL9087.12 3AC 50/60 Hz 400/230 V phase monitor if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 5 pieces of Dold 0054502 IL9087.12 3AC 50/60 Hz 400/230 V phase monitor we can offer you a price of 167,00 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.