Dold 0026353 BA9041 3AC50HZ 500V phase sequence relay
|
193,77 EUR |
|||||||||||
|
( 230,59 EUR incl. VAT ) ≈ £162.19 | ≈ $212.95 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 1002067 | ||||||||||
| Mfg Part No: | 0026353 | ||||||||||
| UPC/EAN: | 4030641263539 | ||||||||||
| Weight: | 0.34 kg | ||||||||||
| Type: | BA9041 3AC50HZ 500V | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0026353:
Applications
This relay is intended for use in industrial three-phase networks, particularly in plants with electric drives where correct rotation direction is critical. It is suitable for networks with a rated voltage of 3 AC 500 V at 50 Hz. The standard measurement range is 3 AC 400 V, with the device detecting voltages within 0.8 to 1.1 times the rated voltage. The operating temperature ranges from -20 °C to +60 °C, and the storage temperature is also within -20 °C to +60 °C. The operating altitude is limited to a maximum of 2000 m above sea level.
Functions and Equipment in Detail
The device features two changeover contacts (11-14 and 21-24), which close when the correct phase sequence is detected. The pickup time is less than 100 ms, and the drop-out time is less than 50 ms. The thermal current rating (Ith) is 5 A. The switching capacity according to AC 15 is 2 A at AC 230 V for closing contacts and 1 A at AC 230 V for opening contacts. The electrical life is 250,000 switching operations at 3 A and AC 230 V (cos ϕ = 1). The mechanical life is at least 50 million switching operations. The maximum fuse rating is 4 A gG / gL.
Technology Explained Simply
The relay continuously monitors the phase sequence and voltage presence. In case of incorrect sequence or phase failure, the output is deactivated. The output contacts are designed as changeover contacts, allowing flexible wiring. The operating voltage ranges from 3 AC 220 V to 500 V, with a rated voltage of 3 AC 500 V. The frequency is 50 Hz, with the option to obtain 60 Hz upon request. The rated power consumption is less than 3.5 VA. The enclosure protection rating is IP 40, and the terminals have IP 40. The housing is made of thermoplastic material with V0 flammability rating according to UL 94.
Compatibility and Accessories
The relay is designed for use in enclosures and is mounted on a DIN rail. The terminals are designed for connection with solid conductors (2 x 2.5 mm²) or stranded conductors (2 x 1.5 mm²) with heat-shrink tubing according to DIN 46228-1/-2/-3/-4. The stripping length is 10 mm. The mounting is done using flat terminals with self-lifting clamping parts according to IEC/EN 60999-1. The device is designed for continuous operation and meets the requirements of overvoltage category III up to 3 AC 480 V and category II for 3 AC 500 V. EMC requirements are fulfilled according to IEC/EN 61000-4-2 to -6, including surge voltages, high-frequency radiation, and fast transients. Radio frequency interference suppression complies with emission limit class B according to EN 55011.
Mounting and Installation
Mounting is done on a DIN rail according to IEC/EN 60715. The mounting torque is 0.8 Nm. The terminals are designed for connection with solid and stranded conductors. The stripping length is 10 mm. The connection terminals are clearly labeled: L1, L2, L3 for input lines and 11-14, 21-24 for output contacts. The width is 45 mm, and the dimensions are 45 mm (width) × 73.2 mm (height) × 119.8 mm (depth). The device weighs 310 g.
Operational Advantages
The phase sequence relay BA 9041 ensures correct rotation direction of drives and prevents damage caused by incorrect phase sequence. Simple wiring and clear indication via the green LED facilitate commissioning and maintenance. The high mechanical and electrical life ensures reliable long-term use. Compliance with the standard IEC/EN 60255-1 and fulfillment of EMC requirements ensure suitability for demanding industrial environments. The IP 40 protection rating protects against contact and dust, making the device suitable for use in enclosures. In networks with high harmonic content or commutation peaks (e.g., with thyristor-controlled drives), the relay may indicate false phase failures. In such cases, it is recommended to test the device on-site or combine it with an asymmetry relay (e.g., BA 9040).
| Technical data | |
| 1- / 3-phase | 3 |
| Enclosure design | Switch cabinet |
| Measuring range max. | 500 V |
| Output contacts | 2 C/O contacts |
| Standard measuring range | 3 AC 400 V |
| Width | 45 mm |
| Type | BA 9041 |
| Variant | |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | 3AC 500 V 50 Hz |
Questions & answers
What is the delivery time of Dold 0026353 BA9041 3AC50HZ 500V phase sequence relay?
The article Dold 0026353 BA9041 3AC50HZ 500V phase sequence relay is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0026353 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0026353 BA9041 3AC50HZ 500V phase sequence relay always at the best possible price. We can give you a discount of 2% on Dold 0026353 BA9041 3AC50HZ 500V phase sequence relay if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 5 pieces of Dold 0026353 BA9041 3AC50HZ 500V phase sequence relay we can offer you a price of 185,05 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.