| Lieske Part No.: | 1152415 | ||||||||||
| Mfg Part No: | 0053650 | ||||||||||
| UPC/EAN: | 4030641536503 | ||||||||||
| Weight: | 0.23 kg | ||||||||||
| Type: | BA9054/010 AC50-500V AC/DC80-230V | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0053650:
Applications
This relay is designed for monitoring voltages in the range of AC 50–500 V. It is suitable for applications requiring precise and reliable voltage monitoring, such as in production plants, power supply systems, or rail vehicle technology. The galvanic isolation between auxiliary circuit and measurement circuit ensures safe and interference-free measurement, even at high voltages.
Functions and Equipment in Detail
The device features 2 changeover contacts as output contacts, which can be used to control auxiliary circuits or alarm systems. The switching delay is 0 to 20 seconds and is activated once the set threshold is exceeded. This delay prevents unwanted switching operations caused by short-term voltage fluctuations. The response delay is also integrated to ensure stable reaction to voltage changes. The auxiliary voltage can be operated in both AC and AC/DC mode with 80–230 V, enabling flexible integration into existing power supply systems.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measurement voltage. For AC voltages, the device is calibrated to the RMS value, enabling accurate measurement even with sinusoidal voltages. Adjustment is performed via rotary switches, allowing both the response threshold and the hysteresis value to be set. The hysteresis depends on the set value and ensures that the relay does not trigger for minor fluctuations around the threshold. The LED indicators signal operational readiness (green LED) and activation of the output relay (yellow LED), facilitating diagnosis during operation.
Compatibility and Accessories
The relay complies with standards IEC/EN 60255-1 and IEC/EN 60947-1 and carries UKCA and CCC certifications. It is designed for a maximum rated voltage of AC 1000 V and DC 900 V, although the measurement range for this variant is limited to AC 50–500 V. The width is 45 mm, allowing installation in standard enclosures. Terminal markings include A1/A2 for auxiliary voltage, e/f for measurement connection, and contacts 11–14 and 21–24 for the two changeover contacts.
Mounting and Installation
The device is intended for installation in enclosures. Mounting is done via screw terminals, with connection markings clearly indicated on the device. Threshold adjustment is performed directly on the front via rotary switches, without requiring additional tools or accessories. The galvanic isolation between measurement and auxiliary circuit ensures safe installation even in electrically demanding environments.
Advantages in Operation
Precise and reliable voltage monitoring enables preventive maintenance and reduces the likelihood of failures. The integrated switching delay minimizes false alarms caused by short-term voltage fluctuations. The LED indicators facilitate visual monitoring during operation, and galvanic isolation enhances safety. The device is designed for high overload capacity and can measure frequencies up to 5 kHz, making it suitable for applications with pulsating or modulated voltages as well.
| Technical data | |
| 1- / 3-phase | 1 |
| Enclosure design | Switch cabinet |
| Nominal voltage max. | AC 1000 V, DC 900 V |
| Output contacts | 2 C/O contacts |
| Width | 45 mm |
| Type | BA 9054 |
| Operate delay | |
| Variant | |
| Auxiliary voltage | AC/DC 80 - 230 V |
| Contact equipping | 2 changeover contacts |
| Measuring range | AC 50 - 500 V |
| Start up delay | Without |
| Switching delay | 0 - 20 s |
| Approvals and Markings | UKCA, CCC |
| Variant | Overvoltage relay. Energized on trip. Time delay at setting value |
Questions & answers
What is the delivery time of Dold 0053650 BA9054/010 AC50-500V AC/DC80-230V voltage relay Tv=0-20s?
The article Dold 0053650 BA9054/010 AC50-500V AC/DC80-230V voltage relay Tv=0-20s is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0053650 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0053650 BA9054/010 AC50-500V AC/DC80-230V voltage relay Tv=0-20s always at the best possible price. We can give you a discount of 2% on Dold 0053650 BA9054/010 AC50-500V AC/DC80-230V voltage relay Tv=0-20s if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0053650 BA9054/010 AC50-500V AC/DC80-230V voltage relay Tv=0-20s we can offer you a price of 310,99 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.