Dold 0017938 AK9840.82 3AC50/60Hz 440V asymmetry relay
|
669,51 EUR |
|||||||||||
|
( 796,72 EUR incl. VAT ) ≈ £560.38 | ≈ $735.79 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 100046 | ||||||||||
| Mfg Part No: | 0017938 | ||||||||||
| UPC/EAN: | 4030641179380 | ||||||||||
| Weight: | 0.33 kg | ||||||||||
| Type: | AK9840.82 3AC50/60HZ 440V | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0017938:
Applications
This relay is suitable for monitoring three-phase networks in industry, production facilities, building technology, and emergency power supplies. It can also be used in networks with a neutral conductor, although the N connection is not required. In this case, the rated voltage must be converted to the line-to-line voltage. The device is particularly suitable for networks with high harmonic content, such as those found in thyristor installations, automatic reactive power compensation systems, or emergency power supplies. The measurement method used ensures that the harmonic content does not distort the trip values.
Functions and Features in Detail
The device detects voltage asymmetry by measuring the difference between two voltages. It does not respond to symmetrical voltage drops as long as the undervoltage detection threshold of 0.7 times the rated voltage is not exceeded. If the set asymmetry value (5 to 20 % of the rated voltage) is exceeded or undervoltage occurs, the output relay is released after the adjustable trip delay (0.5 to 5 seconds). In the case of incorrect phase sequence, the release occurs immediately. Reverse voltage detection is also integrated; depending on network conditions, reverse feeding is recognized either as asymmetry (delayed) or as incorrect phase sequence (immediate).
Technology Explained Simply
The device operates on the standby current principle, where the output relay is activated (closed) during normal operation. In the event of a fault, it is deactivated (opened). The status indication is provided by an LED, which lights up when the output relay is active. The LED turns off when the relay trips. The trip delay is continuously adjustable to avoid false tripping due to short-term voltage fluctuations. Adjustment is made via a rotary control on the device. The measurement ranges extend from 0.7 to 1.1 times the rated voltage (at 3AC 400 V) and up to 1.2 times the rated voltage (at 3AC 440 V), with a maximum delay of 1.5 seconds.
Compatibility and Accessories
The relay is available for rated voltages from 3AC 110 to 690 V, with the variant specified here designed for 3AC 440 V. It is certified according to IEC/EN 60255-1. The contact configuration includes 2 changeover contacts, suitable for controlling auxiliary contacts or warning lights. The width is 70 mm, making it suitable for standard enclosure mounting. It can also be used for automatic switching to battery-powered emergency lighting when the mains voltage drops by 30 % (according to VDE 0108).
Mounting and Installation
Mounting is carried out in an enclosure. The connections L1, L2, L3 are used to connect to the three-phase network to be monitored. The output contacts (15-16, 15-18, 25-26, 25-28) are intended for connection to external switching devices. The LED indicator shows the status of the output relay. Settings for asymmetry and delay are adjusted directly on the device. No additional auxiliary voltages are required.
Operational Advantages
Early detection of network disturbances enables preventive maintenance and prevents damage to machines and installations. Simple installation without auxiliary voltage reduces wiring effort. High stability under harmonic load makes the device suitable for demanding industrial applications. The clear LED indication and adjustable delay increase operational safety and system availability.
Note: Batteries are not included in the delivery scope.
| Technical data | |
| 1- / 3-phase | 3 |
| Enclosure design | Switch cabinet |
| Measuring range max. | 3 AC 690 V |
| Output contacts | 2 C/O contacts |
| Standard measuring range | 3 AC 400 V |
| Width | 70 mm |
| Type | AK 9840 |
| Operate delay | |
| Variant | |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | 3AC 440 V 50/60 Hz |
Questions & answers
What is the delivery time of Dold 0017938 AK9840.82 3AC50/60Hz 440V asymmetry relay?
The article Dold 0017938 AK9840.82 3AC50/60Hz 440V asymmetry relay is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0017938 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0017938 AK9840.82 3AC50/60Hz 440V asymmetry relay always at the best possible price. We can give you a discount of 2% on Dold 0017938 AK9840.82 3AC50/60Hz 440V asymmetry relay if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 3 pieces of Dold 0017938 AK9840.82 3AC50/60Hz 440V asymmetry relay we can offer you a price of 639,38 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.