Dold 0001042 AI 897 AC45-400Hz 500V 10-80kΩ insulation monitor
|
268,13 EUR |
|||||||||||
|
( 319,07 EUR incl. VAT ) ≈ £224.42 | ≈ $294.67 plus delivery charges: 55,00 € |
|||||||||||
| On order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 100166 | ||||||||||
| Mfg Part No: | 0001042 | ||||||||||
| UPC/EAN: | 4030641010423 | ||||||||||
| Weight: | 0.245 kg | ||||||||||
| Type: | AI 897 AC45-400HZ 500V 10-80K-OHM | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Dold 0001042:
Applications
The AI 897 is used in industrial plants, manufacturing technology, medical facilities, and installations with IT networks where high electrical safety is required. It is particularly suitable for pure AC and rotating current networks, where monitoring the insulation resistance is necessary to prevent dangerous earth faults. Monitoring is performed via a measuring circuit that requires only one phase of the network, as faults on unconnected phases can be detected due to the low-ohmic coupling of phases in the supply transformer. Only one insulation monitor may be installed in a network to avoid false alarms.
Functions and Equipment in Detail
The device features a 1 changeover contact as contact configuration, used for signaling an insulation fault. The maximum switching voltage is AC 400 V, and the thermal current is 6 A. The switching capacity complies with standards IEC/EN 60947-5-1 (AC 15 and DC 13). The electrical life is at least 300,000 switching operations at 10 A and AC 250 V. The mechanical life is at least 30 million switching operations. The test button PT allows checking the device's functionality, and an external test button can be connected to PT1–PT2. An external reset button can be connected to LT1–LT2 to manually clear the alarm.
Technology Explained Simply
The insulation monitor operates with a measurement voltage of DC 18 V and a maximum measurement current of less than 0.1 mA. The response delay is less than 4.2 seconds when the resistance drops from infinite to 90 % of the threshold value at a threshold of 50 kΩ and a capacitance of 1 μF. When dropping to 0 kΩ, the delay is approximately 2 seconds. The hysteresis is approximately 50 % at 50 kΩ, meaning the alarm is triggered only when the resistance falls below the threshold and resets when it rises above the threshold. The response uncertainty is ±15 % at 50 kΩ. The device consumes approximately 2.5 VA and is designed for continuous operation.
Compatibility and Accessories
The device is certified according to IEC/EN 61557-8 and designed for pure AC and rotating current networks. It can be programmably configured for memory behavior (via bridge LT1–LT2) or hysteresis behavior (without bridge). Terminal markings include A1/A2 for connection lines, PE for protective conductor, PT1/PT2 for external test buttons, and LT1/LT2 for external reset buttons. The protection rating of the housing is IP 40, protecting against touch and solid foreign objects larger than 1 mm. The operating temperature ranges from -20 °C to +60 °C, and the storage temperature ranges from -25 °C to +70 °C. The operating altitude is limited to below 2000 m.
Mounting and Installation
The insulation monitor is designed for installation in enclosures and has a width of 45 mm. Mounting is done in standard control panels, with terminals connected according to circuit diagram specifications. Connection terminals are clearly labeled, and functions are detailed in the data sheet. Installation is performed without auxiliary voltage, reducing power supply requirements.
Advantages in Operation
The device provides reliable and low-maintenance monitoring of insulation resistance. The continuously adjustable threshold allows adaptation to different installations. The integrated test button and the option for an external reset button enhance usability. The high mechanical and electrical life ensures long operational life. Compliance with standard IEC/EN 61557-8 ensures conformity with international safety standards. The EMC immunity is certified according to IEC/EN 61000-4-2 to -4-6, ensuring reliability in electromagnetically stressed environments. The rated impulse withstand voltage is 4 kV at pollution degree 2, enhancing insulation safety. The insulation test voltage is AC 2.5 kV for 1 second.
Functions and Equipment in Detail
The device operates without auxiliary voltage, simplifying installation. The contact configuration consists of a changeover contact used for signaling a fault. The maximum switching voltage is AC 400 V, and the thermal rating is 6 A. The switching capacity complies with standards IEC/EN 60947-5-1. The electrical life is at least 300,000 switching operations at 10 A and AC 250 V. The mechanical life is at least 30 million switching operations. The test button PT allows checking functionality, and an external test button can be connected to PT1–PT2. An external reset button can be connected to LT1–LT2 to manually clear the alarm.
Technology Explained Simply
The insulation monitor operates with a measurement voltage of DC 18 V and a maximum measurement current of less than 0.1 mA. The response delay is less than 4.2 seconds when the resistance drops from infinite to 90 % of the threshold value at a threshold of 50 kΩ and a capacitance of 1 μF. When dropping to 0 kΩ, the delay is approximately 2 seconds. The hysteresis is approximately 50 % at 50 kΩ, meaning the alarm is triggered only when the resistance falls below the threshold and resets when it rises above the threshold. The response uncertainty is ±15 % at 50 kΩ. The device consumes approximately 2.5 VA and is designed for continuous operation.
Compatibility and Accessories
The device is certified according to IEC/EN 61557-8 and designed for pure AC and rotating current networks. It can be programmably configured for memory behavior (via bridge LT1–LT2) or hysteresis behavior (without bridge). Terminal markings include A1/A2 for connection lines, PE for protective conductor, PT1/PT2 for external test buttons, and LT1/LT2 for external reset buttons. The protection rating of the housing is IP 40, protecting against touch and solid foreign objects larger than 1 mm. The operating temperature ranges from -20 °C to +60 °C, and the storage temperature ranges from -25 °C to +70 °C. The operating altitude is limited to below 2000 m.
Mounting and Installation
The insulation monitor is designed for installation in enclosures and has a width of 45 mm. Mounting is done in standard control panels, with terminals connected according to circuit diagram specifications. Connection terminals are clearly labeled, and functions are detailed in the data sheet. Installation is performed without auxiliary voltage, reducing power supply requirements.
Advantages in Operation
The device provides reliable and low-maintenance monitoring of insulation resistance. The continuously adjustable threshold allows adaptation to different installations. The integrated test button and the option for an external reset button enhance usability. The high mechanical and electrical life ensures long operational life. Compliance with standard IEC/EN 61557-8 ensures conformity with international safety standards. The EMC immunity is certified according to IEC/EN 61000-4-2 to -4-6, ensuring reliability in electromagnetically stressed environments. The rated impulse withstand voltage is 4 kV at pollution degree 2, enhancing insulation safety. The insulation test voltage is AC 2.5 kV for 1 second.
| Technical data | |
| Auxiliary voltage | Without |
| Enclosure design | Switch cabinet |
| IMD type | AC |
| Nominal voltage IT system | AC 24 - 500 V |
| Response value | 10 - 80 kΩ |
| Response value type | Adjustable |
| Width | 45 mm |
| Type | AI 897 |
| Variant | |
| Alarm value | 10 - 80 kOhm |
| Contact equipping | 1 changeover contact |
| Nominal voltage | AC 500 V 45 - 400 Hz |
| Variant | Settable response value |
Questions & answers
What is the delivery time of Dold 0001042 AI 897 AC45-400Hz 500V 10-80kΩ insulation monitor?
The article Dold 0001042 AI 897 AC45-400Hz 500V 10-80kΩ insulation monitor is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0001042 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0001042 AI 897 AC45-400Hz 500V 10-80kΩ insulation monitor always at the best possible price. We can give you a discount of 2% on Dold 0001042 AI 897 AC45-400Hz 500V 10-80kΩ insulation monitor if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0001042 AI 897 AC45-400Hz 500V 10-80kΩ insulation monitor we can offer you a price of 256,06 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.