Product information for Dold 0044430:
Applications
This relay is intended for use in industrial plants, building technology, and control systems. It is particularly suitable for applications requiring high switching power at DC voltage, such as switching motors, transformers, or other inductive loads. The design also allows use as an input coupling relay to forward signals from sensors or initiators to control devices, or as an output coupling relay to control loads via a PLC.
Functions and Equipment in Detail
The device features a switching position indicator implemented via a button on the front. This button also serves for manual actuation of the contacts. When the relay is energized, the button is pushed in, indicating the closed switching position. In the de-energized state, the black button is flush with the front edge. The contacts are actuated via a toggle armature and a plunger; after the excitation voltage drops, the armature is returned to its resting position by a spring. The maximum number of output contacts is three changeover contacts, with the current version featuring two openers.
Technology Explained Simply
The protective circuit at the coil input protects the relay against voltage spikes and prevents damage due to miscontrol. The initiator actuation enables use with 2-wire initiators, with an allowable residual current ≤ 3 mA. The maximum thermal current rating (Ith) is 16 A, ensuring high load capacity during continuous operation. The 6 mm contact opening ensures secure separation at high switching powers, especially with inductive loads. The device complies with standard EN 60947-5-1, which defines requirements for switching devices for electrical equipment.
Compatibility and Accessories
The relay is designed for use in standard installation distributors and can be combined with other devices from the IL 8701 series. It is designed for use with DC 24 V and can be operated in systems with polarized voltage supply (A1+ / A2). Terminal markings follow the standard: A1 / A2 for control signals, with DC devices observing polarity A1+ / A2+. The contacts are designed for loads in the range of 0.3 to 60 V and 1 to 300 mA, where the gold plating may be burned off for small loads, making reuse for such loads impossible.
Mounting and Installation
The relay is installed in an installation distributor, with the width of 35 mm enabling mounting in standard switchboards. The connection terminals are clearly labeled, with designations 11, 12, 14, 21, 22, 24 for the contacts. Installation is carried out by mounting in a suitable enclosure or distributor, with electrical connections to be made according to circuit diagrams and standards. The manual actuation button allows for easy functional testing without electrical supply.
Advantages in Operation
The relay offers high thermal load capacity with an Ith of 16 A, making it suitable for continuous operation. The switching position indicator and manual actuation facilitate maintenance and troubleshooting. The protective circuit at the coil input increases reliability and extends service life. The variant with 6 mm contact opening ensures secure separation at high switching powers, especially with inductive loads. The design as an installation distributor enables easy integration into existing systems.
| Technical data | |
| Enclosure design | Distribution board |
| Output contacts max. | 3 C/O contacts |
| Thermal current Ith max. | 16 A |
| Width | 35 mm |
| Type | IL 8701 |
| Initiator triggering | |
| Suppressor circuit on the coil input | |
| Variant | |
| Contact equipping | 2 NC contacts |
| Nominal voltage | DC 24 V |
| Variant | 6 mm contact opening, for switching large inductive direct current voltage loads |
Questions & answers
What is the delivery time of Dold 0044430 IL8701.06/006 DC24V switching relay?
The article Dold 0044430 IL8701.06/006 DC24V switching relay is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0044430 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0044430 IL8701.06/006 DC24V switching relay always at the best possible price. We can give you a discount of 2% on Dold 0044430 IL8701.06/006 DC24V switching relay if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 5 pieces of Dold 0044430 IL8701.06/006 DC24V switching relay we can offer you a price of 149,94 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.